***DO NOT MAIL THIS FORM***
TP_009_F Fire Alarm System Certification Form
6
Section (A)
*Note: The certification of smoke
detector sensitivity shall be
performed according to the
Philadelphia Fire Code Section
907.
F-907: Alternate year sensitivity
testing shall begin in odd-
numbered years. Where the
one-year sensitivity test occurs
in an even-numbered year, the
next sensitivity test is not due
until the second subsequent
odd-numbered year.
Results of sensitivity tests shall
be listed on page 4 of this form or
an NFPA compliant panel printout
shall be provided for each year
testing is performed.
Complete Sections (B) and
(C) only if applicable.
• Are signs mounted at each pull station stating:
“IN CASE OF FIRE: SOUND ALARM AND CALL 911 or THE FIRE DEPARTMENT”? ☐Yes ☐No
• Are the manual fire alarm box tests acceptable? ☐Yes ☐No
• Are the smoke detector inspection / tests acceptable? ☐Yes ☐No
• Are the smoke detector thermal elements tests acceptable? ☐Yes ☐No
• Are the smoke detector control output tests acceptable? ☐Yes ☐No
• Are non-restorable heat detectors inspected and in satisfactory condition? ☐Yes ☐No
• Are restorable heat detector tests acceptable? ☐Yes ☐No
• Are the alarm verification tests satisfactory? ☐Yes ☐No
• Are the duct smoke detector tests acceptable? ☐Yes ☐No
• *Is the sensitivity of all Smoke Detectors tested in accordance with NFPA 72 (2016)
Section 14.4.4.3.4? ☐Yes ☐No
(B) Sprinkler System Supervision (complete if applicable) ☐Yes ☐No
If no, explain: ____________________________________________________________________________________
• Are the water flow switch inspection / tests acceptable? ☐Yes ☐No
• Are the valve tamper switch inspection / tests acceptable? ☐Yes ☐No
• Are the low temperature sensor inspection / tests acceptable? ☐Yes ☐No
• Are low air pressure switch inspection / tests acceptable? ☐Yes ☐No
• Are the Fire Pump power supervision inspection / tests acceptable? ☐Yes ☐No
• Are the Fire Pump Running supervision inspection / tests acceptable? ☐Yes ☐No
• Are the Fire Pump Trouble supervision inspection / tests acceptable? ☐Yes ☐No
• Are Fire Pump Alternate Power inspection / tests acceptable? ☐Yes ☐No
(C) Other Initiation (complete if applicable) ☐Yes ☐No
• Are all range hood / other suppression systems interconnected to this system as required? ☐Yes ☐No
• Are all range hood / other suppression systems inspections / tests acceptable? ☐Yes ☐No
• Are all existing air handler duct smoke detectors interconnected to this system? ☐Yes ☐No
• Were all air handler duct smoke detector inspection / tests acceptable? ☐ Yes ☐ No
7
Audible / Visible Devices
Section (A)
Complete the table on page 3 to
record the ambient and alarm
sound level tests.
(Continue on next page)
(A) AUDIBLE / VISIBLE DEVICES
• Are the ambient sound levels tested with the normal ambient noises present (HVAC, etc.)?
and recorded on Page 3? ☐Yes ☐No
• Are alarm sound levels tested and recorded on Page 3? ☐Yes ☐No
• Are visible alarms tested and operating properly? ☐Yes ☐No
• Did sound levels reach the minimum requirement noted below? ☐Yes ☐No
(check the appropriate box below)
☐ Systems installed prior to January 1984 = Sufficient volume to be heard
☐ January 1984 until March 1991 = 15 dba above ambient in occupied spaces
☐ May 1991 until December 2009 = 70 dba in sleeping rooms, 70 mechanical spaces, 60 in remaining spaces
☐ January 2010 until Present = 75 dba sleeping rooms, 70 in mechanical spaces and 60 in remaining spaces