Calibrated Flow Measurement and
Balancing Valve
Sizes:
1
⁄2" – 2"
Series iDROSET CSD calibrated flow measuring and static
balancing valves are designed for hydronic heating and cooling
systems. With patented flow measurement technology inte-
grated into the valve, their large easy-to-read flow gauge and
hand wheel allow the continuous reading of flow and the setting
of flow without tools or additional instrumentation. The iDRO-
SET CSD’s ball-type design provides up to a 25:1 turn-down
ratio, positive shut-off and hand wheel locking screw to secure
adjustment.
The iDROSET CSD series is available with F-NPT connections
from ½" up to 2" with flow rate capability up to 7 GPM.
Features
• Patented integrated flow measurement technology factory
calibrated to +/- 10% accuracy
• Large gauge for easy reading of flow
• Lockable, gauge-integrated hand wheel for setting flow
• Ball valve design with positive shutoff
• Balancing turn-down ratio of up to 25:1
• Up to 7 GPM capacity
• Factory tested to +/-10% accuracy
Applications
• Fan coil units
• Water source heat pumps
• Reheat coils
• Panel coils
• Small branch lines
• Unit heaters
• Unit ventilators
• Finned radiation
• Convectors
• Small pumps
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
The information contained herein is not intended to replace the
full product installation and safety information available or the
experience of a trained product installer. You are required to thor-
oughly read all installation instructions and product safety infor-
mation before beginning the installation of this product.
NOTICE
Specifications
A calibrated flow measurement and static balancing valve shall
be installed on each hot/chilled water unit or as otherwise shown
on plans. The valve shall include integral flow measuring capabil-
ity factory calibrated to an accuracy standard of +/- 10%, flow
indicator gauge with design flow indicator, lockable hand wheel
for flow adjustment and positive shut-off capability. The valve
shall be a Watts Series iDROSET CSD