LC-100 Intelligent Power Pack
Load shed dimming or
ON/OFF switching
Dual voltage 120/277 VAC
Daylighting control
with photosensor
Two-relay output power pack
that accepts signals from
multiple control devices
Product
Overview
Features
Tunes maximum light level
output for greater energy
savings potential
Dimming convenience
with 0-10V ballasts
Single package with relay outputs, dimming
channels, power supply, and device inputs for
simpler installation
Two switch inputs accept three-wire momen-
tary, two-wire momentary pushbutton, or
maintained low voltage switches
Hold-ON feature keeps lighting on during
scheduled time, reverts to occupancy sensor
control after hours
Burn in timer prevents lamps from dimming for
initial 100 hours for extended lamp life
The LC-100 is a power pack with two relay outputs
and two dimming channels delivering both switch-
ing and 0-10V dimming control to lighting loads.
Signal inputs offer integrated operation with a
range of control devices.
Dimming Control
Applications
The LC-100 integrates control of other devices
to meet room-specific lighting control needs. It
is ideal for compliance with bi-level switching,
daylighting and lighting shutoff energy code provi-
sions. Where load shedding is needed, the LC-100
can switch off non-critical lighting while leaving
other lighting on. Or with controllable ballasts, it
can dim lighting down to preset load “shed” levels.
Operation
A dual voltage device capable of operating at either
120 or 277V, the LC-100 installs as a standard
power pack, connecting to junction boxes in a
ceiling or a location close to controlled loads. With
24VDC at 150mA available, it provides power to
occupancy sensors, photocells, and other devices.
Low voltage switch inputs give occupants ON/
OFF switching and up/down dimming control of
two independent lighting loads. Separate signal-
ing inputs for occupancy sensors, time clocks and
photocells allow shutoff and daylighting control
while providing convenient scenarios (i.e., blink
warning, manual on or auto on, hold on, on only) to
meet control needs.
Description
Pilot light output for status annunciation at
switches
Blink warning five minutes prior to shutoff
Isolated relay contact for each relay output pro-
vides status
Manual ON/Auto ON settings for convenience
and energy savings
After hour override adjustable to 30 minutes, 1
hour, 2 hours or 4 hours
Works with the LS-301 dimming photosensor to
provide closed loop dimming control
Qualifies for ARRA-funded public works projects
When used with 0-10V controllable ballasts, the
LC-100 provides dimming and ON/OFF control
of up to 100 ballasts per dimming channel.
Occupants can conveniently dim up/down and turn
lighting ON/OFF using momentary low voltage
switches. The load shed feature dims lighting
to preset levels during peak demand periods to
reduce energy consumption. Lighting maximum
levels can also be set for greater energy savings.
www.wattstopper.com | 800.879.8585
COMMERCIAL OCCUPANCY SENSORS & CONTROLS
Wiring &
Installation
Pub. No. 14703 rev.10/2009
Ordering
Information
Installation
Notes
Specifications
120/277 VAC voltage input, 50/60 Hz
Two relay outputs rated 20 Amp 120V tungsten
and ballast, 20 Amp 277V ballast
Two isolated NO/NC relays rated 1 Amp @
24VDC
NEMA 1 enclosure; acceptable for use in
plenum spaces
Output power 150mA @ 24VDC with automatic
overload protection
Dual voltage input 120 or 277VAC @ 14 Watts
maximum
Switch wiring distances up to 1000 feet with 18
gauge wire
Dimensions: 6.63” x 6.13” x 2.13” (168.4mm x
155.7mm x 54.1mm) with a 1/2 inch snap-in
nipple
UL and cUL listed
Five year warranty
LC-100 Wiring Connections, Inputs, and to Dimming Ballasts
LC-100 Wiring Connections
LC-100
24 VDC; 150 mA**
1*2020
Catalog No. Input Voltage Ballast (A) Incan (A) Motor (HP) Output
Load Ratings
* 1 Hp rated at 120/250 VAC. ** Output is 150 mA with relays connected.
120/277 VAC; 50/60 Hz
line voltage wiring
low voltage wiring
low voltage wiring
LC-100
low voltage switches
0 - 10V ballast
Junction
box
BLK Power
WHT Neutral
GRN Ground
RED Output 1
RED Load & Line
YLW Output 2
YLW Load & Line
LC-100
Intelligent Power Pack
Model #:
800.879.8585 • 972.578.1699
0-10V Ballast
Daylight
Shed
Unoccupied
24VDC
Shed Signal
Time Clock
Photocell
Occupancy
Sensor 24VDC
Designed and Manufactured in USA
Industrial Control
Equipment 83AJ
01627r1
1 Blink Disable
2 ON Only when occupied
3 Automatic ON
4 Dimming
5 Daylighting Enable
6 Time Override #1
7 Time Override #2
8 100 Hour Burn In
Configuration Switches
Load Output Rating
120/277VAC, 60Hz, 1hp
20Amp Tungsten or Ballast
Auxiliary Output Rating
1Amp, 24VDC
24VDC
OFF
ON
Sensor
24VDC
Com
Gray
Violet
- +
Shed
Level
- +
Max
Level
Type 1 enclosure
For operation within a
Maximum Ambient of 60°C
Acceptable for use in plenum
Low voltage wiring
Power
Neutral
Ground
Output 1
Load & Line
Output 2
Load & Line
WHT
GRN
RED
RED
YLW
YLW
BLK
Sensor Input
BLUE
RED
BLACK
+24VDC
COMMON
OCC SNS
LC-100 Terminals
Photocell Input
BLUE
RED
BLACK
+24VDC
COMMON
DAYLT
LC-100 Terminals
LS-100
Load Shed
Load
Shedding System
+24VDC
SHED
LC-100 Terminals
Time Scheduled Occupancy
+24VDC
UNOCC
LC-100 Terminals
Closed contacts signal non-
occupancy. Open contacts
signal occupancy.
Closed contacts signal load
shed. Open contacts restore
from load shed mode.
OPEN
12345678
O
N
OPEN
12345678
Max light level and shed light level settings
Connection terminals for occupancy sensors, time clocks, etc
Connection terminals switch inputs and
channel outputs (typical of 2)
Configuration switches
Status LEDs
Switch Input 1
Switch Input 2
1. All WattStopper power packs should be installed in accordance with state, local, and national electrical codes and requirements.
2. Power packs are designed to attach to existing or new electrical enclosures with 1/2 inch knockouts. (Check electrical codes in
your area.)
3. Low-voltage wiring should use stranded, 18-22 AWG, properly rated cable. Do not run low voltage Class 2 wiring with high voltage
wiring. For plenum return ceilings use UL listed plenum-approved cables.