DEDICATED CIRCUIT YES NO
DATE OF BATTERY
INSTALLATION OR “UNKNOWN”
PANELBOARD AND CIRCUIT
DESIGNATION
CHARGER TEST PASS FAIL UNK
CIRCUIT NUMBER IS LABELED ON
FIRE ALARM CONTROL UNIT
YES NO
LOAD VOLTAGE PASS FAIL UNK
DISCONNECTING MEANS IS
SECURED
YES NO
DISCHARGE TEST PASS FAIL UNK
DISCONNECTING MEANS IS
CLEARLY LABELED
YES NO
BATTERY CONDITION
ACCEPTIBLE
UNACCEPTIBLE
SYSTEM TESTS AND INSPECTIONS
NOTIFICATIONS ARE MADE PRIOR TO ANY TESTING
MONITORING ENTITY YES NO
BUILDING OCCUPANTS YES NO
BUILDING MANAGEMENT YES NO
FIRE MARSHAL YES NO
DEVICE TEST TYPE COMMENTS
CONTROL UNIT VISUAL FUNCTIONAL
________________________________________________________
LAMPS/LEDs VISUAL FUNCTIONAL
________________________________________________________
TROUBLE SIGNALS VISUAL FUNCTIONAL
________________________________________________________
AUDIBLE NOTIFICATION
DEVICES
VISUAL FUNCTIONAL
________________________________________________________
VISIBLE NOTIFICATION
DEVICES
VISUAL FUNCTIONAL
________________________________________________________
TELEPHONE LINE(s) VISUAL FUNCTIONAL
________________________________________________________
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
DEVICE LOCATION DEVICE TYPE TEST TYPE RESULTS
VISUAL FUNCTIONAL PASS FAIL
VISUAL FUNCTIONAL PASS FAIL
VISUAL FUNCTIONAL PASS FAIL
VISUAL FUNCTIONAL PASS FAIL
VISUAL FUNCTIONAL PASS FAIL
VISUAL FUNCTIONAL PASS FAIL
VISUAL FUNCTIONAL PASS FAIL
VISUAL FUNCTIONAL PASS FAIL
HAVE ANY DEVICES BEEN ADDED OR REMOVED SINCE THE LAST INSPECTION? YES NO
IS THE FIRE ALARM CONTROL UNIT PROTECTED BY A SMOKE DETECTOR? YES NO
WAS THE TRANSMISSION OF ALARM EVENTS TO THE MONITORING ENTITY CONFIRMED? YES NO
HAVE THE FOLLOWING BEEN NOTIFIED THAT TESTING IS COMPLETE? MONITORING AGENCY YES NO
BUILDING OCCUPANTS YES NO
BUILDING MANAGEMENT YES NO
FIRE MARSHAL YES NO
IS THE SYSTEM FUNCTIONING NORMALLY? YES NO
IS THE SYSTEM MONITORED? YES NO
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH NFPA 72
NAME OF INSPECTING
TECHNICIAN
_______________________________
NAME OF OWNER OR
REPRESENTATIVE
_____________________________
TECHNICIAN’S
SIGNATURE
_______________________________
OWNER OR REPRESENTATIVE
SIGNATURE
_____________________________
DATE:_____________________
ATTACH CENTRAL STATION’S LOG OF THE TEST TO THIS REPORT AND RETURN TO:
SAG HARBOR VILLAGE CODE ENFORCEMENT, PO BOX 660, SAG HARBOR, NY 11963
TEL 631-725-2804 FAX 631-725-4852
click to sign
signature
click to edit
click to sign
signature
click to edit