Commercial (Non-Residential)
Architectural Drawing Requirements
Interior Alteration
These items should be shown on the architectural drawings submitted for permit.
Additional items may be required based on the specific project circumstances.
General(as indicated)
Drawing sheet size - 24” x 36” (preferred maximum
size)
Project address-every sheet
Drawing date-with revision date on each affected
sheet
North arrow on all plans
Scale
Architect’s (or Structural Engineer’s) name / address
/ telephone
Architect’s (or Structural Engineer’s) State of Illinois
seal with signature and date and license expiration
date – on cover sheet with index of drawings or on
every sheet. Required for all commercial alterations
where structural or egress modifications are
proposed
Applicable codes or include a reference to locally
adopted codes
Code data - including: zoning district, zoning
setbacks for each side, use group(s), construction
type, floor area, whether or not there is a fire
protection system, etc.
Structural design loads & material design values (if
applicable)
Accessibility compliance with Illinois Accessibility
Code (IAC) & ANCI 117.1 is required
Fire rated assembly designations & UL numbers for
walls, ceilings, etc. (if applicable)
On the cover sheet, state the method of energy code
compliance (prescriptive or performance type) and
submit compliance documents (if performance).
Indicate mandatory R-values for ducts, piping, etc.
SitePlan(as applicable and unless information is contained on
civil engineer’s or surveyor’s drawings)
For zoning compliance review where there is a
change of occupancy, parking calculations are
required with a site plan
It will be assumed for interior alterations that there is
a compliant accessible way to, and into, the building.
It is the applicant’s responsibility to include any site
and / or building entrance modifications as part of
the permit application if the accessible way is not
code compliant.
Indicate any new site equipment locations (if
applicable)
Indicate any new water service, sanitary or storm
sewer service sizes & locations
Plans (as required)
Demolition Plan-as required
‘Key Plan’ for project location
‘Egress (Life Safety) Plan’ (if applicable)
Floor Plan (including roof if necessary) with:
o Room names
o Dimensions
o Rated wall locations
o Wall, door & glazing locations
o Structural information (if altered)
o Mechanical-indicate locations of:
Supply/return ducts
Heating units
Other equipment
o Electrical-indicate locations of:
Service panel with size
Lights & switches (address IECC switching)
Receptacles
Emergency lights & exit signs
o Plumbing–indicate locations of:
Plumbing fixtures, incl. mop sink &
drinking fountains
Water heater
o Accessibility compliance dimensions-include
hatched boxes for clearances at all doors,
plumbing fixtures, etc.
Reflected Ceiling Plan (as required)
Elevations (as required)
Interior elevations
Exterior elevations (if any exterior work)
Details (as necessary)
HVAC ventilation schedule with outside air
indicated
Electrical schematic diagram Plumbing riser
diagrams
Door and hardware schedule
Energy code (IECC) compliance documents –
prescriptive or performance and indicate mandatory
requirements for ducts, piping, etc.
Construction details/sections/schedules
Door and hardware schedule