Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ONTARIO BUILDING CODE SUPPLEMENTARY STANDARD SB-10
PROJECT INFORMATION
Project:
Location:
Building Permit Application No.:
Date:
Architectural Designer
Information*
Mechanical Designer
Information*
Electrical Designer
Information*
Name
Name
Address
Address
City Province
City Province
Signature Date(YY/MM/DD)
Signature Date(YY/MM/DD)
*IF MORE DESIGNERS ARE INVOLVED, PROVIDE ADDITIONAL COPIES OF THIS FORM.
THIS CHECKLIST IS A CONVENIENCE DOCUMENT ONLY AND IS BASED ON THE ENERGY EFFICIENCY REQUIREMENTS DESCRIBED IN THE ONTARIO
BUILDING CODE SUPPLEMENTARY STANDARD SB-10 DIVISION 3. THIS CHECKLIST IS NOT A SUBSTITUTE FOR COMPLYING WITH THE REQUIREMENTS OF
THE ONTARIO BUILDING CODE. WHILE CARE HAS BEEN TAKEN TO ENSURE ACCURACY OF THIS CHECKLIST, DESIGNERS AND BUILDING OFFICIALS MUST
REFER TO THE ACTUAL WORDING AND REQUIREMENTS OF THE ONTARIO BUILDING CODE (O.REG. 350/06 AND AMENDMENTS UP TO AMENDING
O.REG. 315/12).
THIS CHECKLIST IS MADE AVAILABLE FOR CODE USERS BY THE MINISTRY OF MUNICIPAL AFFAIRS AND HOUSING. USERS SHOULD ALWAYS CONSULT
WITH THE AUTHORITY HAVING JURISDICTION, IF THE CHECKLIST IS GOING TO BE SUBMITTED TO THAT AUTHORITY. THE MINISTRY OF MUNICIPAL
AFFAIRS AND HOUSING DOES NOT ASSUME RESPONSIBILITY FOR ERRORS OR OVERSIGHTS RESULTING FROM THE INFORMATION CONTAINED HEREIN.
PLEASE FILL IN THE ACTUAL VALUES INSTALLED AND CHECK BOXES AS THEY APPLY.
OBC SB-10 COMPLIANCE SUMMARY
Energy Efficiency Design:
There are three energy compliance options to meet the requirements of OBC SB-10 Division 3. Please select the
compliance option selected for this project. The energy efficiency of all buildings must be designed to:
Compliance Path
Forms to
Complete
(A) Achieve the energy efficiency levels attained by conforming to the ASHRAE 90.1-2013, “Energy Standard
for Buildings Except Low-Rise Residential Buildings” and Chapter 2 of SB-10 (Division 3).
This compliance path includes both prescriptive and performance path options. Please proceed to Form A.
YES
FORM A
(B) Achieve the energy efficiency levels attained by conforming to the National Energy Code of Canada for
Buildings 2015 and Chapter 3 of SB-10 (Division 3).
This compliance path includes both prescriptive and performance path options. Please proceed to Form B.
YES
NECB
(C) Section 7 “Energy Efficiency” of 2014 ANSI/ASHRAE/USGBC/IES 189.1, excluding Sections 7.2.b, 7.4.7.3,
7.4.8 and 7.5
YES
click to sign
signature
click to edit
click to sign
signature
click to edit
click to sign
signature
click to edit
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ONTARIO BUILDING CODE SUPPLEMENTARY STANDARD SB-10
PROJECT INFORMATION ADDITIONAL DESIGNER SIGNATURES
Project:
Location:
Building Permit Application No.:
Date:
Designer Information (Other)*:
Designer Information (Other)*:
Designer Information (Other)*:
Specialty
Specialty
Name
Name
Address
Address
City Province
City Province
Signature Date(YY/MM/DD)
Signature Date(YY/MM/DD)
*AS APPLICABLE TO SB-10 2017 PROVISIONS AND REQUIREMENTS.
THIS CHECKLIST IS A CONVENIENCE DOCUMENT ONLY AND IS BASED ON THE ENERGY EFFICIENCY REQUIREMENTS DESCRIBED IN THE ONTARIO
BUILDING CODE SUPPLEMENTARY STANDARD SB-10 DIVISION 3. THIS CHECKLIST IS NOT A SUBSTITUTE FOR COMPLYING WITH THE REQUIREMENTS OF
THE ONTARIO BUILDING CODE. WHILE CARE HAS BEEN TAKEN TO ENSURE ACCURACY OF THIS CHECKLIST, DESIGNERS AND BUILDING OFFICIALS MUST
REFER TO THE ACTUAL WORDING AND REQUIREMENTS OF THE ONTARIO BUILDING CODE (O.REG. 332/12 AND AMENDMENTS UP TO AMENDING
O.REG. 194/14 AND MINISTER RULING M-16-S-27.).
THIS CHECKLIST IS MADE AVAILABLE FOR CODE USERS BY THE MINISTRY OF MUNICIPAL AFFAIRS AND HOUSING. USERS SHOULD ALWAYS CONSULT
WITH THE AUTHORITY HAVING JURISDICTION, IF THE CHECKLIST IS GOING TO BE SUBMITTED TO THAT AUTHORITY. THE MINISTRY OF MUNICIPAL
AFFAIRS AND HOUSING DOES NOT ASSUME RESPONSIBILITY FOR ERRORS OR OVERSIGHTS RESULTING FROM THE INFORMATION CONTAINED HEREIN.
click to sign
signature
click to edit
click to sign
signature
click to edit
click to sign
signature
click to edit
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
OBC SB-10 AND ASHRAE 90.1 - 2013 COMPLIANCE SUMMARY Form A
Project:
Location of Project:
Building Permit Application No.:
Climatic Zone (SB-10 Division 3 Section 1.3):
ASHRAE 90.1 2013 COMPLIANCE AS MODIFIED BY OBC SB-10 DIVISION 3
The building design complies with the mandatory provisions of the following sections regardless of the compliance path:
ASHRAE 90.1-2013 Standard Section
Compliance
Column
Form
5.4 BUILDING ENVELOPE AND SB-10 DIVISION 3
YES
FORM 5.4
6.4 HEATING, VENTILATING AND AIR CONDITIONING
YES
FORM 6.3 or
FORM 6.4
7.4 SERVICE WATER HEATING SYSTEMS AND EQUIPMENT
YES
FORM 7.4
8.4 POWER
YES
FORM 8.4
9.4 LIGHTING
YES
FORM 9.4
10.4 OTHER EQUIPMENT AND SB-10 DIVISION 3
YES
FORM 10.4
METHOD OF COMPLIANCE
Building Design must comply with either the Prescriptive Requirements or the Energy Cost Budget Method. Indicate which method was
selected.
Compliance Method
Compliance
Column
Form
PRESCRIPTIVE COMPLIANCE
YES
COMPLETE SECTION A-1
ENERGY COST BUDGET METHOD
YES
COMPLETE SECTION A-2
A-1: PRESCRIPTIVE COMPLIANCE ASHRAE 90.1-2013 AND OBC SB-10
The building design complies with the Prescriptive Compliance requirements of the following sections:
Standard Section
Reference
Compliance
Column
Form
Sec 5 BUILDING ENVELOPE Prescriptive Requirements (5.5 of 90.1)
Building Envelope Trade-Off (5.6 of 90.1)
YES
YES
FORM 5.5 or
FORM 5.6
Sec 6 HVAC SYSTEMS Simplified Approach for HVAC Systems
Mandatory + Prescriptive Path Option
YES
YES
FORM 6.3 or
FORM 6.4
Sec 7 SERVICE WATER HEATING Prescriptive Path Option
YES
FORM 7.4
Sec 9 LIGHTING Prescriptive Requirements
YES
FORM 9.5
A-2: ENERGY COST BUDGET METHOD ASHRAE 90.1-2013 AND OBC SB-10
Compliance
Column
Form
The building design complies with the provisions of Section 11 of ASHRAE 90.1-2013,
based on Division 3 of SB-10.
YES
FORM 11
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
SECTION 5.4 MANDATORY PROVISIONS
Building insulation has been designed to comply with section 5.4.1 of ASHRAE 90.1-2013 as
modified by Chapter 2 of OBC SB-10.
YES
Building fenestration and doors have been designed to comply with section 5.4.2 of ASHRAE
90.1-2013 as modified by Chapter 2 of OBC SB-10.
YES
Building air leakage has been designed to comply with section 5.4.3 of ASHRAE 90.1-2013 as
modified by Chapter 2 of OBC SB-10.
YES
ASHRAE 90.1-2013 AND OBC SB-10 DIVISION 3 MANDATORY PROVISIONS Form 5.4
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
Section 5.5 Overall Building Design Requirements
The building design must comply with the following general requirements. If any of these requirements are not met, the prescriptive
path cannot be pursued. Consider the building envelope trade-off compliance or the Energy Cost Budget Method Described in
Chapter 11 of ASHRAE 90.1-2013:
Gross Wall Area: _________
Vertical Fenestration Area: _________
Vertical fenestration area is less than 40% of the gross wall area
YES
Gross Roof Area: _________
Skylight Area: _________
Total skylight area does not exceed 3% of the gross roof area
YES
Where the main entrance is located on the south orientation and the south-oriented wall area
is larger than west-oriented wall area, and where the south-oriented wall area is larger than
east-oriented wall area, per ASHRAE 90.1-2013 5.5.4.5, either:
(a) total east and west vertical fenestration areas are each less than 25% of total vertical
fenestration area for the whole building, or
(b) east and west area-weighted SHGC is less than area-weighted SHGC for total
fenestration
Exception (from ASHRAE 90.1-2013 Section 5.5.4.5): ______________________________
YES N/A
YES N/A
Where electric space heating provides more than 10 per cent of the heating capacity, the
building envelope shall comply with the requirements of Table SB 5.5-7 of SB-10, regardless of
its climatic location
YES N/A
For Climate Zone 5, minimum skylight fenestration area conforms to the requirements of
ASHRAE 90.1-2013 5.5.4.2.3.
YES N/A
Identify SB-10 Table used for maximum U-Factors or minimum RSI-Values : _____________
Complete the table on Form 5.5-2 to show compliance for all envelope components. Attach as many copies of this form as required
to ensure that all envelope components are represented.
For all opaque surfaces, compliance must be demonstrated by meeting either:
1. The minimum R-values of insulation added in framing cavities and continuous insulation as specified in Tables SB5.5-5 to
SB5.5-7.
2. The maximum U-factor, C-factor, or F-factor for the entire assembly as specified in Tables SB5.5-5 to SB5.5-7. U-factor is to be
determined from tables in Appendix A of ASHRAE 90.1-2013 or through calculation methods described in ASHRAE 90.1-2013
Appendix Section A9.
For all fenestration products, compliance with U-factors, SHGC and VT must be determined for the overall fenestration product.
1. Fenestration shall have a U-factor and SHGC not greater than those specified in SB-10 Tables SB5.5-5 to SB5.5-7.
2. Where automatic daylighting controls are required in accordance with Section 9.4.1.1(e) or (f), fenestration shall have a ratio
of VT divided by SHGC not less than that specified in Tables SB5.5-5 through SB5.5-7 for the appropriate fenestration area.
3. U-factor to be determined through CSA or NFRC rating or by using ASHRAE 90.1-2013 Appendix A default values.
ASHRAE 90.1-2013 & SB-10 SECTION 5.5 PRESCRIPTIVE ENVELOPE OPTION Form 5.5-1
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
Please complete the following table to include information on all walls, roofs, doors, and floors used in the design.
OPAQUE BUILDING ENVELOPE COMPONENTS
Opaque Element -
Description
(1)
Space
Conditioning
Category
(2)
Class of Construction
(3)
Criteria Max. U-
Value
(4)
or Min
RSI
Design U-Value
(4)
or RSI
Area Weighted
Avg. Used
(5)
?
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
Please complete the following table to include information on all fenestration products used in the design.
FENESTRATION ENVELOPE COMPONENTS
Fenestration -
Description
(1)
Space
Conditioning
Category
(2)
Class of Construction
(3)
U-Value
(4)
SHGC
(6)
VT/SHGC
Area Weighted
Average Used
(5)
?
Crit.
Des.
Crit.
Des.
Crit.
Des.
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
NR R SH
Y N
(1) Indicate if Element is a Wall, Roof, Floor, Door, Window or Skylight and a Tag or Description (eg Wall W1).
(2) Select from Non-residential (NR), Residential (R), or Semiheated (SH).
(3) Select from the subclasses of roofs, walls, floors, doors and fenestration provided in Tables SB5.5-5 to SB5.5-7 (eg. Steel
Framed for walls). Note that curtain wall systems are considered a steel framed wall.
(4) F-Factors can be used for floors and C-Factors for below Grade Walls as applicable.
(5) Elements of the same type, space category, and class of construction can be averaged using area weighting to show
compliance only if U-Values are used.
(6) Design SHGC may be higher than the criteria if one of the exceptions from ASHRAE 90.1-2013 5.5.4.4.1 or 5.5.4.4.2 is
applicable. Please use the space below to identify the fenestration elements (if any) which an exception for SHGC is being
claimed.
(7) Design VT/SHGC ratio may be lower than the criteria if one of the exceptions from ASHRAE 90.1-2013 5.5.4.6 is applicable.
Please use the space below to identify the fenestration elements (if any) which an exception for VT/SHGC is being claimed.
SHGC and VT/SHGC EXCEPTIONS
Fenestration Element
SHGC or VT/SHGC exception from ASHRAE 90.1-2013 5.5.4.4.1, 5.5.4.4.2, or 5.5.4.6
ASHRAE 90.1-2013 & SB-10 SECTION 5.5 PRESCRIPTIVE ENVELOPE OPTION Form 5.5-2
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ASHRAE 90.1-2013 & SB-10 SECTION 5.5 BUILDING ENVELOPE TRADE-OFF OPTION Form 5.6
Note that this option may only be pursued using the procedure described in ASHRAE 90.1-2013 Section 5.6 as modified
by the requirements of Chapter 2 of SB-10
Calculated EPF for proposed building*: ______
Calculated EPF for budget building*: ______
Envelope performance factor (EPF) for proposed building is less than or equal to the envelope performance
factor of the budget building.
YES
All components of the building envelope shown on architectural drawings or installed in existing buildings have
been separately described and modeled in the proposed building design, with exception for envelope
assemblies that cover less than 5% of the total area of its corresponding assembly type, and whose area can be
included with another similar assembly (based on thermal properties and orientation) as noted in Section
5.6.1.1.
YES
A software program* incorporating the requirements of ASHRAE 90.1-2013 as modified by SB-10 has been used
to calculate the EPF. A report from this software is attached.
Name of software: _____________________
YES
*Note that the EPF must be calculated by a simulation program which includes the requirements of ASHRAE 90.1-2013 as
modified by SB-10.
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ASHRAE 90.1-2013 & SB-10- SECTION 6.3 HVAC SIMPLIFIED APPROACH Form 6.3
If simplified HVAC method is used complete this form, otherwise proceed to Form 6.4.
Number of Stories:
Gross floor area:
Reference
Standard Compliance
6.3.1
The building is 2 stories or less in height and has a gross floor area less than 2,300 m².
□ YES
6.3.2
All of the requirements in Section 6.3 as outlined below must be met by each HVAC system in the
facility.
6.3.2.a
System serves a single HVAC zone.
□ YES
6.3.2.b
The equipment meets the variable flow requirements of Section 6.5.3.2.1.
□ YES □ N/A
6.3.2.c
If a cooling is installed, it is provided by a unitary packaged or split-system air conditioner that is
either air-cooled or evaporatively cooled and meets the efficiency requirements shown in Tables
6.8.1-1, 6.8.1-2, and 6.8.1-4.
□ YES □ N/A
6.3.2.d
The system has an air economizer with outside airflow capacity and controls as required per
Section 6.5.1., unless exempt.
□ YES □ N/A
6.3.2.e
Heating is provided by a unitary packaged or split-system heat pump, a fuel-fired furnace, an
electric resistance heater or a baseboard system connected to a boiler. All heating equipment
meets the efficiency requirements shown in Table 6.8.1-2, 6.8.1-4, 6.8.1-5, and 6.8.1-6 as
modified by SB-10 Table SB 6.8.1-2017.
□ YES □ N/A
6.3.2.f
System meets the exhaust air energy recovery requirements of Section 6.5.6.1 as modified by SB-
10, unless exempt.
□ YES □ N/A
6.3.2.g
The system is controlled by a manual changeover or dual setpoint thermostat.
□ YES
6.3.2.h
Heat pumps equipped with auxiliary internal electric resistance heaters (if any) have controls to
prevent supplemental heater operation when the heating load can be met by the heat pump
alone, unless exempt.
□ YES □ N/A
6.3.2.i
The system controls do not permit reheat or any other form of simultaneous heating and cooling
for humidity control.
□ YES □ N/A
6.3.2.j
Systems are provided with a time switch that (1) can start and stop the system under different
schedules for seven different day-types per week; (2) is capable of retaining programming and
time setting during a loss of power for a period of at least 10 h; (3) includes an accessible manual
override that allows temporary operation of the system for up to 2 h; (4) is capable of
temperature setback down to 13° C during off hours; and (5) is capable of temperature setup to
32° C during off hours unless exempt.
YES □ N/A
6.3.2.k
Piping is insulated in accordance with values given in Table 6.8.3A and 6.8.3B. Insulation exposed
to weather is suitable for outdoor service (i.e. protected by aluminum, sheet metal, etc. or
painted with a coating that is water retardant and provides shielding from solar radiation).
□ YES □ N/A
6.3.2.l
Ductwork and plenums are insulated in accordance with Tables 6.8.2A and 6.8.2B and sealed in
accordance with Section 6.4.4.2.1.
□ YES □ N/A
6.3.2.m
Specifications call for ducted air systems to be balanced.
□ YES □ N/A
6.3.2.n
Outdoor air intake and exhaust systems meet the controls requirements of Section 6.4.3.4.
□ YES □ N/A
6.3.2.o
Where separate heating and cooling equipment serve the same temperature zone, thermostats
are interlocked to prevent simultaneous heating and cooling.
□ YES □ N/A
6.3.2.p
Systems with a design supply air capacity greater than 5,000 L/s have optimum start controls.
□ YES □ N/A
6.3.2.q
In spaces larger than 50m² and with design occupancy 25 people per 100m², the system
complies with the demand control ventilation requirements in Section 6.4.3.8, unless exempt.
□ YES □ N/A
6.3.2.r
The system complies with the door switch requirements of Section 6.5.10.
□ YES □ N/A
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
SECTION 6 HVAC 6.4 MANDATORY PROVISIONS AND 6.5 PRESCRIPTIVE REQUIREMENTS Form 6.4
Reference
Standard Compliance
Mandatory Provisions Complete only if simplified HVAC method is not used.
6.4.1
Equipment shown in 6.8.1-1 through 6.8.1-13 meets the minimum performance (as modified by
SB-10 Table SB 6.8.1-2017) at the specified rating conditions in accordance with the test
procedures in the tables or those in SB-10 Section 6.4.1.A.
□ YES
6.4.2.1
Load calculations for heating and cooling systems are done as per ASHRAE Standard 183-2007 for
selection of all equipment and systems.
□ YES
6.4.2.2
Pressure drop through each device and pipe segment in the critical circuit at design conditions has
been calculated in accordance with generally accepted engineering standards and handbooks.
□ YES
6.4.3
Mandatory controls requirements are met by all the equipment in the building as outlined in
Section 6.4.3.
□ YES
6.4.4.1
Ductwork, piping, and equipment insulation meets the requirements of Section 6.4.4.1.
YES
6.4.4.2
Construction documents specify sealing and pressure testing of ductworks and plenums as per
Section 6.4.4.2.
□ YES
6.4.5
Site-assembled or site-constructed walk-in coolers and freezers shall conform to the requirements
of Section 6.4.5.
□ YES
6.4.6
All refrigerated display cases shall conform to the requirements of Section 6.4.6., including Section
6.4.1.1 and Tables 6.8.1-1 through 6.8.1-13 as modified by SB-10.
□ YES
Prescriptive Requirements Complete this section if not using Energy Cost Budget Method.
6.5.1
Each cooling system that has a fan employs either airside or waterside economizer unless exempt.
□ YES □ N/A
6.5.1.1
Airside economizers are capable of modulating outdoor air dampers to provide up to 100% design
airflow for cooling and the system provides relief capacity for such airflow.
□ YES □ N/A
6.5.1.2.1
Waterside economizers are capable of cooling supply air up to 100% of the expected system
cooling load at the conditions listed under Section 6.5.1.2.1, unless exempt.
□ YES □ N/A
6.5.1.2.2
Waterside economizer systems with pressure drop greater than 45kPa are isolated from main
cooling loop to reduce pumping input in the normal cooling mode.
□ YES □ N/A
6.5.1.3
Economizer systems incorporate integrated economizer controls per ASHRAE 90.1-2013 6.5.1.3
□ YES □ N/A
6.5.1.4
Economizer operation does not increase the building heating energy use during normal operation,
except as allowed under ASHRAE 90.1-2013 6.5.1.4
□ YES □ N/A
6.5.1.5
Systems with hydronic cooling and humidification systems designed to maintain inside humidity at
a dew-point temperature greater than 2°C use a water economizer if required by ASHRAE 90.1-
2013 6.5.1.
□ YES □ N/A
6.5.2
Simultaneous heating and cooling is limited with compliant zone, hydronic system,
dehumidification, and humidification controls as per Section 6.5.2.
□ YES □ N/A
6.5.3
Cooling system fan controls comply with the requirements of 6.5.3.2 and 6.5.3.3.
□ YES □ N/A
6.5.3.1
Fan systems exceeding 4kW nameplate power have fan power limitations 10% below limitations
specified in ASHRAE 90.1-2013 Table 6.5.3.1.1-1 and Section 6.5.3.1.2.
□ YES □ N/A
6.5.4.1
Boiler systems with design input of ≥ 293 kW comply with the turndown ratio specified in Table
6.5.4.1.
□ YES □ N/A
6.5.4.2
Pumping systems greater than 7.5 kW employ compliant variable flow controls, unless exempt
6.5.4.3
Chilled water plants with more than one chiller and boiler plants with more than one boiler
reduce loop water flow automatically whenever a chiller or boiler is shut down and isolated.
□ YES □ N/A
6.5.4.4
Hydronic systems exceeding design capacity of 88 kW include controls to reset supply water
temperature based on building loads or outdoor air temperature, unless exempt.
□ YES □ N/A
6.5.4.5
Hydronic heat pumps and unitary air-conditioners include automatic water shutoff when the
compressor is off (unless units are employing water economizer) and those having total pump
system power greater than 3.7 kW have variable speed control.
□ YES □ N/A
6.5.4.6
Chilled water and condenser water pipe is sized according to Table 6.5.4.6.
□ YES □ N/A
6.5.5
Open-circuit cooling towers have fans meeting the energy efficiency requirements of Section
6.5.5.3 and have flow turndown in compliance with 6.5.5.4.
□ YES □ N/A
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
SECTION 6 HVAC 6.4 MANDATORY PROVISIONS AND 6.5 PRESCRIPTIVE REQUIREMENTS Form 6.4
6.5.5.2
All heat rejection equipment provide fan controls that comply with Section 6.5.5.2, with variable
speed drives on fan motors ≥ 5.6 kW.
□ YES □ N/A
6.5.6.1
Exhaust air energy recovery is provided for fan systems meeting the conditions listed on Table
6.5.6.1. Energy recovery is at least 55% effective and bypass is available to permit air economizer
operation as per Section 6.5.1.1.
□ YES □ N/A
6.5.6.2
Condenser heat recovery system for heating or preheating hot water is provided, unless exempt.
□ YES □ N/A
6.5.7.1
Kitchen exhaust systems are designed as per Section 6.5.7.1.
□ YES □ N/A
6.5.7.1.5
Specifications call for performance testing of kitchen exhaust systems.
□ YES □ N/A
6.5.7.2
Laboratory fume hoods with a total exhaust system flow > 2,360 L/S comply with the variable air
volume control requirements of 6.5.7.2.
□ YES □ N/A
6.5.8.1
Heating of unenclosed spaces is done by radiant heating, except loading docks with air curtains.
□ YES □ N/A
6.5.9
Cooling equipment with hot-gas bypass controls is designed with multiple steps of unloading or
continuous capacity modulation, with capacity limits as indicated in Table 6.5.9 for VAV systems.
Constant volume units do not have hot gas bypass.
□ YES □ N/A
6.5.10
All conditioned spaces with a door to the exterior have door switches interlocked with heating
and cooling controls per Section 6.5.10, unless exempt.
□ YES □ N/A
6.5.11
Refrigeration systems that are comprised of refrigerated display cases, walk-in coolers, or walk-in
freezers connected to remote compressors, remote condensers, or remote condensing units meet
the requirements of Sections 6.5.11.1 through 6.5.11.2.
□ YES □ N/A
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ASHRAE 90.1-2013 & SB-10- SECTION 7 SERVICE WATER HEATING Form 7.4
SECTION 7 SERVICE WATER HEATING 7.4 MANDATORY PROVISIONS AND 7.5 PRESCRIPTIVE REQUIREMENTS
Reference
Item
Standard Compliance
7.4.1
Load calculations for heating and cooling systems are done in accordance with manufacturer’s
published sizing guidelines or generally accepted engineering standards and handbooks for
selection of all equipment and systems.
□ YES
7.4.2
All equipment used solely for the following purposes meets or exceeds the efficiency
requirements and testing criteria of Table 7.8, as modified by SB-10 7.4.2.A, unless exempt.:
heating potable water
pool heaters
hot water storage tanks
Exemptions:
□ YES □ N/A
7.4.3
The following service hot water piping is insulated to levels shown in Table 6.8.3-1:
a. Recirculating system piping, including piping of a circulating tank type water heater.
b. The first 2.4m of outlet piping for a constant temperature non-recirculating storage
system.
c. Inlet pipe between storage tank and heat trap in a non-recirculating storage system.
d. Pipes that are externally heated (e.g. heat tracing).
□ YES □ N/A
7.4.4.1
All water-heating systems have temperature controls that are adjustable down to 49
o
C or lower.
Exception: Equipment that must be protected from corrosion, as per manufacturer’s
installation instructions.
□ YES □ N/A
7.4.4.2
Systems designed with pipe heating systems such as heat trace have temperature or time
controls to disable during extended periods without hot water demand.
YES □ N/A
7.4.4.3
Public lavatories have outlet temperature controls that limit the discharge temperature to 43
o
C.
□ YES □ N/A
7.4.4.4
Tanks with remote heaters have circulation pump controls to limit operation of circulation pumps
to a maximum of five minutes after the end of the heating cycle.
□ YES □ N/A
7.4.5.1
Pool heaters have readily accessible ON/OFF switch without adjusting the thermostat setting.
Gas-fired heaters do not have standing pilot lights.
□ YES □ N/A
7.4.5.2
Per SB-10 7.4.5.2, heated exterior public pools and public spas shall be equipped with pool
covers, unless over 60% of their energy for heating (computed over an annual operating season)
is derived from site-recovered or site-solar energy.
□ YES □ N/A
7.4.5.3
Pool heaters and circulation pumps have time switches, unless exempt.
□ YES □ N/A
7.4.6
Heat traps are provided to all vertical risers serving storage water heaters and storage tanks.
□ YES □ N/A
Prescriptive Requirement Complete this section if not using Energy Cost Budget Method.
7.5
Boiler systems that provide space heating as well as service water heating meet the conditions of
Sections 7.5.1 and 7.5.2.
□ YES N/A
7.5.3
Gas service hot-water systems with a total installed gas water-heating input capacity of 293 kW
or greater, shall have a minimum input capacity-weighted average thermal efficiency of 90%,
unless exempt.
□ YES □ N/A
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ASHRAE 90.1 & SB-10- SECTION 8,9 &10 POWER, LIGHTING AND OTHER EQUIPMENT
SECTION 8 POWER 8.4 MANDATORY PROVISIONS Form 8.4
Reference
Item
Standard Compliance
8.4.1
Feeder conductors and branch conductors are sized as per Section 8.4.1.
□ YES
8.4.2
At least 50% of all 125 volt 15- and 20-Ampere receptacles (installed in conference rooms, rooms
used primarily for printing and/or copying functions, breakrooms, classrooms, and individual
workstations), and at least 25% of branch circuit feeders (installed for modular furniture not
shown on the construction documents), are provided with automatic receptacle controls that
function on a) time-of-day schedule or b) occupant sensor or c) occupancy signal from another
control or alarm system, with exceptions as listed, as modified by SB-10.
□ YES □ N/A
8.4.3
Unless exempted, measurement devices are shown in design documents to monitor the total
electrical energy, as well as the electrical energy use separately for HVAC systems, interior
lighting, exterior lighting, and receptacle circuits. For buildings with tenants, these systems are
separately monitored for the total building and (excluding shared systems) for each individual
tenant. Data recording and storage capabilities meet the requirements of 8.4.3.2.
□ YES □ N/A
8.4.4
Low Voltage Dry-Type Distribution Transformers meet nominal efficiencies shown in Table 8.4.4,
unless exempt.
□ YES □ N/A
SECTION 9 LIGHTING MANDATORY PROVISIONS CHECKLIST Detailed Form 9.4-1
Reference
Item
Standard Compliance
9.4.1.1
For each space in the building, all of the lighting control functions indicated in ASHRAE 90.1-2013
Table 9.6.1, for the appropriate space type in column A, have been implemented, as described by
Section 9.4.1.1:
a. Local Control
b. Restricted to manual ON
c. Restricted to partial automatic ON
d. Bilevel lighting control
e. Automatic daylight responsive controls for sidelighting
f. Automatic daylight responsive controls for toplighting
g. Automatic partial OFF (full OFF complies)
h. Automatic full OFF
i. Scheduled shutoff
□ YES
9.4.1.2
Lighting for parking garages is controlled by automatic shutoff controls meeting the
requirements outlined in Section 9.4.1.2.
□ YES □ N/A
Lighting for parking garages is controlled by one or more devices that reduce lighting power of
each luminaire by at least 30% when there is no activity within a zone for at most 30 minutes.
Each lighting zone for this requirement cannot exceed 334 m², except daylight transition zones
and ramps without parking.
□ YES □ N/A
Daylight transition zones in parking garages are controlled separately. These are automatically
controlled to reduce by at least 50% from sunset to sunrise.
□ YES □ N/A
Parking garage luminaires within 6m of perimeter walls that have a net opening-to-wall ratio of
at least 40% automatically reduce power in response to daylight, except daylight transition zones
and ramps without parking.
□ YES □ N/A
9.4.1.3
Additional control is provided to the special applications listed in Section 9.4.1.3
□ YES □ N/A
9.4.1.4
Exterior lights are shut off by an automatic photosensor when available daylight is sufficient,
unless exempt.
□ YES □ N/A
All building façade and landscape lighting is automatically shut off overnight as per 9.4.1.4.
□ YES
Exterior lighting not for façade or landscape, including for signage, is automatically controlled to
reduce lighting power by at least 30% overnight or during inactive periods as per 9.4.1.4.
(Uncovered parking areas are exempt per SB-10)
□ YES
9.4.2
Exterior building lighting power complies with ASHRAE 90.1-2013 9.4.2 as modified by SB-10.
Form 9.4.2 may be used to demonstrate compliance.
□ YES
9.4.3
Third party functional testing of all lighting control devices and systems is specified in the
construction documents.
□ YES
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
SECTION 9.4 LIGHTING EXTERIOR LIGHTING POWER MANDATORY COMPLIANCE Form 9.4-2
Reference
Standard Compliance
9.4.3
Exterior Lighting Zone _______________ (Table SB 9.4.2-22017)
Total Installed Exterior Lighting Power ______________ W ≤ value of
exterior LPA __________W *
List any exemptions that apply:
□ YES □ N/A
* Calculation worksheet (FORM 9.4-3) is required.
SECTION 9.5 LIGHTING INSTALLED LIGHTING POWER PRESCRIPTIVE COMPLIANCE Form 9.5-1
Prescriptive Requirements Complete if not using Energy Cost Budget Method
Reference
Standard Compliance
9.5
9.6
9.5 INTERIOR LIGHTING POWER ALLOWANCE BY BUILDING TYPE
Calculation of Interior Lighting Power Allowance (ILPA) by Building Type based on Table SB 9.5.1
2017 *
Building Type ______________________
Gross Lighted Area ______________ m²
Lighting Power Density ______________ W/m²
Total Installed Interior Lighting Power ______________ W ≤ value of
Interior LPA ______________ W *
□ YES □ N/A
9.6 INTERIOR LIGHTING POWER ALLOWANCE BY SPACE FUNCTION
Calculation of Interior Lighting Power Allowance (ILPA) for each space based on Table SB 9.6.1
2017 *
Total Installed Interior Lighting Power ______________ W ≤ value of
Interior LPA ______________ W *
List any exemptions that apply:
□ YES □ N/A
* Calculation worksheet (FORM 9.5-2) is required.
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ASHRAE 90.1 & SB-10 - SECTION 9 LIGHTING COMPLIANCE WORKSHEET FORM 9.4-3
Project:
Designer Name:
Exterior Building Lighting Power Allowance - refer to Table SB 9.4.2-22017
Location / Application
Allowance
Area or Length (m² or m)
Tradable
Power
Allowance
Exterior Lighting Zone
Base Site Allowance
Tradable Power Allowance
Exterior Installed Lighting Power
ID
Luminaire description (including number of lamps per fixture, watts per
lamp, type of ballast, type of fixture)
Number of
Luminaires
Watts/
Luminaire
Total
Watts
Total Exterior Lighting Power
* If additional space is required to provide further information, please attach a separate sheet(s) of paper.
** If trade-offs or exceptions are used attach calculations.
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ASHRAE 90.1 & SB-10 - SECTION 9 LIGHTING COMPLIANCE WORKSHEET FORM 9.5-2
Project:
Designer Name:
Interior Power Allowance (Building Area Method) -refer to Table SB 9.5.12017
Building
Type
Lighting Power Density
Allowance (W/m²)
Gross Lighted Floor Area
(m²)
Lighting Power Allowance
(W) (LPDxGLFA)
Total Power Allowance
Interior Lighting Power Allowance (Space by Space Method) - refer to Table SB 9.6.12017
Building
Type
Common/Specific
Space Type
Lighting Power Density
Allowance (W/m²)
Space Area
(m²)
Lighting Power Allowance
(W)
Total Power Allowance
Interior Connected Lighting Power
Space
ID
Luminaire Description
(including number of lamps per fixture, watts
per lamp, type of ballast, type of fixture)
Number of
Luminaires
Watts/
Luminaire
Total
Watts
Total Interior Lighting Power
* If additional space is required to provide further information, please attach a separate sheet(s) of paper.
** If additional interior lighting power, trade-offs or exceptions are used attach calculations.
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
SECTION 10 OTHER EQUIPMENT - MANDATORY PROVISIONS Form 10.4
Reference
Item
Standard Compliance
10.4.1
Electric motors are in compliance with Table SB-10 Table 10.4.1.A where applicable; otherwise,
they comply with ASHRAE 90.1-2013 Tables 10.8-1, 10.8-2, 10.8-3 and 10.8-6, as applicable.
YES
10.4.2
Service water pressure booster pumps have pressure sensors to vary pump speed and/or start
and stop pumps.
YES N/A
No devices are installed to reduce the pressure of all of the water supplied by any booster
system or pump, except for safety devices.
YES N/A
Booster pumps shut off when there is no service water flow.
YES N/A
10.4.3
All elevator cab lighting systems have efficacy of not less than 35 lumens per Watt.
YES N/A
Elevator cab ventilation fans for elevators without air conditioning consume less than 0.7 W·s/L
at maximum speed.
YES N/A
Cab interior light and ventilation is de-energized when elevators are stopped and unoccupied
with doors closed for over 15 minutes.
YES N/A
10.4.4
Escalators and moving walks automatically slow to the minimum permitted speed in accordance
with ASME A17.1/CSA B44 or applicable local code when not conveying passengers.
YES N/A
10.4.5
The building is designed to facilitate future installation of means to measure and monitor energy
use by each energy type described in Section 10.4.5.1, per SB-10 10.4.5.3.
YES N/A
Note: Numbering is based on SI edition of ASHRAE 90.1-2013. Version 1 - May, 2017
ASHRAE 90.1-2013 & SB-10 ENERGY COST BUDGET (ECB) COMPLIANCE REPORT FORM 11
Project:
Designer Name:
Occupancies
Floor Area
Annual Consumption Summary
(1)
Reference
Building Energy
Proposed Building
Energy
Units
Assembly
____________
Space Heating
_____________
______________
________
Health/Institutional
____________
Space Cooling
_____________
______________
________
Hotel/Motel
____________
HVAC Fans
_____________
______________
________
Light Manufacturing
____________
Pumps
_____________
______________
________
Multifamily
____________
Service Hot Water
_____________
______________
________
Office
____________
Interior Lighting
_____________
______________
________
Restaurant
____________
Other __________
_____________
______________
________
Retail
____________
Other __________
_____________
______________
________
School
____________
Warehouse
____________
Total Annual Energy
________
Other
____________
Total Annual Energy Cost
$
>
$
Total
____________
Total Annual CO2e Emissions
>
________
Proposed Building Description
Peak Electric Demand*
>
________
__________________________________
*OR Building components specified in SB-10 Division 3 Chapter 1 Clause
1.1.2.3(5) comply with the prescriptive requirements of ASHRAE 90.1-2013
YES
__________________________________
__________________________________
__________________________________
Reference and Proposed Building Energy Consumptions are calculated by:
__________________________________
Please specify modelling software: ___________________________________
__________________________________
HVAC System Descriptions
Energy Efficiency Features in Proposed Building Design
(2)
Reference Building Design
______________________________________________________
______________________________________________
______________________________________________________
______________________________________________
______________________________________________________
______________________________________________
______________________________________________________
______________________________________________
______________________________________________
Proposed Building Design
______________________________________________
______________________________________________________
______________________________________________
______________________________________________________
______________________________________________
______________________________________________________
______________________________________________________
______________________________________________
______________________________________________
Building is in compliance with mandatory requirements of sections
5.4, 6.4, 7.4, 8.4, 9.4, and 10.4.
YES
Compliance Result
The design detailed in the above referenced plans complies with the mandatory requirements of the ASHRAE 90.1-2013 Standard and
the additional requirements of Supplementary Standard SB-10. The calculated proposed building energy cost (design energy cost), CO
2
emissions and peak electric demand do not exceed the calculated reference building energy cost (energy cost budget) CO
2
emissions
and peak electric demand. Therefore, this design DOES COMPLY with the ASHRAE 90.1-2013 ECB compliance methodology and the
additional requirements of Supplementary Standard SB-10.
Individual certifying authenticity of the data provided in this analysis:
Signature:
Name/Title:
Notes: (1) Verify with building official whether full modelling report is required to be submitted
(2) Explain major energy saving features utilized to achieve modelled savings