SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 1 04.27.20
®
Phase-Adaptive Power Module
Provides dimming control for 1zone of a full 16 A
lighting load.
May be used to dim incandescent, halogen, electronic
low-voltage, magnetic low-voltage, neon/cold cathode.
Phase-adaptive technology automatically selects leading-
edge or trailing-edge dimming for low-voltage transformers.
Up to 3 power modules may be controlled by a single
dimmer (C5-BMJ- will control only 1 module).
Use PHPM-WBX- models for 3-wire fluorescent dimmer
input and PHPM-PA- models for 2-wire input.
PHPM-WBX- models can be used in conjunction with
BCI-0-10 for 0 10 V dimming applications. For more
information, see Application Note #516 (Lutron P/N048516)
at www.lutron.com
Models available for control voltage of 120 V~ only or
220 – 277V~.
Models available for load voltage of 120 V~ only or
120 – 277V~.
Compatible with 220 / 240 V~, non-CE systems. Contact
Lutron for specific system applications.
Not for use with non-dim loads.
Works with 120 V~ or 220 277 V~ versions of:
Lutron in-wall neutral wire dimmers; see approved list in
the Dimmers and Switches Specification Guide (Lutron P/N
3671746) at www.lutron.com (see Lighting Load Interfaces
section)
GRAFIK Eye QS control units *
LP, LCP, and GP dimming panels **
HomeWorks QS remote power panels **
HomeWorks QS in-line dimmer
HomeWorks QS DIN-rail power modules
EcoSystem interface C5-BMJ-XXX
Energi Savr Node PRO LED+ phase-adaptive fixture
controller
RadioRA 2 neutral wire dimmers; see approved list
in the specification submittal (Lutron P/N 369225) at
www.lutron.com
HomeWorks QS neutral wire dimmers; see approved
list in the specification submittal (Lutron P/N 369305) at
www.lutron.com
Caséta Wireless neutral wire dimmers; see approved
list in the specification submittal (Lutron P/N 369987) at
www.lutron.com
Models and Capacities
Control
Voltage
1, 2
Load
Voltage
1, 2
Load
Capacity
Model Number
3, 4
120 V~ 120 V~ 16 A PHPM-PA-120-WH
120 V~ 120 – 277 V~ 16 A PHPM-PA-DV-WH
220 – 277 V~ 120 – 277 V~ 16 A PHPM-PA-277 / DV
120 V~ 120 V~ 16 A PHPM-WBX-120-WH
120 V~ 120 – 277 V~ 16 A PHPM-WBX-DV-WH
220 – 277 V~ 120 – 277 V~ 16 A PHPM-WBX-277 / DV
1
All voltages are phase-to-neutral.
2
For explanation of “control voltage” and “load voltage”, see page 5.
3
Use PHPM-PA- models for incandescent/halogen dimmers and set the
controller load type to “power module” or “incandescent”.
4
Use PHPM-WBX- models for 3-wire fluorescent dimmers and set the
controller load type to “fluorescent”.
* For PHPM-PA- models, set load type to “power module”.
** For PHPM-PA- models, set load type to “incandescent”.
Use only PHPM-WBX models with this product; using PHPM-PA- models
is not recommended
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 2 04.27.20
®
Specifications
Power
Control voltage
120 V~ only
PHPM-PA-120-WH
PHPM-PA-DV-WH
PHPM-WBX-120-WH
PHPM-WBX-DV-WH
220 – 277 V~
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Load voltage
120 V~ only
PHPM-PA-120-WH
PHPM-WBX-120-WH
120 – 277 V~
PHPM-PA-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-DV-WH
PHPM-WBX-277 / DV
Capacity: Full 16 A
120 V~: 1920 W
120 – 277 V~: 1920 – 4432 W
220 – 240 V~: 3520 – 3840 W
Frequency: 50 / 60 Hz
Load (output) power: Phase independent of control
device/control voltage
Sources/Load Types
Operates these sources with a smooth, continuous,
Square Law dimming curve:
Incandescent (tungsten)
– Halogen
Magnetic low-voltage transformer (iron core)
Electronic (solid-state) low-voltage transformer (must
be manufacturer-approved for reverse-phase
control dimming)
Neon / Cold cathode
Incandescent and electronic low-voltage sources may be
controlled on the same circuit / control zone. Up to 30%
of the capacity of the unit can be used for incandescent
lighting.
Incandescent and magnetic low-voltage sources may be
controlled on the same circuit/control zone. Up to
30% of the capacity of the unit can be used for
incandescent lighting.
Electronic low-voltage and magnetic low-voltage sources
may NOT be controlled on the same circuit / control zone.
PHPM-PA- and PHPM-WBX- models are not for use
with non-dim loads. Use switching power module
(PHPM-SW-DV-WH) for non-dim loads.
Minimum load on power module is 10 W.
Output must be directly connected to the load. Load side
switching is not recommended.
Key Design Features
Automatically selects between forward-phase/
leading edge (e.g., magnetic low-voltage) and reverse-
phase / trailing edge (e.g., electronic low-voltage)
dimming / output based on connected load.
Patented RTISS Equipped circuitry compensates in real
time for incoming line voltage variations: Compensates
for + / –2% change in RMS voltage/cycle and + / –2% Hz
change in frequency/second.
Provides air-gap off.
Module protects itself during most temporary over-current
and over-voltage conditions.
Two LEDs on front of unit provide diagnostic information
(visible when faceplate is removed).
Terminals
Each terminal accepts up to two 12 AWG (2.5 mm
2
) wires.
Environment
32 to 104 °F (0 to 40 °C). Relative humidity less than 90%
non-condensing.
Indoor use only.
Maximum heat output of module: 135 BTU / hour.
Mounting
Surface or recess mount.
Power module is UL tested and approved for use in
spaces designed for environmental air handling.
Regulatory Approvals
Models: PHPM-PA-120-WH, PHPM-PA-DV-WH,
PHPM-WBX-120-WH, PHPM-WBX-DV-WH
– UL
RoHS Compliant
– CSA
– NOM
– CIDET
Complies with requirements for use in other
spaces used for environmental air (plenums) per
NECR2014300.22(C)(3).
Models: PHPM-PA-277 / DV, PHPM-WBX-277 / DV
– UL
RoHS Compliant
Complies with requirements for use in other
spaces used for environmental air (plenums) per
NECR2014300.22(C)(3).
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 3 04.27.20
®
Dimensions and Mounting
Mount in 2-gang U.S. wallbox, 3.5 in (89 mm) deep or
4×4in (102 × 102 mm) junction box, 2.1 in (53mm)
deep.
For indoor use only.
This device generates heat; mount only where ambient
temperature is 32 to 104 °F (0 to 40 °C).
Mount with arrows facing up to ensure adequate cooling.
Allow 4.5 in (114 mm) above and below faceplates when
mounting several modules in a vertical layout.
Units may butt together when mounted in a horizontal
layout.
Mount so line (mains) voltage wiring is at least 6 ft (1.8 m)
from sound or electronic equipment and wiring.
Mount within 7° of true vertical.
Front View
Side View
Mount to 2-gang U.S. wallbox
Mount to 4×4 in (102×102 mm), 2.1in (53mm) deep
U.S. junction box
Mount to 4×4 in (102×102 mm), 2.1in (53mm) deep
U.S. junction box with barrier
(for 277 V~ loads if required by local electrical code)
5.1 in
(129.5 mm)
6.3 in
(160 mm)
1.4 in (35.5 mm)
1.2 in (30.5 mm)
Mounting Methods
Barrier
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 4 04.27.20
®
Wiring
12 AWG (2.5 mm
2
) copper (Cu) wires (75 °C / 167 °F
minimum) for input power and load circuit.
Strip 1/2 in (12 mm) insulation from wires before
connecting.
Run separate neutral for load circuit; no common neutrals.
Wiring to a Dimmer
Single Power Module to Single Control Device: Combined Power Feed for Control and Load Sides
The power module may be on the same circuit / control zone as the control unit only if the total load does not exceed the
rating of the breaker.
Use PHPM-WBX- models for 3-wire fluorescent dimmers and PHPM-PA- models for other dimmer types.
PHPM-PA-DV-WH and PHPM-WBX-DV-WH are included as 120 V~ only because of limits on zone-in voltages.
For specific wire colors, see the wallbox lighting controls catalog (Lutron P/N 3691746) at www.lutron.com/wallbox
May be used with GFI breaker protected loads. Load
circuit wiring (from GFI breaker to power module to
load) must be run in its own non-metallic conduit,
or nuisance tripping may occur. Maximum 100 ft
(30.5m) between power module and load.
May be used with AFI breaker protected loads. Maximum
load on AFI circuit is 1000 W. Exceeding 1000 W may
cause nuisance tripping of AFI breaker.
H/L
N
DH
Dimmer
Zone In
Control Neutral
Circuit breaker
Load
DH (yellow / orange wire)
SH (capped)
H / L
N
D
Feed
120 V~
• PHPM-PA-120-WH
• PHPM-PA-DV-WH
• PHPM-WBX-120-WH
• PHPM-WBX-DV-WH
220 – 277 V~
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
H / L
N
D
(continued on next page…)
Legend
H / L Hot / Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 5 04.27.20
®
Wiring to a Dimmer (continued)
Single Power Module to Single Control Device: Separate Power Feeds for Control and Load Sides
The load breaker may be on a different phase from the control breaker.
Use PHPM-WBX- models for 3-wire fluorescent dimmers and PHPM-PA- models for other dimmer types.
Load feed must not exceed voltage rating of the load
1
; control feed must not exceed voltage rating of the dimmer
2
.
For specific wire colors, see the wallbox lighting controls catalog (Lutron P/N 3691746) at www.lutron.com/wallbox
1
“Load feed” and “load voltage” refer to the circuit powering the load dimmed by the power module.
2
“Control feed” and “control voltage” refer to the circuit powering the dimmer that controls the power module.
Legend
H / L Hot / Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
H/L
N
DH
Dimmer
Zone In
Control Neutral
Load breaker
Control breaker
Load
DH (yellow / orange wire)
SH (capped)
H / L
N
D
Load feed
120 V~
• PHPM-PA-120-WH
• PHPM-WBX-120-WH
120 – 277 V~
• PHPM-PA-DV-WH
• PHPM-WBX-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
H / L
N
D
Control feed
120 V~
• PHPM-PA-120-WH
• PHPM-PA-DV-WH
• PHPM-WBX-120-WH
• PHPM-WBX-DV-WH
220 – 277 V~
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
(continued on next page…)
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 6 04.27.20
®
H/L
N
DH
H/L
N
DH
H/L
N
DH
Dimmer
Control breaker
DH (yellow / orange wire)
SH (capped)
Zone In
Control Neutral
Load breaker
Load
Zone In
Control Neutral
Load breaker
Load
Zone In
Control Neutral
Load breaker
Load
H / L
N
D
H / L
N
D
H / L
N
D
Load feed
120 V~
• PHPM-PA-120-WH
• PHPM-WBX-120-WH
120 – 277 V~
• PHPM-PA-DV-WH
• PHPM-WBX-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Load feed
120 V~
• PHPM-PA-120-WH
• PHPM-WBX-120-WH
120 – 277 V~
• PHPM-PA-DV-WH
• PHPM-WBX-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Load feed
120 V~
• PHPM-PA-120-WH
• PHPM-WBX-120-WH
120 – 277 V~
• PHPM-PA-DV-WH
• PHPM-WBX-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
H / L
N
D
Control feed
120 V~
• PHPM-PA-120-WH
• PHPM-PA-DV-WH
• PHPM-WBX-120-WH
• PHPM-WBX-DV-WH
220 – 277 V~
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Legend
H / L Hot / Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
(continued on next page…)
Wiring to a Dimmer (continued)
Multiple Power Modules to Single Control Device
Shown with separate feeds for control and loads. All breakers
must be turned off prior to installing or servicing the modules.
Up to 3 power modules may be wired to a single dimmer.
Use PHPM-WBX- models for 3-wire fluorescent dimmers and
PHPM-PA- models for other dimmer types.
Load feed must not exceed voltage rating
of the load; control feed must not exceed
voltage rating of the dimmer.
For specific wire colors, see the
wallbox lighting controls catalog (Lutron
P/N3691746) at www.lutron.com/wallbox
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 7 04.27.20
®
Wiring to a Dimmer (continued)
Single Power Module to Multiple Control Devices
The power module may be on the same circuit / control zone as the control unit only if the total load does not exceed the
rating of the breaker.
Use PHPM-WBX- models for 3-wire fluorescent dimmers and PHPM-PA- models for other dimmer types.
Load feed must not exceed voltage rating of the load; control feed must not exceed voltage rating of the dimmer.
For specific wire colors, see the wallbox lighting controls catalog (Lutron P/N 3691746) at www.lutron.com/wallbox
H/L
N
DH
Dimmer
(Main
Dimmer)
Accessory /
Companion
Dimmer or
3-Way
Switch
Zone In
Control Neutral
Load breaker
Control breaker
Load
DH (yellow / orange wire)
SH (capped)
H / L
N
D
N
H / L
Load feed
120 V~
• PHPM-PA-120-WH
• PHPM-WBX-120-WH
120 – 277 V~
• PHPM-PA-DV-WH
• PHPM-WBX-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Control feed
120 V~
• PHPM-PA-120-WH
• PHPM-PA-DV-WH
• PHPM-WBX-120-WH
• PHPM-WBX-DV-WH
220 – 277 V~
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Legend
H / L Hot / Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 8 04.27.20
®
Wiring to a GRAFIK Eye QS
Single Power Module to Single Control Device: Separate Power Feeds for Control and Load Sides
The load type for the output must be set appropriately on the panel’s circuit selector (for an LP or GP panel), on the controller
(for an LCP panel), or in the HomeWorks software (for a HomeWorks panel).
For PHPM-PA- models, set load type to “incandescent”.
For PHPM-WBX- models, set load type to “fluorescent”.
Load feed must not exceed voltage rating of the load; control feed must not exceed voltage rating of the dimmer.
For specific wire colors, see the wallbox lighting controls catalog (Lutron P/N 3691746) at www.lutron.com/wallbox
123456LN
H/L
N
DH
Zone In
Control Neutral
Load breaker
Load
H / L
N
D
Load feed
120 V~
• PHPM-PA-120-WH
• PHPM-WBX-120-WH
120 – 240 V~
• PHPM-PA-DV-WH
• PHPM-WBX-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Control breaker
GRAFIK Eye QS Control Unit
Wire to
appropriate
zone
H / L
N
D
Control feed
120 V~
• PHPM-PA-120-WH
• PHPM-PA-DV-WH
• PHPM-WBX-120-WH
• PHPM-WBX-DV-WH
220 – 240 V~
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Legend
H / L Hot / Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 9 04.27.20
®
Wiring to an EcoSystem C5-BMJ Interface (for PHPM-WBX- models only)
Single Power Module to Single Dimming Module: Separate Power Feeds for Control and Load Sides
The load breaker may be on a different phase from the control breaker.
Use PHPM-WBX- models only.
Load feed must not exceed voltage rating of the load.
For specific wire colors, see the wallbox lighting controls catalog (Lutron P/N 3691746) at www.lutron.com/wallbox
H/L
N
DH
Zone In
Control Neutral
Load breaker
Control breaker
Load
H / L
N
D
H / L
N
D
Load feed
120 V~
• PHPM-WBX-120-WH
120 – 277 V~
• PHPM-WBX-DV-WH
PHPM-WBX-277 / DV
DH (Orange)
N (White)
PHPM-WBX- models only
C5-BMJ-16A
SH (Red) (capped)
Control feed
120 V~
• PHPM-WBX-120-WH
• PHPM-WBX-DV-WH
220 – 277 V~
PHPM-WBX-277 / DV
Legend
H / L Hot / Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 10 04.27.20
®
H/L
N
DH
DH
DH
DH
DH
H
N
N
N
N
N
Zone In
Control Neutral
Load breaker
Load
H / L
N
D
Load feed
120 V~
• PHPM-PA-120-WH
• PHPM-WBX-120-WH
120 – 277 V~
• PHPM-PA-DV-WH
• PHPM-WBX-DV-WH
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Power (Hot / Live)
(3) 14 to 2/0 AWG (2.0 to 70 mm
2
)
Neutral
(1) 14 to 2/0 AWG (2.0 to 70 mm
2
)
Dimmed Hot
(1) 14 to 10 AWG (2.0 to 4.0 mm
2
)
(1) 14 to 10 AWG (2.0 to 4.0 mm
2
)
Neutral
Branch
circuit
breakers
Legend
H / L Hot / Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
Wiring to an LP, GP, LCP, or HomeWorks Panel
Single or Multiple Power Modules to Single Power Panel
The load type for the output must be set appropriately on the panel’s circuit selector (for an LP or GP panel), on the controller
(for an LCP panel), or in the HomeWorks software (for a HomeWorks panel).
For PHPM-PA- models, set load type to “incandescent”.
For PHPM-WBX- models, set load type to “fluorescent”.
Load feed must not exceed voltage rating of the load.
For specific wire colors, see the wallbox lighting controls catalog (Lutron P/N 3691746) at www.lutron.com/wallbox
Control Voltage:
120 V~
• PHPM-PA-120-WH
PHPM-PA-DV-WH
• PHPM-WBX-120-WH
• PHPM-WBX-DV-WH
220 – 277 V~
PHPM-PA-277 / DV
PHPM-WBX-277 / DV
Lutron, )Lutron, GRAFIK Eye, HomeWorks, EcoSystem, RadioRA, RadioRA 2, Energi Savr Node, LED+, and RTISS Equipped are trademarks or registered trademarks of Lutron
Electronics Co., Inc. in the US and/or other countries.
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Phase-Adaptive Power Module Power Interfaces
369835f 11 04.27.20
®
L/ H
N
DL
Def
1
2
3
Opt
Ta > 70 ˚C
Prog
Input
Entrada
Entrée
120 V~
16 A
50 / 60 Hz
QSN-4A5-D
CCI
800 W
500 W 500 W 500 W
H
M
L
+1.844.LUTRON1
lutron.com
Zn 1 Zn 2
Zn 3
Zn 4
277 V
8.3 A
50 / 60 Hz
~
CCI
COM
MUX
MUX
COM
L N NL N N N
DL1 DL2 DL3 DL4
N
N DL
N
L/H
Phase-Adaptive
Outputs
L/H
Control Feed
(120/277 V~)
Lighting
Loads
Zone In
Control
Neutral
Load breaker
L L
N N N N
N
DL1
DL2 DL3 DL4
Legend
L/H Line/Hot
N Neutral
DL Dimmed Line
Earth / Ground
Not Used
Wiring to an Energi Savr Node PRO LED+ Phase Adaptive Fixture Controller
Single or Multiple Power Modules to Single Power Panel
The load type for the output must be set appropriately.
For PHPM-PA- models, set load type to “forward-phase”.
Load feed must not exceed voltage rating of the load.
Not Compatible with PHPM-WBX- models.
Up to three power modules may be wired to an output.
Load feed
120 V~
• PHPM-PA-120-WH
277 V~
• PHPM-PA-DV-WH
PHPM-PA-277 / DV
Control Voltage:
120 V~
• PHPM-PA-120-WH
PHPM-PA-DV-WH
277 V~
PHPM-PA-277 / DV
11