1
Plan Review Checklist OnLine Submission
1 & 2 Family Residential
9th edition, Massachusetts State Building Code
Site Information:
o Lot Area
o Frontage
o Zoning Overlay District
o Flood Zone Deignations
Project Information:
Structure Setbacks:
Construction Details:
o Water Supply
o Sewage Disposal system
o Zoning District
o Flood Zone Information
Estimated Construction Cost:
Residential Data Collection Checklist
2015 International Energy Conservation Code - Residential Provisions
Climate Zone 5
Building ID: Name of Evaluator(s):Date:
Building Name: Address:
Building Contact (optional): Name: Phone: Email:
Compliance Approach (check all that apply): Prescriptive Trade-Off
Performance
Compliance Software Used: Above-Code Program:
Conditioned Floor Area:
ft
2
Building Type: 1-and 2-Family, Detached:
Multifamily:
1-and 2-Family Dwellings Modular Townhouse
Apartment Condominium
Existing Building RenovationExisting Building AdditionNew BuildingProject Type:
Foundation Type: Basement Slab Conditioned Crawl Space
Floor Over Unconditioned Space
2015 IECC
Section #
Pre-Inspection/Plan Review
Prescriptive Code
Value
Plans Verified
Value
Field Verified
Value
Complies? Comments/Assumptions
103.1, 103.2
[PR1]
1
Construction drawings and
documentation demonstrate
energy code compliance for the
building envelope.
Complies
Does Not Comply
Not Observable
Not Applicable
103.1, 103.2,
403.7
[PR3]
1
Construction drawings and
documentation demonstrate
energy code compliance for
lighting and mechanical systems.
Systems serving multiple dwelling
units must demonstrate
compliance with the IECC
Commercial Provisions.
Complies
Does Not Comply
Not Observable
Not Applicable
302.1, 403.6
[PR2]
2
Heating and cooling equipment is
sized per ACCA Manual S based
on loads calculated per ACCA
Manual J or other methods
approved by the code official.
Heating:
Btu/hr_____
Cooling:
Btu/hr_____
Heating:
Btu/hr_____
Cooling:
Btu/hr_____
Complies
Does Not Comply
Not Observable
Not Applicable
Additional Comments/Assumptions:
10/15/2012P
1
2 3
Low Impact (Tier 3)High Impact (Tier 1) Medium Impact (Tier 2)
Version 3.0
3
Accredited HERS Rater
6. Plans and specifications showing the proposed work
o Temporary structures applications shall indicate begin and end time, and size of structure.
Tents and similar structures must produce a Certificate of Flame Retardant
SEE TABLE §R301.2(1) FOR FOOTNOTES
Ground
Snow
Load
Wind
Speed
(mph)
Seismic
Design
Weathering
Frost Line
Depth
Termite Decay Winter
Design
Temp
Ice Shield
Underlayment
Required
Flood
Hazard
Air
Freezing
Index
Mean
Annual
Temp
Table
5301.2 (5)
Table
5301.2.(4)
N/A Figure
5301.2 (3)
4ft.
minimum
unless
engineered
data shows
otherwise
Figure
5301.2 (6)
Figure
5301.2 (7)
Appendix
780 CMR
120.J
Table
120.J.3.2.1
As required by
the exterior
roof covering
manufacturer;
roof pitch and
local climate
must also be
considered
Refer to
applicable
Flood
Insurance
Rate Map
(FIRM)
Only
utilized in
the design
and
construction
of frost
protected
shallow
foundations
Only
utilized in
the design
and
construction
of frost
protected
shallow
foundations
50 psf 126 mph
NA Severe §5403.1.4
M o d e rat e
t oH e a vy
S l i g h t t o
M o d e r a t e
NA §5905.0
FIRM
MAPS
See note
J Table
5301.2(1)
See note K
Table
5301.2(1)
PROCEDURE FOR OBTAINING A BU
NEW CONSTRUCTION FOR UNDEVELOPED LOT & ADDITIONS, ALTERATIONS,
ACCESSORY STRUCTURES
(In addition to the above requirements)
7. Building Construction Documents
General
o Electronic set of construction documents §R107.1
o Construction documents for structures to be constructed in flood hazard areas are required
to be prepared by a design professional pursuant to § R107.1.4
o Also see Grafton Zoning Bylaws
o Documentation concerning disturbed / fill soils that support foundations shall be
in accordance with §R401.2
Construction Drawings
Cover Sheet
o Address with Assessor Map and Parcel
o Date of latest revision
o Tabulated Square Foot Area all levels (and spaces if applicable)
o Design live load all spaces and levels
o Building height above grade
o Wind Exposure category each building side
o Window, door, skylight and cladding schedule showing associated positive and negative
design pressure and zone number including manufacturers specifications cut sheets on each type
window, door, skylight and cladding being installed.
o Identify class of material Table §R401.4.1 and Table
§R405.1 Construction documents (
1
/
4
scale minimum)
o Floor Plan (all levels)
o Building dimensions Space designation – (ie: living room, kitchen, bedroom, storage, etc.)
o Demonstrate light and ventilation compliance §R303.1
o Door and window location per schedule on cover sheet, identifying egress windows and
safety glazing
o Show attic access size and location
o Location and type of smoke detectors and carbon monoxide detectors & completed install permit.
Emergency escape and rescue required. Basements, habitable attics and every sleeping
room shall have at least one operable emergency escape and rescue opening.
1
o 2015 IECC R403.5 Mechanical ventilation (Mandatory). Location of unit must be marked on plans
Specification along with installation maunal must be submitted.
o If utilizing existing equipment, you MUST submit a heat loss calculation showing existing loads
and also proposed new loads (manual J)
o Heating system location, size (BTU), location of fuel source and method of combustion air
make-up (manual S)
o Location of ductwork…if installed in exterior wall, the Energy Conservation Application Form
noted above must reflect decreased R-value or indicate method of maintaining exterior wall
integrity (manual D)
Completed Mechanical Permit application
10. Foundation Plan
o Show dimensions and location of all footings, pads and columns
o Footing sections and elevations where steps are intended
o Show size and location of all steel reinforcement bars if applicable
o Wall height and thickness with concrete PSI rating
o Anchor bolt size, spacing and embedded depth
o Show basement / crawl space ventilation method
o Show basement / crawl space access size and location
o Foundation hold down devices type and location when used with the alternative braced wall
panels for braced wall requirements as allowed by FIGURE R602.10.3.2
o Location and framing size of all cripple walls, with detail of walls less than 14 inch stud height
o Passive Radon Control detail & shall indicate pathways for routing of conduit
o Location of foundation drain exhaust or sump pit…drainage exclusion exception must be
approved by building official §R405
Vapor Retarder detail as per §R405.2.2 A 6milthick (0.15 mm) polyethylene vapor retarder
Demonstrate compliance with section §R403.1.7.2 Foundation Clearance from Slope
o Conventional framing plan all levels including roof, showing size, spacing and direction of
structural members
o Conventional header and beam sizes, spans and bearing clearly showing load path to
foundation (ie: doorways, windows, archways, overhead doors, covered porches and decks
and structural ridges). Detail showing insulated headers.
o Engineered floor framing and roof truss plans stamped by a professional registered engineer
in the Commonwealth of Massachusetts.
Raised rafter construction details stamped by a professional registered engineer in the
Commonwealth of Massachusetts.
Floor Fire Protection §R302.13
o Roof truss layout shall show type of uplift protection, bearing location, hangers and any other
unique application. Multiple roof layouts shall require separate roof sectionals.
o Engineered manufactured beams and columns stamped by a registered professional engineer
in the Commonwealth of Massachusetts. Calculations shall be site specific verifying they
generated the loads indicated and that the input and output data provided is site specific to
include verification of load path and column adequacy to foundation…disclaimers of any kind
shall be rejected.
o Provide stamped engineered analysis for bearing stud wall height greater than 10 feet, and for
non-load bearing stud walls in excess of heights listed in Table §R602.3(5).
o Show exterior and interior wall bracing locations supporting wall brace method identified on
cover sheet.
12. Elevations
o Exterior building elevations all sides to include final grade
o Exterior siding material – provide evaluation report for types of exterior wall cladding in
conformance with the design pressure schedule provided on the cover sheet Exterior roofing
material l– provide evaluation report for types of exterior roofing material in conformance
with the design pressure schedule provided on the cover sheet.
Exterior building elevation demonstrating protection of wood based products against decay.
7
SECTION R314 SMOKE ALARMS
R314.1 Smoke detection and notification. All smoke alarms shall be
listed in accordance with UL 217 and installed in accordance with the
provisions of this code and the household fire warning equipment
provisions of NFPA 72.
R314.2 Smoke detection systems. Household fire alarm systems
installed in accordance with NFPA 72 that include smoke alarms, or a
combination of smoke detector and audible notification device installed as
required by this section for smoke alarms, shall be permitted. The
household fire alarm system shall provide the same level of smoke
detection and alarm as required by this section for smoke alarms. Where a
household fire warning system is installed using a combination of smoke
detector and audible notification device(s), it shall become a permanent
fixture of the occupancy and owned by the homeowner. The system shall
be monitored by an approved supervising station and be maintained in
accordance with NFPA 72.
Exception: Where smoke alarms are provided meeting the requirements of
Section R314.4.
R314.3 Location. Smoke alarms shall be installed in the following
locations:
1. In each sleeping room.
2. Outside each separate sleeping area in the immediate vicinity of
the bedrooms.
3. On each additional story of the dwelling, including basements and
habitable attics but not including crawl spaces and uninhabitable
attics. In dwellings or dwelling units with split levels and without an
intervening door between the adjacent levels, a smoke alarm installed
on the upper level shall suffice for the adjacent lower level provided
that the lower level is less than one full story below the upper level.
When more than one smoke alarm is required to be installed within
an individual dwelling unit the alarm devices shall be interconnected
in such a manner that the actuation of one alarm will activate all of
the alarms in the individual unit.
8
R314.3.1 Alterations, repairs and additions. When alterations,
repairs or additions requiring a permit occur, or when one or more
sleeping rooms are added or created in existing dwellings, the
individual dwelling unit shall be equipped with smoke alarms located
as required for new dwellings.
R314.5 Heat Detector. A single heat detector listed for the ambient
environment shall be
installed in:
1. Any integral garage (“garage under”) or attached garage to the main
house (detached garages do not require a heat detector).
2. A new addition attached garage to an existing dwelling. If the existing
house contains a fire detection system that is compatible with the garage
heat detector, then the detector shallbe interconnected to the existing
system. Where the existing fire detection system is not compatible with the
garage heat detector, the garage heat detector shall be connected to a
sounder (occupant notification appliance) or compatible heat detector
containing a sounding device, located in the dwelling and within 20 feet
(6096 mm) of the nearest door to the garage from the dwelling. The
required garage heat detector is neither required to incorporate audible
alarm notification nor is any audible notification device required in the
garage.
R314.5.1 Heat Detector Placement. For flat-finished ceilings, the single
heat detector shall be placed on or near the center of the garage ceiling.
For sloped ceilings having a rise to run of greater than one foot in eight feet
(305 mm in 2438 mm), the single heat detector shall be placed in the
approximate center of the vaulted ceiling but no closer than four inches
(102 mm) to any wall.
R315.1 Governing Regulations. Carbon monoxide alarms (alarms) for
new construction and
existing dwellings shall be furnished, installed and maintained by the owner
in accordance with this section, M.G.L. c. 148, § 26F½ , 527 CMR 31.00:
Carbon Monoxide Alarms, 248 CMR, NFPA 720 and the manufacturer’s
instructions.
R315.2 Installation Locations. One alarm shall be installed on each story
of a dwelling unit, including basements and cellars (but not including crawl
9
spaces and uninhabitable attics). When mounting a carbon monoxide alarm
on a story with a bedroom, the alarm, shall be located outside of bedrooms
but no further than 10 feet of any bedroom door. If a combination
smoke/carbon monoxide alarm is used, its location must comply with this
section.
R315.3 New Construction. Alarms shall either be an interconnected 120V
or part of a low voltage combination system or wireless system. Alarms
shall have secondary (standby) power from monitored batteries in
accordance with NFPA 72. For fire alarm control units (panels) and
wireless systems, the panel battery shall serve as the source of secondary
power. Alarms shall be UL 2034 or UL 2075 listed, as applicable. Alarms
may be interconnected with fire alarms providing they are compatible and
the fire alarms take precedence.
R315.4 Existing Dwellings. For existing dwellings, carbon monoxide
alarms shall be provided in accordance with Section 315 for new
construction, as applicable, for the following circumstances:
1. When one or more bedrooms are added or created in a dwelling unit, the
entire dwelling
shall be provided with alarms.
2. When a dwelling unit undergoes complete reconstruction such that all
walls and ceilings are open to framing the entire dwelling unit shall be
provided with alarms.
3. In an existing two-family dwelling, when one or more bedrooms are
added or created in both of the two dwelling units, the entire building shall
be provided with alarms.
4. In a townhouse building when one or more bedrooms are added or
created in a dwelling then that dwelling unit shall be provided with carbon
monoxide alarms.
5. In a townhouse building when a dwelling unit undergoes complete
reconstruction such that all walls and ceilings are open to framing, that
dwelling unit shall be provided with carbon monoxide alarms.
10