Specifications
• No power pack required.
• Power Supply Output (Terminal B):
- 24 V , 50 mA maximum.
- An auxilliary power supply must be used if the
maximum current limit is exceeded.
• Occupant Sensor Signal Input (Terminal A):
- Input must be dry contact closure or solid-state
output from the Occupant Sensor:
Dry Contact Closure from Occupant Sensor:
- Referenced to Common (Terminal C) or
Power Supply (Terminal B: 24 V ).
- Rated Voltage: 20 V when open.
- Rated Current: 0.5 mA when closed.
Solid-State Output from Occupant Sensor:
- Open collector (NPN or PNP) or
active-high/active-low.
- When open collector NPN or active-low
referenced to Common (Terminal C),
on-state voltage at Terminal A must be
less than 6 V (at 0.3 mA).
- When open collector PNP or active-high
referenced to Power Supply (Terminal B),
on-state voltage at Terminal A must be
greater than 18 V (at 0.3 mA).
- Off-state leakage current less than ±60 uA.
- Outputs must stay in the closed or open states
for at least 40 msec in order to be recognized by
the Wallstation.
• Wallstation is miswire protected up to 36 V .
• Wallstation supplies power for and receives a
control signal back from one occupant sensor.
Occupant Sensor Connection
Occupant Sensor Wiring
• Use low-voltage PELV (Class 2: USA) wiring to
connect the Occupant Sensor to the Wallstation.
Caution! A seeTouch Wallstation that is
supplying power to an occupant sensor
counts as 2 Control Station Devices
(CSDs) on the CSD link.