ILLUMINATION
Long lasting, efficient, ultra bright white LED lamp heads.
1W (8 LEDs x 0.125 watt) per head.
High performance chrome-plated metallized reflector and
plastic lens for optimal light distribution.
Adjustable LED lamp heads provide optimal center-to-center
spacing. High-lumen option available for increased center-
to-center spacing.
ELECTRICAL
Dual 120/277 voltage standard. Optional 120/347V (for
Canada) and multi-tap 208/220/240 voltage available.
Charge rate/power “ON” LED indicator light and push-to-test
switch for mandated code compliance testing.
3.6V long life, maintenance-free, rechargeable NiCd battery.
Internal solid-state transfer switch automatically connects
the internal battery to LED lamp heads for minimum
90-minute emergency illumination.
Fully automatic solid-state, two rate charger initiates battery
charging to recharge a discharged battery in 24 hours.
MOUNTING
Surface mount via easy connect back plate, which fits
most standard junction boxes and snaps into place making
internal electrical connections.
Top and side knockout for conduit applications.
Suitable for wall or ceiling mount.
HOUSING
Injection-molded, engineering grade, 5VA flame retardant,
high-impact resistant, thermoplastic in white or black finish.
OPTIONS
SDT: Self-diagnostic feature performs monthly, biannual,
and annual tests to ensure reliable operation and meet
electrical and life safety codes.
HL: 12-LEDs per head provide increased center-to-center spacing.
SPV: UL Listed for special voltage option
.
CSA: Tested to meet requirements of CSA C22.2 No.
141.10 standard for emergency lighting equipment
.
WARRANTY / LISTING
Five year warranty on all electronics and housing. Batteries
pro rated for five years.
UL (standard)/CSA (optional) listed for damp locations
(0°C – 50°C).
Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,
Local and State Codes.
DIMENSIONS
ORDERING INFORMATION
1. Not available with SDT options.
Sample Part Number: LEDR-1
MODEL HOUSING COLOR OPTIONS
LEDR-1 Blank White SDT Self-diagnostics
B Black SPV 208/220/240 Volt, 50/60Hz
1
HL High-Lumen
CSA 120/347V, 60Hz
STANDARD OPTIONAL
12”
10
1
/
16
4
9
/
16
3
11
/
16
5
1¾”
2½”
LEDR1
LED Emergency Unit
TYPE:
PROJECT:
CATALOG#:
2055 Luna Road Suite 142 | Carrollton, TX 75006
T 214.884.1150 | F 972.247.0200 | sales@saylite.com
04/16/2020
ELECTRICAL INFORMATION
CENTER-TO-CENTER SPACING GUIDELINES
For reference only.
Meets NFPA 101 Requirements for: 10’ center-to-center spacing - 3’ path of egress 1’ from wall - 7 1/2’ mounting height.
CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)
120V 277V 347V 208V 220V 240V 120V 277V 347V 208V 220V 240V
LEDR-1 1.8 1.8 - 2.6 3.5 3.1 0.022 0.010 - 0.024 0.029 0.025
LEDR-1 SDT 1.6 1.6 ----0.020 0.010 ----
LEDR-1-CSA 2.0 - 2.0 - - - 0.023 - 0.008 - - -
1
0.2 0.3 0.5 0.4 0.4 0.5 0.6 0.8 1.0 0.8 0.9 0.8 0.4 0.2 0.2
2
0.3 0.5 0.7 0.8 0.9 0.8 0.9 1.0 1.1 1.4 1.1 0.8 0.5 0.3 0.2
3
0.4 0.7 1.0 1.0 1.1 1.1 1.1 1.3 1.4 1.1 0.9 0.9 0.7 0.5 0.2
4
0.5 0.7 0.9 1.1 1.2 1.2 1.0 1.1 1.1 1.0 1.1 0.8 0.6 0.3 0.2