WATER SYSTEM AUDIT AND FLOW TEST
Address
City
State Zip
For
Well Size
Est. Depth
?
Est. Pump Set
?
Est. Static Level
Pumping Level
@
____
GPM* @
___
psi @
Amps. Pumping Duration
Pumping Level
Pumping Level
@
___
@
GPM* @ __
GPM* @
psi @
psi @
Amps. Pumping Duration
Amps. Pumping Duration
Max Pump Pressure
psi @
' @
Amps. Pipe size and type
Motor
HP Max Amps @
Volts
Windings Y-B
Y-R
B-R
Motor leads to ground
Ohms
Tank type
@
psi
Pressure set, on
psi, off
psi
Tank delivers
gal
New tank
gal
General condition of: Pump
Motor
Pressure Tank
___
Electrical
__
Piping
Misc. Wire is
UF is
Items in Need of Repair
Control box date
__
Estimated Cost of Repair
1.
2.
3.
4.
5.
(All work is done on a time and material basis)
Additional Comments:
.
Checked and certified by
Date
Print Name
Tech
Note: DATA ABOVE REPRESENTS CONDITIONS OBSERVED ON DATE OF FLOW TEST TO THE BEST OF OUR KNOWLEDGE. WE DISCLAIM ANY RESPONSIBILITY FOR ANY CHANGES IN WATER FLOW, FLUCTUATIONS IN DEPTH, WATER
QUALITY, MECHANICAL BREAKDOWN, OR OTHER CONDITIONS BEYOND OUR CONTROL. WE HAVE NOT REMOVED THE PUMP FROM THE WELL, SO THE PUMP SETTING, WELL DEPTH, OR WATER LEVELS MAY DIFFER FROM ABOVE DUE TO
PIPE AND WIRE OBSTRUCTIONS NORMALLY IN THE WELL. THE INFORMATION ON THIS PAGE IS PROPRIETARY INFORMATION AND MAY NOT BE COPIED OR USED IN ANY WAY WITHOUT CONSENT OF BRUCE MACKAY PUMP AND WELL
SERVICE, INC.*GPM MAY NOT BE REPRESENTATIVE OF A WELL'S LONG-TERM YIELD OR MEET THE NEEDS OR REQUIREMENTS OF ANY
PARTICULAR OWNER. PLEASE CALL FOR DETAILS.
1.
2.
3.
4.
5.
7465 Longley Lane
Reno, NV 89511
Office: (775) 851-1600
Fax: (775) 851-1602
"Your complete water system professional"
NV Lic.#23095 & 23096 CA Lic. #595616
License Limit $750,000
'
'
'
"
'
'
'
______
21-0196
2045 Applegate Road
Reno
NV
89521
Sandra Sokabe
6
-
327
12
0
13.2
5
361
7.5
40
10.3
40
352
6
60
11.2
20
100+
330
8.8
1 1/4. galv
2
13.2
230
2
5
6
Infinity
266
34
40
60
23
23
fair
worn
ok
-
-
-
10-4 sub
10-4 direct
15
None at this time.
The system was tested at the well head and yielded 7.5 gpm at 40 psi from 361'. The pump is showing
some normal wear as a new pump produces approximately 12 gpm at 40 psi from 360'. The motor is
showing wear and indicated; the amperages is increasing as the psi increases whereas it should be
decreasing. The pressure tank delivered the proper amount of draw down.
The system functioned at the time of service. Please call with any questions.
Stewart Kemp
7-22-21
Chris T.