Customer Guide for Electric Service West Virginia
September 2015
(Page Intentionally Blank)
i September 2015
TABLE OF CONTENTS
1.0 INTRODUCTION .........................................................................................................................................1
2.0 DEFINITIONS ..............................................................................................................................................2
3.0 GENERAL INFORMATION ..........................................................................................................................6
3.1 Availability & Character of Service ...............................................................................................................6
3.2 Application for Service .................................................................................................................................6
3.3 Line Extensions ............................................................................................................................................7
3.4 Number of Services & Meters ......................................................................................................................8
3.5 Use of Service by Customer ........................................................................................................................8
3.6 Interruption & Liability ...................................................................................................................................9
3.7 Final Connections ........................................................................................................................................9
3.8 Grounding/Bonding ................................................................................................................................... 10
3.9 Inspection .................................................................................................................................................. 10
3.10 Meter & Seal Tampering ........................................................................................................................... 10
3.11 Meter Attachments .................................................................................................................................... 10
3.12 Disconnect/Reconnect of Existing Service (Upgrades/Maintenance)....................................................... 11
3.13 Locating Underground Electric Facilities ................................................................................................... 11
3.14 Required Clearance from Markout for Digging in the Vicinity of Company Underground Electric
Facilities ................................................................................................................................................... 11
3.15 Buildings/Structures & Swimming Pools/Spas/Hot Tubs near Electric Lines ........................................... 11
3.16 Attachments on Company-Owned Facilities ............................................................................................. 11
3.17 Clearance of Trees from Power Lines ...................................................................................................... 12
3.18 Access to Customer’s Premises ............................................................................................................... 12
3.19 Company’s Equipment On Customer’s Premises ..................................................................................... 12
3.20 Requested Protection For Persons Working Near Company Facilities .................................................... 13
4.0 TEMPORARY SERVICE .......................................................................................................................... 13
5.0 PERMANENT SERVICE OVERHEAD .................................................................................................. 13
5.1 General ...................................................................................................................................................... 13
5.2 Service Drop Clearances .......................................................................................................................... 14
5.3 Mobile Homes or Mobile Home Parks ...................................................................................................... 14
5.4 Travel Trailer or RV Parks ......................................................................................................................... 14
5.5 Central Pole Distribution Metering Service ............................................................................................... 15
6.0 PERMANENT SERVICE UNDERGROUND .......................................................................................... 15
6.1 General ...................................................................................................................................................... 15
6.2 Underground Services from Overhead Lines ............................................................................................ 16
6.3 Underground Services in Underground Residential Areas ....................................................................... 16
6.4 Underground Services in Underground Commercial Areas ...................................................................... 16
6.5 Underground Services in Central Business District Network Areas ......................................................... 17
6.6 Transformer Foundations & Vaults ........................................................................................................... 17
6.7 Mobile Homes or Mobile Home Parks ...................................................................................................... 17
7.0 METER INSTALLATIONS ........................................................................................................................ 18
7.1 General ...................................................................................................................................................... 18
7.2 Meter Locations ......................................................................................................................................... 18
7.3 Group Meter Installations .......................................................................................................................... 19
7.4 Meter Relocations ..................................................................................................................................... 19
7.5 Minimum Meter Sockets Requirements .................................................................................................... 20
7.6 Metering Equipment Installation Guideline Summary ............................................................................... 22
7.7 Minimum Size Meter Socket - 480-Volt Services ...................................................................................... 23
7.8 Installations Requiring 400 Amperes & Less of Continuous Metering Load ............................................. 23
7.9 Installations Requiring Over 400 Amperes of Continuous Metering Load ................................................ 23
7.10 Approved Current Transformer Cabinets .................................................................................................. 24
7.11 Service at Voltages Greater Than 600 Volts ............................................................................................. 26
7.12 Disconnect Requirements ......................................................................................................................... 26
8.0 CUSTOMER EQUIPMENT ....................................................................................................................... 26
8.1 Motors (Inrush Limitations & Motor Protection) ......................................................................................... 26
8.2 Power Factor ............................................................................................................................................. 29
8.3 Welders & Industrial Furnaces .................................................................................................................. 29
8.4 Commercial Cooking, Space Heating, Water Heating, & Ice / Snow Melting ........................................... 29
8.5 Low-Voltage Surge Arresters (600 Volts or Less)..................................................................................... 29
September 2015
ii
8.6 UPS, Cogeneration, Back-up Generation, & Interconnected Generation ................................................. 29
8.7 Harmonic Producing Equipment ............................................................................................................... 30
8.8 Protective Devices .................................................................................................................................... 30
8.9 Special Equipment .................................................................................................................................... 30
iii September 2015
EXHIBITS
Service Material Guideline for West Virginia Operating Companies (2 pages) ................................... Exhibit 1
Service Drop Clearance Minimum for Services under 600 Volts ......................................................... Exhibit 2
Typical Temporary Service Overhead Installation ............................................................................... Exhibit 3
Typical Temporary Service Underground Installation ......................................................................... Exhibit 4
Typical Grounding Details ................................................................................................................... Exhibit 5
Typical Overhead Single-phase Service Entrance Installation 400 Amp or Less ................................ Exhibit 6
Overhead Service Typical Service Drop Attachment .......................................................................... Exhibit 7
Exhibit not used in West Virginia ......................................................................................................... Exhibit 8
Exhibit not used in West Virginia ......................................................................................................... Exhibit 9
Standoff Attachment of Customer Underground Service Lateral(s) on West Virginia Operating
Companies’ Poles ........................................................................................................................ Exhibit 10
Typical Overhead Service Central Distribution Installation ................................................................. Exhibit 11
Typical Underground Service Central Distribution Installation ............................................................ Exhibit 12
Typical Single Mobile Home Service Overhead & Underground ......................................................... Exhibit 13
Metering & Service Facilities for Mobile Homes & Travel Trailer Parks Four or More Meters ............. Exhibit 14
Metering Installation Single-Phase & Three-Phase 480-Volt Self-Contained Meter with
Source-Side Disconnect 400 Amp or Less .................................................................................. Exhibit 15
Multiple Metering Installation Self-Contained Metering 400 Amp or Less ........................................... Exhibit 16
Metering Installation Self-Contained Single-Phase 120/208Y V Network 400 Amp or Less ............... Exhibit 17
Metering Installation Three-Phase Self-Contained Metering 400 Amp or Less ................................... Exhibit 18
Metering Installation Indoor/Outdoor - Metering Cabinet with Current Transformers Details .............. Exhibit 19
Metering Installation Outdoor Current Transformer Cabinet Mounted On a Building .......................... Exhibit 20
Underground Secondary Service in Pad-Mounted Transformer with Current Transformers ............... Exhibit 21
Minimum Clearances from Structures for Oil-Filled Pad-Mounted Equipment .................................... Exhibit 22
Clearances of Pad-Mounted Equipment, Pedestals, Handholes, or Manholes from Shrubs, Plants,
Fences, Wall Screenings, & Other Obstructions .......................................................................... Exhibit 23
Typical Trenching Details for Installation of Secondary/Service Lateral & Primary
Conductors (Direct Buried or Conduit) (3 pages) ......................................................................... Exhibit 24
Three-Phase Transformer Pre-Cast Concrete Foundation (3 pages) ................................................ Exhibit 25
Concrete Flat-Pad Foundation Pad-Mounted Transformer 75 to 500 kVA Three-Phase,
34.5 kV & Below High-Side .......................................................................................................... Exhibit 26
Concrete Flat-Pad Foundation Pad-Mounted Transformer 750 to 2500 kVA Three-Phase,
34.5 kV & Below High-Side .......................................................................................................... Exhibit 27
Concrete Flat-Pad Foundation Pad-Mounted Transformer General Notes ......................................... Exhibit 28
Typical Single-Phase Box Pad Foundation Installation ....................................................................... Exhibit 29
Vehicular Barrier for Pad-Mounted Equipment .................................................................................... Exhibit 30
APPENDIX
Fax Application Builder Install Request Form 1046 ...................................................................... Appendix 1
September 2015
iv
SUMMARY OF MAJOR CHANGES TO THIS GUIDE
(September 2015)
This document replaces the “Customer Requirements for Electric Service. This new document is now titled,
Customer Guide for Electric Service WVand is specific to the FirstEnergy West Virginia Operating
Companies. Since this is the initial publication of this Guide, changes will not be highlighted in this version.
1 September 2015
1.0 INTRODUCTION
This Guide is published to provide pertinent information and guidance to assist customers and their
architects, engineers, builders, and contractors in planning for and obtaining a safe and prompt electric
service.
The information and exhibits contained herein convey general knowledge and do not provide every detail
or every requirement. Furthermore, the information is supplementary to, and does not intentionally
conflict with the National Electrical Code (NEC), the National Electrical Safety Code (NESC), the
Company’s (as defined in Section 2.0) current applicable tariffs, or such state and municipal laws and
ordinances as may be in force within the cities, towns, or communities in which the Company furnishes
electric service. It is always necessary to comply with state statutes, local ordinances, and the
Company's rules, regulations, and tariffs on file with the Public Service Commission of West Virginia.
To the extent that any included information contradicts any terms in the Company’s current applicable
tariff, the tariff provision shall govern.
The Company shall have the right to refuse to connect any wiring or installation that does not fully meet
the aforementioned requirements, regulations, and rules. The Company shall also have the right to
disconnect the wiring or installation of any customer violating any such requirements, regulations, or
rules. This action is not intended to imply that the Company undertakes any obligations to inspect the
customer's wiring and electrical facilities, to assume any obligations, or to make any representations
concerning their adequacy, safety, fitness for purpose, or other qualification. Nothing in the
aforementioned requirements, regulations, rules, or in this Guide shall be construed as imposing or
undertaking such obligations or representations.
All inquiries regarding service requirements should be directed to the Company’s local Engineering
Services Section. Inquiries regarding specific meter related requirements can be directed to the
Company's local Metering Services Section. Any inquiries regarding the NEC or local codes should be
directed to the local inspection authority.
Mandatory rules of this document are those that identify actions that are specifically required or
prohibited and are characterized by the terms shall or shall not.
This Guide is subject to amendment from time to time, and will be re-issued on an as needed basis. It
is the responsibility of the user to obtain the current version. The current edition of this Guide supersedes
all previous issues and instructions.
The current edition of this guide is available at www.firstenergycorp.com/builders-contractors
.
In the future, significant changes to text from the last published version will be identified in the document
by a vertical bar in the outward margin (see example in the right margin of this paragraph). Changes to
the exhibits will be identified by small triangles pointing to the revisions. Note: These triangles point to
changes made to exhibits on the revision dates shown in the lower right corner of the exhibits.
Comments, corrections, and suggestions regarding this document should be submitted in
writing to the Director, Operations Services at FirstEnergy Service Company, Energy Delivery
Operations Services Department, 76 South Main Street, A-GO11, Akron, Ohio 44308.
September 2015
2.0 DEFINITIONS
Terms frequently used in this Guide are as defined below (for additional definitions, refer to the latest
edition of the National Electrical Code):
American National Standards Institute (ANSI): ANSI is an independent administrator and
coordinator of voluntary industry standards (www.ansi.org
).
American Transmission Systems, Incorporated (ATSI): ATSI is one of FirstEnergy’s electric
transmission subsidiaries.
Ampacity: Ampacity is the maximum current, in amperes (amps), that a conductor can carry
continuously under the conditions of use without exceeding its temperature rating.
Application for Service: Application for service is a formal request submitted by the customer to the
Company stating their desire to obtain electric service at a certain time and location. Applications
may be processed by e-mail, telephone, or fax.
Approved: Work or equipment that is acceptable to the FirstEnergy Operating Company or to the
authority having jurisdiction.
Central Business District (CBD) Network: A CBD network is a specialized electrical underground
system that serves a defined area located in the heart of the city (a.k.a. downtown) that is typified
with a high concentration of commercial, retail, and office buildings.
Class of Service: The characteristics of electric service described in terms of voltage, phase,
frequency, and number of wires.
Clearance: Clearance is a specified minimum distance between two objects (measured surface-to-
surface) to assure adequate space for safety, security, or access.
Code: The National Electrical Code (NEC), National Electrical Safety Code (NESC), or other electrical
codes or regulations in effect in the area served.
Company: Refers to the FirstEnergy Operating Companies (FEOC) operating in West VirginiaMon
Power and Potomac Edison.
Current Transformer (CT): Current Transformer is a transformer whose secondary current is a
precise fraction of its primary current (refer to instrument transformer definition).
Customer: The party using the Company's service, or in applicable cases, the property owner or
developer or any party working on behalf of the customer such as an engineer, builder, contractor,
or developer.
Customer's Installation: All wiring, conduit, meter socket, service disconnecting devices, appliances,
lighting, and other equipment installed and/or owned by the customer on the customer’s premises
for the customer’s use. The customer’s electrical equipment is typically governed by the NEC.
Development: A planned project, which is developed by a developer/applicant, for electric service
set out in a recorded plot plan for the construction of single-family residences, detached or otherwise,
mobile homes or apartment houses, all of which are intended for year-around occupancy, if electric
service to the lots necessitates extending the utility’s existing distribution lines.
Distribution Lines: Company lines medium voltage and below typically located in the public right-of-
way in/or along streets, alleys, highways, or on private property for general distribution of electric
service to customers.
3 September 2015
Environmental Protection Agency (EPA): is an agency of the U.S. federal government that protects
human health and the environment by writing and enforcing regulations based on laws passed by
Congress (www.epa.gov).
Federal Aviation Administration (FAA): The Federal Aviation Administration is the national aviation
authority of the United States. An agency of the United States Department of Transportation, it has
authority to regulate and oversee all aspects of American civil aviation (www.faa.gov).
Final Grade: Final grade shall refer to the eventual permanent ground level after all finished grading,
paving, and landscaping is completed.
High-Leg: On a four-wire, delta-connected system where the midpoint of one phase winding is
grounded to supply lighting and similar loads, the conductor or busbar having the higher phase
voltage to ground shall be durably and permanently marked by an outer finish that is orange in color
or by other effective means. Such identification shall be placed at each point on the system where
a connection is made if the grounded conductor is also present (Reference NEC Article 110.15 &
230.56).
Instrument Transformer: An instrument transformer is a high quality transformer that accurately
reproduces in its secondary circuit, a current (CT) or voltage (VT) in proportion to the current or
voltage in the primary circuit.
Institute of Electrical and Electronics Engineers IEEE): is an organization composed of engineers,
scientists, and students. The IEEE is best known for developing standards for the computer, electrical,
and electronics industries (www.ieee.org)
.
Line Extension: Line Extension is the extension of the Company’s distribution facilities, such as pole
lines, underground lines, substations, and transformers for the supplying of electric energy to a
customer or group of customers.
Listed: Equipment, materials, or services included in a list published by an organization that is
acceptable to the authority having jurisdiction and concerned with evaluation of products or services,
that maintains periodic inspection of production of listed equipment or materials or periodic
evaluation of services, and whose listing states that the equipment, material, or services either meets
appropriate designated standards or has been tested and found suitable for a specified purpose.
Meter: Meter is a device for accurately measuring the electric power and energy consumed by a
customer. The Company provides, installs, and maintains the meter.
Meter Socket: A meter socket is a mounting device consisting of meter jaws, connectors, and
enclosure for receiving a socket-type meter.
Mobile Home: A mobile home is a manufactured home that complies with the mobile home definition
in the NEC.
National Electrical Code [NFPA 70] (NEC): is a set of national regulations that govern the installation
of electrical equipment located on the customer’s side of the point of service.
National Electrical Safety Code [IEEE C2] (NESC): is a set of national regulations that govern the
installation, operation, and maintenance of the electric supply and communication lines. NESC
applies to equipment located on the electric utility’s side of the point of service.
National Fire Protection Association (NFPA): is a United States trade association, albeit with some
international members, that creates and maintains private, copyrighted, standards and codes for
usage and adoption by local governments (www.nfpa.org)
.
September 2015
Notification or Design Request (DR) Number: A unique number assigned by the Company used
for designing, tracking, constructing, and billing of a specific job.
Occupational Safety and Health Administration (OSHA): is a federal government agency in the
Department of Labor to maintain a safe and healthy work environment (www.osha.gov)
.
Public Service Commission of West Virginia (PSC of WV): The state regulatory agency that has
jurisdiction over the West Virginia electric utilities (www.psc.state.WV.us
).
Point of Service: Point of service is that point where the Company's equipment or conductors connect
to the customer’s conductors or equipment of the facility.
Raceway: A raceway is an enclosed channel for holding wires or cables.
Select Backfill: Soil or sand free from sharp objects, rocks, scrap building material, or corrosive
material used to backfill a trench for buried cable or conduit.
Service: Delivering electric energy from the Company’s distribution system to a single point of
connection at a customer's premises.
Service Drop: A service drop is a Company-owned set of overhead conductors (including the
connectors) that extend from the last pole or other aerial support to the customer-owned service
entrance conductors at the building or other structure.
Service-Entrance Conductors, Overhead System: The service entrance for an overhead system is
the group of service conductors between the terminals of the service equipment and a point usually
outside the building, clear of building walls, where joined by tap or splice to the service drop.
Service-Entrance Conductors, Underground System: The service entrance for an underground
system is the group of service conductors between the terminals of the service equipment and the
point of connection to the Service Lateral.
Service Equipment: The necessary equipment, usually consisting of circuit breaker or switch and
fuses, and their accessories, located near point of entrance of supply conductors to a building, and
intended to constitute the main control and means of cutoff for the supply to that building.
Service Lateral: A set of underground service conductors extending from the Company’s electric
distribution facilities, including any risers at a pole or other structure or from transformers, handholes,
or pedestals to the first point of connection to the service entrance conductors in a terminal box,
meter, or other enclosure with adequate space, inside or outside the building wall.
Service Territory (electric): Service territory is a defined area in which a given electric utility can
legally provide service. The area is governed by a set of agreements and maps on file with the PSC
of WV.
Tariff:
The applicable Company tariff as filed with, and approved by, the PSC of WV.
Temporary Service: Service supplied for construction purposes or of limited duration and delivered
to a single point through one meter.
Trans-Allegheny Interstate Line Company (TrAIL Co): TrAIL Co. is one of FirstEnergy’s electric
transmission subsidiaries.
Underwriters Laboratories (UL): Underwriters Laboratories is an independent product testing and
certification organization.
5 September 2015
Uninterruptible Power Supply (UPS): An uninterruptible power supply (e.g., battery or flywheel
backup) is an electrical apparatus that provides emergency power to a load when the input power
source is not available.
Voltage Flicker: Voltage flicker is defined as a sudden fluctuation in system voltage, which can result
in objectionable changes in the light output of electric lamps.
September 2015
3.0 GENERAL INFORMATION
3.1 Availability & Character of Service
The information contained in this Guide refers predominately to service requirements at the usual
voltages for residential and general service installations. Service installations greater than 600
volts are not covered in this Guide. The customer should contact the Company with questions
regarding service at voltages greater than 600 volts. The Company's rules, regulations, and tariffs
as filed with the PSC of WV, shall apply to the installation and use of the service furnished.
The customer shall consult the Company to determine whether the desired service is available in
the particular location. This request should be made well in advance of the date actual service
connection is required. If service is available, determine its exact character; that is, the voltage
(such as 120/240 V, 208Y/120 V, or 480Y/277 V), single-phase, three-phase, etc., since these
characteristics may vary in different locations. These characteristics are especially important for
the proper operation of motors and other major equipment. Normally, this information will be
provided in writing from authorized Company personnel to avoid possible misunderstanding.
The service voltage of 240/120 volt delta is not available for underground service energized from
an underground primary source regardless of the source voltage. This service is available from
an overhead closed-delta or open-delta transformer bank energized from an overhead 12.5 kV
and below primary source. Also, this service is available from an open-delta transformer bank
with a maximum transformer capacity of 1-75 kVA and 1-25 kVA energized from an overhead 34.5
kV primary source. Overhead closed-delta transformer banks are not permitted on a 34.5 kV
primary source.
The Company may, if requested, advise and assist existing or prospective customers in the
selection of electrical equipment, facilities, capacitors, and protective coordination.
3.2 Application for Service
The customer shall make applications for each class of service for new, upgraded, or relocated,
permanent or temporary service or when the customer identity changes. Before service is
supplied by the Company, the customer shall complete the application process. Application may
be submitted via the telephone, fax, or the Internet to a Company business office; and should be
submitted well in advance of the date, actual service is required. The appropriate telephone and
fax numbers and Internet address are listed below:
West Virginia Companies
Telephone Number
Fax Number
Mon Power
800-686-0022
877-289-3674
Potomac Edison
800-686-0011
A copy of the Fax Application Builder Install Request Form 1046 can be found in Appendix 1.
Application for electric service can found online at
www.firstenergycorp.com/builders-
contractors. Then click on Establish or Upgrade Service Form” under the headingOnline Form
for New Construction or Service Upgrade.”
After the necessary customer information is received and all customer requirements are met, the
typical minimum lead-time to complete Company work is as follows:
Type of Extension
Lead-time
Residential Service Drop / Lateral
4 weeks
Residential Line Extension
8 weeks
Commercial/Industrial Drop / Lateral
6 weeks
Commercial/Industrial Line Extension
16 weeks
Residential/Commercial/Industrial Development
16 weeks
7 September 2015
These recommendations should allow service to be established as near to the desired time as
practicable. Your Company representative will provide additional information on service
particulars, work scope, and timelines.
The following information is required from the customer. The Company cannot begin work until
the necessary information is provided:
1. Service address (including nearest intersecting roads),
2. Lot number (and block number where applicable) and subdivision name,
3. County/Tax District name,
4. Contact persons (developer/architect, electrical contractor, etc.) names, addresses, mailing
addresses, and their telephone/fax numbers,
5. Owner name, address, mailing address, and telephone/fax numbers,
6. Person to be billed (including their Tax ID or Social Security Number) and the mailing address,
7. Type of electric service required overhead (OH) or underground (UG),
8. Service voltage desired (e.g., 120/240 V single-phase, 208Y/120 V three-phase, or 480Y/277
V three-phase),
9. Amp rating of the main disconnecting means,
10. If Residential: Determine heating fuel (oil, gas, electric, etc.), water heater fuel, electric range,
air conditioning (size, if yes), total square feet, preferred electric meter location, and number
of services. Also, determine if any other large or special electric loads (e.g., welder or kiln)
will be used.
11. If General Service (Commercial/Industrial): Electric one-line, load information (nameplate
data) for all single-phase motors larger than five hp, three-phase motors larger than ten hp,
tons of air conditioning, kW process heat, kW lighting, kW computers, presses, welders, x-ray
machines, and other equipment having an in-rush current or other potentially disturbing
characteristic, as well as other unusual loads.
12. For Developments: An approved plot plan drawn to scale showing crossroads, proposed
structures, wells, septic, decks, drives/parking areas, pools, ponds, preferred service route,
planned major landscape changes and future development areas, and any other known or
proposed obstructions that may interfere with the Company supplying electric service.
Electrical loading information will be required for the design. The customer/developer shall
provide an executed Company standard blanket utility easement for their developments prior
to individual lots being sold or the installation of any Company electrical facilities.
13. Date that the electric service is wanted.
14. For interconnected generation (solar, wind, etc.) see Section 8.6.
The customer/developer shall provide the Company with a copy of the customer plot plan showing
the locations of buildings, lot numbers, property lines, streets, parking lots (if applicable),
easements, underground facilities, obstructions, or utilities (if known), as well as proposed electric
service entrances and metering locations. The customer/developer shall stake the locations of all
proposed buildings, the lot lines, and driveways so that the Company can decide where to install
its facilities.
The Company may refuse to provide electric service, consistent with West Virginia law and
Company tariffs.
3.3 Line Extensions
To avoid delay, customers desiring service beyond the existing electric distribution lines of the
Company are advised to inquire of the Company the conditions under which service will be
extended and make the necessary arrangements before wiring installations are commenced.
Depending on the situation and the nature of the facilities desired or required, the customer may
be responsible for some of the preparation and clearing of the property to clear trees and
vegetation or provide access to Company vehicles and personnel, rights-of-way acquisition,
September 2015
easements, permits, construction costs, and, for underground extensions, trenching and
backfilling. Note: difficulties in obtaining private rights-of-way and governmental permits (e.g.,
FAA, Army Corp of Engineers, or EPA permits) may result in significant delays to the construction.
Cost contributions are defined in the applicable Company’s Tariff. The Company can provide the
terms and conditions of extending its facilities to supply service upon request.
The requirements for a residential structure to be considered a permanent installation:
Masonry or Wood Structure (“stick built” or Modular) Type Home:
Directly connected to a public water system, water well, or other reasonable source of
potable water meeting all applicable local requirements,
Directly connected to an approved septic system, a public sewage system, or an alternate
sewage method meeting all applicable local requirements,
Containing a living area, kitchen, and bathroom,
Located on a permanent foundation.
Mobile or Manufactured Home:
Directly connected to a public water system, water well, or other reasonable source of
potable water meeting all applicable local requirements,
Directly connected to an approved septic system, a public sewage system, or an alternate
sewage method meeting all applicable local requirements,
Wheels and axles removed,
Underpinnings or some type of permanent connection (anchoring).
Vehicle-type units primarily intended as temporary living quarters, to include, but not limited to,
recreational vehicles (“RV’s”), motor homes, travel trailers, truck campers, park trailers and
camping trailers shall not be considered as permanent. Mobile or manufactured homes for the
purpose other than as a dwelling unit (i.e. on-site offices, mobile dressing rooms, banks, clinics,
stores, or mobile displays) shall not be considered as permanent.
3.4 Number of Services & Meters
The Company will connect only one set of service conductors to each separate dwelling (single or
part of a multiple unit), apartment, farm, commercial or industrial establishment as one customer
through one meter or one unified set of meters. Therefore, customers will typically be served at
one voltage at either single-phase or three-phase, but not both. If occupied by several customers,
each customer may have one meter for each class of service rendered. All customer installations
shall conform to the NEC and local codes. Parallel runs of service cable extending from Company-
owned equipment to multi-position meter centers should be avoided and require prior Company
approval.
Upon request and if Company approved, a second service may be permitted based on the
exceptions listed in NEC Article 230.2. A permanent plaque or directory shall be installed at each
service drop or lateral, or at each service equipment location. It shall denote all other services on
or in that building or structure, and the area served by each.
3.5 Use of Service by Customer
Customer-owned wiring and electrical equipment shall be sufficiently sized (per NEC) and listed
for its intended application.
The customer’s wiring and equipment including the self-contained meter socket shall be installed
and maintained by the customer, at the customer’s expense, and in the condition required by the
insurance providers, governmental authorities having jurisdiction, and Company requirements.
It is necessary for the protection of the customer that all work, wiring, and apparatus be installed
and maintained by a qualified electrician. A qualified electrician is one who has the skills and
9 September 2015
knowledge related to the construction and operation of the electrical equipment, systems, and
installations and has received safety training to recognize and avoid the hazards involved.
The Company’s facilities, which are used to provide electrical service, have limited capacity and
may be damaged if they are overloaded. Therefore, the customer shall notify the Company prior
to increasing their energy usage or altering their service equipment so that Company facilities of
proper capacity may be provided. Failure to properly notify the Company of such additional
requirements may result in an extended outage or in damage to the customer’s and/or Company’s
equipment. The customer shall be responsible for all expenses and/or damages to the customer’s
and/or Company’s facilities resulting from failure to give proper notification. The customer may
also be subject to charges by the Company for work required to meet the customer’s alterations.
The customer should contact the Company for information concerning charges for such work.
The service shall not be used in any manner that disturbs or impairs the operation of the
Company's system or that will interfere with service to other customers. If such interference does
occur, due to the use of apparatus installed upon a customer's premises, such customer shall
either discontinue the use of such apparatus or make the necessary revisions to the apparatus,
including additional equipment that may be required to alleviate such conditions, or the Company
shall have the right to discontinue the offending service.
For proper service, the wiring on all single- or three-phase installations shall be arranged so that
the load, to the extent possible, is balanced among each phase-wire. For three-phase services,
the load imbalance between phases shall not be greater than 15 percent of the customer’s peak
load.
3.6 Interruption & Liability
*
The Company will use reasonable diligence in providing regular and uninterrupted service, but the
Company shall not be liable for any loss, cost, damage or expense to any Customer occasioned
by any failure to supply electricity according to the terms of the contract, or by any interruption or
reversal of the supply of electricity, if such failure, interruption or reversal shall be due to the
elements, public enemies, strikes, or order of Court, which are beyond the control of the Company,
or any cause except wilful default or neglect on its part.
3.7 Final Connections
Residential/Commercial - All final connections for temporary or permanent service, between the
Company's facilities and the customer's wiring, shall be made by the Company. Refer to Exhibit
1 to determine party responsible for supplying connectors.
The Company shall assume no responsibility for changing the location of its service drop
attachments if an improper location is chosen without consultation with the Company, or if the
mutually acceptable location is not utilized.
If it becomes necessary for the Company to change the location of its facilities or the character of
the electrical service to comply with the requirements of governmental agencies, codes, or other
causes beyond the Company’s control, the customer shall, at the customer’s expense, change its
facilities (e.g., customer’s wiring, service entrance, and utilization equipment) to accommodate the
Company changes.
Service entrance equipment interrupting capacity shall meet or exceed the maximum available
fault current. The customer should contact the Company to determine the estimated available
fault current and subsequently determine the minimum required equipment rating.
*
To the extent this provision contradicts any terms in the Company’s current applicable tariff, the tariff provision
shall govern.
September 2015
10
3.8 Grounding/Bonding
The customer shall install the service entrance so that all of the grounding/bonding requirements
of the NEC are met or exceeded. The customer’s service entrance shall have a minimum of two
driven ground rods (8 feet minimum length) at least six (6) feet apart. The grounding electrode
conductor shall be continuous from the service entrance main disconnect to both driven ground
rods. Refer to Exhibit 5.
3.9 Inspection
In addition to complying with the NEC, the service shall be in accordance with the requirements
of the Company and such state and local inspection requirements as may be in force at the time
such installation is made.
Before a new, temporary, upgraded, modified, or repaired service to a customer service location
is energized, the Company should verify that the installation of the customer’s meter socket and
associated equipment has been inspected and approved by the local or state electrical inspection
authority.
When the Company deems that a potentially hazardous condition exists, it may refuse to energize
the customer’s service until the customer remedies any deficiencies.
Service Restoration - Fire or Flood: If the meter or service entrance equipment has been subjected
to fire or flood conditions, an inspection from the above referenced authority, and a release, when
applicable, from a Fire Marshall or equivalent is required before service will be restored.
Service Restoration Disconnected Services: If a service has been disconnected (i.e., service
wires cut) for twelve (12) months or more, a new inspection by the local or state inspection
authority is required before the service will be reconnected.
3.10 Meter & Seal Tampering
Tampering means to interfere with, damage, or by-pass a utility meter, conductor, or attachment
with the intent to impede the correct registration of a meter or the proper functions of a conductor
or attachment so far as to reduce the amount of utility service that is registered by the meter.
Tampering includes the unauthorized reconnection of a utility meter, conductor, or attachment that
has been disconnected by the utility.
In the event of tampering, or theft of service by the customer, consumer, or other person, the
Company will comply with the provisions of West Virginia law and Company tariffs. Services that
have been disconnected due to tampering may require an electrical inspection before
reconnection.
Breaking of meter seals and/or removal of meters by customers, electrical contractors, or other
unauthorized personnel, without prior Company permission, is prohibited and may be subject to
penalties.
3.11 Meter Attachments
No attachments by the customer or the customer’s agent are permitted to Company-owned
meters, meter circuits, or ancillary meter devices.
The Company will supply, upon request by a customer, kWh and/or kvarh pulses from a Company-
owned meter for demand control purposes. A cost will be assessed to the customer in accordance
with specific Company charges for this connection.
11 September 2015
3.12 Disconnect/Reconnect of Existing Service (Upgrades/Maintenance)
When upgrading or performing maintenance on an existing service, the customer shall first contact
the Company’s Customer Contact Center for guidance and applicable fees. Customers,
electricians, and contractors (not working under contract to the Company) are not permitted to
disconnect/reconnect overhead service drops. All overhead and underground electrical upgrades
shall be inspected prior to reconnection (refer to Section 3.9).
The Company reserves the right to update meter and service locations at the time of upgrade for
the purposes of applying current clearance requirements and meter location guidelines. Service
equipment installed without approval or incorrectly located shall be subject to change or relocation.
3.13 Locating Underground Electric Facilities
State laws require that an excavator notify the One-Call System in advance of digging. Trained
personnel will locate and mark electrical underground facilities.
To simplify the "Call before You Dig" calling process, 811 has been designated by the FCC as a
nationwide telephone number. In West Virginia, the 811 number will transfer a caller to the
appropriate state One-Call system. You may also contact the appropriate One-Call agency online
at www.call811.com/state-specific.aspx
.
For projects in West Virginia - call West Virginia 811 at least 48 hours but not more than ten
(10) working days, excluding weekends and legal holidays, before digging at #811 or (800) 245-
4848 to request that a location be marked. The Center is open 24 hours/day and 365 days/year.
For more information, or to enter locate tickets, visit www.wv811.com
.
3.14 Required Clearance from Markout for Digging in the Vicinity of Company Underground
Electric Facilities
After the underground facilities have been located (refer to Section 3.13), hand digging is required
within a tolerance zone, which is 18 inches from all sides of the markout stake, flag, or hash mark
and the closest edge of any parallel trench dug by another party adjacent to the Company’s
underground facilities.
3.15 Buildings/Structures & Swimming Pools/Spas/Hot Tubs near Electric Lines
Buildings and structures (including signs, flagpoles, light standards, antennas, or aerials) shall not
be installed under, over or in such proximity to electric lines that they could be raised into or fall
onto such lines or that they cannot be safely maintained. Antennas, aerials, or any device shall
not be attached to a Company pole or any pole supplying electric service to the customer without
specific Company authorization. NESC/NEC clearances shall be maintained. The customer
should consult the Company for specific clearance requirements and possible easement
restrictions.
The Company does not recommend placing a swimming pool, spa, or hot tub under its existing
service drop or other electrical conductors. Specifically, a swimming pool shall not be located
within a minimum of twenty-five (25) feet of the Company’s overhead conductors measured
horizontally from the edge of the pool without written approval from the Company. The clearance
between the Company’s underground cables (primary and secondary) and the edge of the pool
or its auxiliary equipment shall not be less than five (5) feet (measured horizontally).
3.16 Attachments on Company-Owned Facilities
Under no conditions shall the customer’s facilities or other equipment such as signs, posters,
banners, or notices be installed on the Company’s poles or other property unless special
arrangements have been made with the Company. The customer shall contact the Company for
details. The Company does not permit painting of Company-owned equipment by the customer.
September 2015
12
3.17 Clearance of Trees from Power Lines
Trees & Transmission Rights-of-Way
ATSI, TrAIL Co, and the Company's long distance, high voltage transmission lines provide
power to thousands of our customers and are vital reliability links with other utilities across the
country. Keeping our transmission rights-of-way free of unwanted trees and other vegetation
is very important to providing reliable and safe electric service.
All vegetation on or adjacent to the right-of-way shall be low-growing, compatible species.
Additional information on correct tree selection can be found at
www.firstenergycorp.com/trees. Click on “Maintaining Transmission Rights-of-Wayon the
left side of the page.
Trees & Distribution Lines
Tree related incidents are a major cause of electrical outages. Therefore, care must be
exercised when planting trees to make certain that they will not interfere with distribution power
lines, even when the trees reach full, mature growth. Trees that grow more than 25-feet tall
should not be planted within 20 feet of distribution power lines.
Additional information on correct tree selection can be found at
www.firstenergycorp.com/trees. Click on “Selecting the Right Tree for the Location” on the
left side of the page.
3.18 Access to Customer’s Premises
The customer or, if applicable, the landlord, shall grant the Company's employees and authorized
agents access to the customer's premises at all reasonable hours for the purposes necessary in
connection with supplying and maintaining service, and upon termination of service, to remove
any or all such property. In the event of an emergency, the Company's employees and authorized
agents shall have access to customer’s premises at any time. Authorized Company employees
are furnished with a photo identification badge with the Company logo. This badge is available
upon request when they are visiting the customer’s premises.
The customer shall not block access to Company equipment by installing vegetation, fences, walls
or any other obstructions that prohibit access to Company equipment. The customer shall be
responsible for all expenses and/or damages for blocking access to company equipment. The
customer shall contact the Company for details.
If a customer or a property owner fails to grant access for reasons described above, and legal
action is necessary to secure such access, the Company may collect from the customer or the
property owner any and all costs incurred to secure such access.
3.19 Company’s Equipment On Customers Premises
The customer shall provide without cost to the Company, satisfactory right-of-way and a suitable
location for the Company’s equipment, which is necessary for supplying service to the customer
on the premises owned or leased by the customer.
The customer shall provide truck access to all three-phase overhead transformer installations,
pad-mounted transformer (single- and three-phase) installations and other equipment and poles
designated by the Company. The truck access drive shall be a minimum of twelve (12) feet in
width, installed to withstand a 40,000-pound line truck and associated equipment (crane, flatbed
trailer) including the weight of the piece of equipment, and be located within ten (10) feet of the
designated piece of equipment. All access drives shall be permanent, continual, maintained, and
visible for all-season access. Customer shall contact the Company for details.
13 September 2015
3.20 Requested Protection For Persons Working Near Company Facilities
The customer or contractor shall provide reasonable advance notification to the Company when
proposed work is to be performed within such distance of the Company’s facilities that may be
hazardous to the person(s) performing the work, or may otherwise be in violation of federal or
state regulations. The Company may cover, de-energize, or temporarily move its facilities in the
work area, as it deems appropriate. The Company may bill the notifying customer or contractor
for the total cost of performing such work. If circumstances require work outside the normal work
hours, costs for the overtime period will be computed and billed at overtime rates. The customer
or contractor will be required to sign an Acknowledgement/Indemnification Agreement. The
customer should contact the Company for details.
4.0 TEMPORARY SERVICE
When requested by the customer, the Company may provide a temporary overhead or underground
service. The service entrance, meter, and other wiring on temporary indoor or outdoor installations are
installed in the same manner as for permanent installations. When no building is available for the
installation of service conductors and service equipment, the customer shall consult the Company's local
office for recommendations as to suitable support for the service drop or termination of service lateral,
meter, and weatherproof housing for the service equipment. Refer to Exhibit 3 (overhead) and Exhibit
4 (underground) for typical requirements for temporary service structures.
An application for service is required for any temporary service. Refer to “Application for Service” Section
3.2 for additional information regarding temporary service.
Temporary electric service installations should not exceed one year.
The service drop or service lateral shall be extended from the existing overhead secondary, pad-
mounted transformer or pedestal/handhole. The customer shall contact the Company for applicable
fees and limitations.
5.0 PERMANENT SERVICE OVERHEAD
5.1 General
The customer, architect, or contractor shall contact the Company prior to the start of construction
to ascertain the point of attachment for the service drop, type of metering facilities, costs, and
other information relative to the service. Where overhead distribution facilities are available, the
Company will install a suitable overhead service drop to a point of attachment on the customer’s
premises as designated by the Company. The point of attachment will be located to provide the
least cost and shortest practicable service drop distance to the Company’s facilities. The point of
service is the connection of the overhead service drop to the customer’s service entrance
conductors/equipment. The Company shall provide, own, install, and maintain the service drop
conductors from the overhead distribution system to the point of service.
The customer shall provide and maintain a safe, substantial support for the Company’s overhead
service conductors. The service drop support shall be installed in such a manner to maintain the
clearances specified in Section 5.2 and Exhibit 2. The customer shall furnish, install, and maintain
the service bracket necessary for the attachment of the Company’s service drop conductors (refer
to Exhibit 7). In cases where a service mast is required, only power service-drop conductors shall
be attached to the service mast.
In general, service entrance conductors should be installed on the outside of the building to be
served.
When the customer’s load necessitates parallel service entrance conductors, the customer shall
furnish and install suitable equipment (Company approved) to allow the Company to connect the
service drop with a single set of attachments. The customer shall minimize the number of
September 2015
14
conductors to reduce both the electrical connections and the complexities inherent in such
installations.
Refer to Section 3.8 and Exhibit 5 for grounding requirements.
Refer to Exhibits 1, 2, 5, 6, 7, 11, and 14, for typical installations.
5.2 Service Drop Clearances
The point of attachment of the service drop to the building shall be such that the drip loop shall
not be less than ten (10) feet above the ground. In addition, the point of attachment shall be
located to allow the Company to comply with NESC/NEC clearance requirements. The
attachment should not be more than 24 feet above ground unless a greater height is necessary
for proper clearances.
The service drop should not be installed over buildings or swimming pools, spas, or hot tubs.
Some of the more common NESC/NEC minimum clearance requirements are listed below and
most are illustrated on Exhibit 2.
Twelve (12) feet for a multiplex service or twelve feet-six inches (12.5) for an open wire service
above sidewalks and spaces accessible to pedestrians,
Eighteen (18) feet above roads, streets, alleys, driveways and other areas subject to truck
traffic,
Two (2) feet above communication lines (e.g., telephone, CATV) at any point of crossing, and
one (1) foot at the point of attachment to the building,
Three (3) feet between service drop conductors (attached to the buildings) and windows,
doors, porches, and fire escapes,
Five (5) feet between service drop conductors (not attached to the buildings) adjacent to
windows, awnings, fire escapes and other building projections,
Three and one-half (3.5) feet between the service drop conductors and the roofs of projections
that are not accessible to pedestrians.
The service drop shall not cross over property other than that of the customer being served unless
the Company has been provided an executed right-of-way agreement or permit from the owner of
such property.
5.3 Mobile Homes or Mobile Home Parks
The Company has an established policy for extending electric service to mobile homes and may
assist in planning the installation of mobile home parks. The Company's tariffs, as filed with the
PSC of WV, shall apply to the installation and use of the service furnished.
Meter and service facilities for a mobile home or mobile home parks will be determined on a case-
by-case basis.
For non-subdivision type mobile home parks, the Company recommends a group meter
arrangement (Refer to Exhibit 14 for typical installations). Mobile home park operators shall be
responsible for the effective grounding of all mobile homes. Additional information is available
upon request from the Company.
5.4 Travel Trailer or RV Parks
Typically, electric service requirements for travel trailer or recreational vehicle (RV) parks will be
served through one metering point (refer to Section 3.4). The customer should contact the
Company for additional information.
15 September 2015
5.5 Central Pole Distribution Metering Service
A farm or commercial operation with specific load requirements may have service from a
customer-owned central distribution service drop. The customer shall furnish, install, and own a
pole centrally located with respect to the various buildings to be served. The central distribution
pole in each case shall be a dead-end pole, as far as the Company lines are concerned, without
any unmetered service extending beyond it.
If it is impractical to serve all farm buildings from a centrally located pole due to distance between
buildings or the necessity of crossing public roadways, the Company will provide services and
meters for separate accounts for each building, as conditions require.
For details, refer to Exhibit 11 for overhead and Exhibit 12 for underground central distribution
service installations.
6.0 PERMANENT SERVICE UNDERGROUND
6.1 General
The customer, architect, or contractor shall contact the Company, prior to the start of construction
to ascertain from the Company the point of attachment for the Company-owned service lateral.
The Company will designate a location, as close as practical, for the point of service.
Based on an engineering evaluation, a Company representative will determine the pole,
transformer, handhole, pedestal, or manhole location to which an underground service lateral may
be extended. Refer to Exhibit 1 for specific customer and Company installation/ownership
responsibilities for each item associated with the service and for determination of the point of
service. The Company retains ownership of conductors and equipment it supplies. In special
situations, if the point of service varies from Exhibit 1, the customer’s installation documents will
clearly designate the equipment ownership and the exact point of service.
The contractor, developer, or customer shall provide all trenching, conduit, and backfilling as well
as a clear, graded path for installation. The customer shall be responsible for installing the service-
lateral conduit. The Company shall install and maintain the service lateral conductors to the
service point. The Company shall own and maintain all service lateral facilities, including the
service-lateral conduit installed by the customer.
Before excavating, refer to Sections 3.13 and 3.14 for locating and marking underground facilities.
Refer to Exhibit 24 for general trench details for direct buried cables and conduit installations.
Since the actual trench dimensions may vary by changes to final grade, soil condition, location,
and other factors, it is necessary to confirm specific trench dimensions with the Company
representative.
The customer shall provide a trench that is well tamped. Settlement and frost heave of trench
backfill can result in damage to service cable, meter sockets, and house siding. The customer
should install ground movement protection per NEC 300.5 (J). The Company recommends a slip-
joint conduit product, available from several vendors and suppliers.
The commercial customer installed underground service conductors to a pad-mounted
transformer shall be of sufficient length to allow the Company to complete the final electrical
connections.
The customer shall be responsible for connecting all service entrance conductors to any form of
customer-owned disconnecting devices or equipment. The Company will be responsible for
providing all connectors and making all connections to its power transformers, metering cabinets,
manholes, handholes, and pedestals regardless of whether involved conductors are Company or
customer owned.
September 2015
16
Refer to Section 3.8 and Exhibit 5 for grounding requirements.
Additionally for customer installed and owned underground service conductors, if a customer
increases load, the customer is responsible to verify that ampacity, voltage drop, and voltage
flicker limitations are suitable to serve the load. If load is being added, the customer shall advise
the Company so that the Company can ensure all Company associated facilities are adequate to
serve the increased load.
There should be no fence, guardrail, wall, or other obstruction placed near pad-mounted
equipment (e.g., transformers, handholes, pedestals, switchgear) that would limit the Company
from performing maintenance or repair on the equipment. This includes any tree, shrub, bush, or
other vegetation that would have to be removed in order to operate, maintain, or replace
equipment. The minimum clearance is three (3) feet from the back and sides, and ten (10) feet
from the front of all pad-mounted equipment or any pad-mounted switchgear doors. Refer to
Exhibits 22 and 23. Additionally, a customer shall not cover (even partially) any of these devices
with plants, mulch, dirt, rocks, artificial rocks, or other landscaping as this prevents them from
being quickly located, safely operated, as well as accelerating their corrosion. Company shall not
be responsible for replacing shrubs, plants, fences, wall screenings, or other obstructions that
need to be removed for maintenance or restoration work.
6.2 Underground Services from Overhead Lines
The Company supplies and installs all underground service laterals from the Company’s overhead
lines. The customer is responsible for the trenching, backfilling, and conduit.
6.3 Underground Services in Underground Residential Areas
For single-phase underground services at 400 amps or less, the Company shall install only one
set of service cables sized for the expected load. Multiple or parallel sets of cables are not
provided for services at 400 amps or less. Refer to Exhibit 1 and Exhibit 8.
For services greater than 400 amps, the customer shall consult the Company as soon as possible
during the building design stage to discuss the multiple or parallel cable service requirements.
Due to connector physical limitations, cable size shall be limited to 750 kcmil when terminating in
a handhole, pedestal, or in a single-phase pad-mounted transformer.
6.4 Underground Services in Underground Commercial Areas
It is imperative that the customer contact the Company as soon as practical in the customer’s
electrical design/planning stage to ensure that appropriate accommodations can be made for the
required Company facilities. The customer shall provide the Company with suitable space at a
location designated by the Company to accommodate the necessary transformation and switching
equipment required to supply the customer’s load. Space requirements may vary depending on
the customer’s load and service requirements, as well as the availability of Company facilities in
the area.
The Company shall provide, install, and maintain the necessary primary cable, transformer(s), and
switchgear to provide electric service as well as a pad-mounted enclosure, handhole, pedestal, or
other suitable means to terminate the service lateral cable.
Due to connector physical limitations, cable size shall be limited to 750 kcmil when terminating in
a single-phase pad-mounted transformer and limited to 1000 kcmil when terminating in a three-
phase pad-mounted transformer. For underground services at 400 amps or less, the Company
shall own and install only one set of service cables sized for the expected load. Multiple or parallel
sets of cables shall not be acceptable for services at 400 amps or less, unless prior written
agreement is made with the Company.
17 September 2015
When no outdoor location is available, other options may be considered. Those options will
require written approval from the Manager of Regional Engineering Services. This needs to be
completed early in the building design/planning stage. Additional special needs and design
specifications (Company, OSHA, NESC, NFPA, NEC, etc.) will be discussed so that the
appropriate safety, maintenance, and operating conditions can be satisfied. The Company’s
equipment shall be accessible at all times.
For services greater than 400 amps, the customer shall consult the Company as soon as possible
during the building design stage to discuss the multiple or parallel cable service requirements.
Where a service raceway or duct enters from an underground distribution system, the customer
shall seal the end within the building with suitable compound to prevent the entrance of moisture
(water) or gases. Spare or unused ducts shall also be sealed.
Refer to Exhibits 15, 16, 18, 19, 20, and 21 for typical installations.
6.5 Underground Services in Central Business District Network Areas
This is not applicable in Mon Power or Potomac Edison - West Virginia.
6.6 Transformer Foundations & Vaults
The customer shall provide a suitable above ground external site to accommodate a pad-mounted
transformer. The site shall have compact, level ground, and not subject to flooding or pooling
water. The area selected should avoid high contamination areas and areas subject to vehicle
damage (e.g., delivery trucks, garbage trucks, snowplows, large farm equipment, etc.). The
provided area shall be of sufficient size to accommodate the installation, removal, maintenance,
and upgrades in a safe manner.
For single-phase installations, the customer shall provide the excavation, and provide and install
the base material (per Exhibit 29). The Company shall provide and the customer shall install all
single-phase box pad foundations.
For three-phase installations, the customer shall provide the excavation and shall provide and
install the base material, grounds, and a concrete transformer pad in accordance with Exhibits 26,
27, and 28.
If such a site is not available, alternate options will be evaluated and approved by the Manager of
Regional Engineering Services. If a transformer vault is the only option available, the vault shall
be furnished and maintained by the customer on the customer’s premises at the customer’s
expense, in accordance with national, local, and Company requirements.
Transformer vaults may contain only the supply transformers and associated primary equipment
and, where necessary, customer-owned secondary bus. Under no conditions are service-meters,
customer-owned fuses, switches, or other customer-owned equipment to be installed therein.
Secondary devices and service meters, however, should be installed as near the transformer vault
as practicable, but not in it.
For certain high usage customers, current and voltage instrument transformers constitute a part
of the Company's metering equipment. For distribution secondary voltages, they are usually
installed in instrument transformer enclosures. For vaults in buildings, these enclosures are
located outside the transformer vault, preferably on the vault wall, unless some other more
desirable location is approved by the Company. Refer to Exhibit 19 and 20 for a typical metering
installation with current transformers.
6.7 Mobile Homes or Mobile Home Parks
Refer to Exhibits 13 and 14 for typical installations.
September 2015
18
7.0 METER INSTALLATIONS
7.1 General
Meters and meter testing devices are furnished, installed, and maintained by the Company. These
devices are Company-owned and shall not be moved or the connections changed by any person
other than authorized employees of the Company (refer to Section 3.10).
All metering shall be installed on the line-side of the customer's main disconnecting means except
for the following:
A 480Y/277-volt self-contained metering installation,
Where the Company requires a non-fusible meter disconnect ahead of the meter (refer to
Exhibit 15),
Where the NEC requires a main disconnect ahead of a group of more than six (6) meters
(refer to Exhibit 16).
The customer shall consult the Company prior to purchasing or installing equipment.
Meter sockets, metering transformer cabinets, and all other enclosures and switch boxes installed
on the line side of the meter shall be equipped with provisions to accept a Company meter seal
before connection will be made by the Company. Meter sockets, transformer cabinets, and other
meter service enclosures shall not be used by the customer as junction boxes - only service
entrance conductors are permitted. Metered and unmetered conductors shall not be installed in
the same conduit, enclosure, or raceway. All energized meter sockets shall be properly covered
at all times especially if the meter has been removed. Meter sockets and service conduits shall
not be recessed into the wall. Unmetered service entrance cables or service entrance conduits
on buildings, poles, or structures shall not be concealed or recessed.
All self-contained, single-position meter sockets will be furnished by the Company and installed
by the customer. In the event of a failure of a Company-owned standard meter socket, the
Company will repair the socket or provide a replacement for the failed socket. The customer is
responsible for the installation of the replacement socket. If the customer’s service entrance
conductors require replacement, the Company will furnish a replacement socket to the customer
for installation by the Customer’s electrical contractor.
Meter installations that have the meter socket as part of a pedestal, multi-metered equipment, or
attached to an integral part of customer-owned service equipment shall be approved by the
Company prior to purchase and installation by the customer.
The Company, in accordance with the rate schedule selected and the type of service supplied,
determines the capacity and type of meter installation to accommodate the customer's load.
7.2 Meter Locations
The customer shall provide space for the installation of the Company's meters and equipment at
an outside location designated by the Company. Outdoor meter locations are required for all
meters except where the Company gives approval otherwise.
Outdoor
All new outdoor meter installations shall be located on the building at the nearest practical point
from Company facilities and readily accessible to authorized Company representatives. If the
nearest point is not feasible due to physical obstructions, such as garage doors or windows, the
Company shall choose an alternate location closest to its service facilities.
The meter socket shall be installed so that the center of the socket is approximately five feet above
the finished grade. Exceptions to this requirement to avoid obstacles or maintain safety shall be
19 September 2015
approved prior to installation. Meter socket height for pedestals, multi-meter equipment, or meter
sockets attached to or an integral part of customer-owned service equipment shall be approved
by the Company.
Clearance in front of and to the sides of meter sockets and metering equipment shall be
maintained per NEC Article 110.26 (30-inch width and 36 inches in front of the meter and extend
from the grade, floor, or platform to a height of 6.5 feet or the height of the equipment, whichever
is greater). The above clearances shall be maintained regardless of structural changes of the
building. The location should not be subject to severe vibration. Meters and metering equipment
shall not be installed in dangerous locations or locations where the meter readers or service
personnel may inadvertently damage flowerbeds or shrubbery or where it will be necessary for
them to climb over fences or other obstructions to perform their work. The meter socket shall not
be installed in carports, open porches, or other such areas that may be enclosed by walls or
screens. Additionally, they shall not be installed in locations where they may be accidentally
damaged, such as on buildings where they will extend unguarded into alleys, driveways, drive-
thrus, or where they will cause inconvenience to the customer or the Company.
A meter may be located on a customer-owned pole with prior Company approval. This pole shall
be yellow pine, cedar, or equivalent, pressure-treated and provide proper clearances (refer to
Exhibit 2). Before installing the pole, the customer should consult the Company for proper size
(length and class) and setting depth. Any metering installation on a Company-owned pole shall
have the specific written approval of the Company.
The customer shall install steel concrete filled barrier posts to protect metering equipment where
vehicle traffic may interfere with or damage such equipment. Refer to Exhibit 30.
Meters shall not be located closer than three (3) feet to any natural gas equipment. For locations
near tanks containing flammable gas or liquid (e.g., propane, gas or oxygen) meters shall be no
closer than fifteen (15) feet.
Indoor
Indoor installations shall be preapproved by the regional Metering Services Section.
Where an indoor installation is required, the meters should be located on the first floor or in the
basement where they shall be readily accessible to authorized Company representatives. The
location should not be subject to severe vibration, excessive dampness, high magnetic fields, or
excessive heat and shall be installed in accordance to the NEC.
7.3 Group Meter Installations
In multiple occupancy (two or more occupancies) buildings, where several floors, apartments,
stores, etc., are rented separately, meters and service equipment shall be located preferably all
together. In high-rise buildings, it may be necessary to have several meter locations, possibly
every other floor or every third floor as may be necessary.
The meter room or space shall be readily accessible to all tenants and Company representatives
at reasonable hours. This room shall be for the sole purpose intended and shall meet local fire
codes as well as the NEC. This room shall not be used for the storage of materials or equipment.
Refer to Exhibit 16 for typical indoor/outdoor installation for multiple occupants.
7.4 Meter Relocations
When alterations or additions to a building or its wiring require a change in the meter location, the
customer shall notify the Company before proceeding with any work. The customer may be
responsible for the Company’s cost for facility modifications. The customer shall be responsible
for all costs incurred in the moving the meter socket and wiring.
September 2015
20
7.5 Minimum Meter Sockets Requirements
Meter sockets (single-position) for a service of 400 amps or less are supplied by the Company
and installed by the customer. For other service sizes, refer to Exhibit 1 for customer/Company
responsibilities. All meter sockets shall meet the minimum requirements as defined below. For
services greater than
400 amps, the customer should consult the Company for the appropriate
metering equipment.
Minimum Requirements For All Meter Sockets
Shall be UL listed and labeled
Meter socket jaws shall be tin plated copper and spring supported
Lugs shall be extruded aluminum tin plated
Sockets shall be 5
th
terminal adaptable (at the 9 o’clock position)
Sockets shall be ringless type with clasp and slot closure
Sockets shall have ¼-inch ground wire knockout
Cardboard or plastic protector
Triple ground lug (triplex)
Shall accept blanking plate
Meter sockets designed for underground service connections shall be side-wired
Dual use meter sockets designed for both overhead and underground service connections shall be
side-wired
Residential Single-Phase Commercial Single- & Three-Phase
Shall have bypass horns Shall have lever-operated jaw release and by-pass rated for
100% continuous duty (does not apply to single-phase
temporary services).
All sockets shall have the Landis & Gyr HQ Series, the Milbank
HD Series, or the Eaton/Cutler Hammer MSL Series Block
Assembly.
Additional Requirements for Specific Socket Types
Single-Phase Single-Position Overhead 100 Amperes & 200 Amperes:
Small hub opening (minimum)
Lug size - #6 AWG to 2/0 AWG (for 100 A) or #2 AWG to 350 kcmil (for 200 A)
Bottom knockout -inch conduit minimum
Hub not included
Single-Phase Single-Position Overhead 400 Amperes:
Large hub opening
3/8-inch stud lug size - #4 AWG to 600 kcmil
Bottom knockout – 3-inch conduit minimum
Large hub opening
Bypass lever with jaw release
Single-Phase Multiple-Position OH/UG 125 Amperes:
Small hub opening (minimum)
Lug size - #6 AWG to 2/0 AWG (load) and #2 AWG to 350 kcmil (line)
Bottom knockout – 3-inch conduit (for incoming utility cable)
Hub not included
Single-Phase Multiple-Position OH/UG 200 Amperes:
Large hub opening
Lug size - #2 AWG to 350 kcmil (load) and #6 AWG to 400 kcmil (line)
Minimum 2-inch conduit per position bottom knockout, additional bottom knockout 3-inch conduit (for
incoming utility cable)
Hub not included
21 September 2015
Single-Phase Multiple-Position OH/UG 125 Amperes with disconnect switch:
Small hub opening (minimum)
Lug size - #6 to 2/0 AWG (load) and #4 AWG to 350 kcmil (line)
Bottom knockout – 3-inch conduit (for incoming utility cable)
Hub not included
Disconnect switch
Side-wired
Single-Phase Multiple-Position OH/UG 200 Amperes with disconnect switch:
Large hub opening
Lug size - #2 AWG to 350 kcmil (load) and 1/0 AWG to 600 kcmil (line)
Bottom knockout – 3-inch conduit (for incoming utility cable)
Hub not included
Disconnect switch
Single-Phase Single-Position UG 200 Amperes:
Lug size - #2 AWG to 350 kcmil
Bottom knockouts two 3-inch conduits
Side-wired
Single-Phase Single-Position UG 400 Amperes:
3/8-inch stud with lug size - #4 AWG to 600 kcmil
Bottom knockouts two 4-inch conduits
Bypass lever with jaw release
Side-wired
Single-Phase Single- and Double-Position UG Pedestal 200 Amperes:
Lug size - #2 AWG to 350 kcmil
Stabilizing foot or base
A hasp for a padlock may be provided in place of barrel lock
Grounding provisions (if the pedestal is metal, it shall be grounded to meter socket ground or have
another method of grounding it)
36 inch minimum below grade (including stabilizing foot or base)
Series main breaker
Poly-Phase Single-Position Self-Contained OH 125 Amperes & 200 Amperes:
Small hub opening (minimum)
Lug size - #6 to 2/0 AWG (for 125 A) or #6 AWG to 350 kcmil (for 200 A)
Bottom knockout (min) – 2-inch conduit (125 A) or 3-inch conduit (200 A)
Seven-terminal three-phase four-wire
Poly-Phase Single-Position Self-Contained OH/UG 400 Amperes:
Large hub opening
3/8-inch stud with lug size - #6 AWG to 600 kcmil
Bottom knockout – 4-inch conduit
Seven-terminal three-phase four-wire or five-terminal three-phase three-wire
Side-wired
Poly-Phase Single-Position Self-Contained UG 200 Amperes:
Lug size - # 6 AWG 350 kcmil
Bottom knockout (min) – 3-inch conduit
Seven-terminal three-phase four-wire
Side-wired
September 2015
22
Gangable Sockets:
Maximum height to center of top socket 72 inches
Minimum height to center of bottom socket 24 inches (indoor) or 30 inches (outdoor)
Minimum spacing between meters eight (8) inches
Five jaw standard for three-phase in, single-phase out (for 120/208 V three-wire applications)
400-A units approved on a case-by-case basis
Residential units no bypass lever; Commercial units bypass lever required
A hasp for a padlock may be provided in place of barrel lock
480-V units shall have disconnecting means on source side of each socket with provisions for meter seal
and/or padlock
7.6 Metering Equipment Installation Guideline Summary
The Company shall approve all metering equipment locations.
The meter socket shall be mounted level.
Mount the meter socket on a solid part of the structure.
Use corrosion inhibited mounting hardware.
Do not mount the meter socket with nails.
Meter socket shall be surface mounted. Do not build-in or enclose the meter
socket or meter within the structure.
Do not recess the meter socket in brick, masonry, or siding.
The installation shall meet the requirements set forth by the NEC and any local,
state, or federal codes that apply to the installation. For installations that require
electrical inspection, the inspection is required before the installation is connected
to the Company’s system.
It is recommended that a qualified electrical contractor perform all work on
customer facilities.
Customer’s meters, auxiliary devices, relays, etc., shall normally not be connected
to the Company’s metering circuits.
The Company shall furnish the metering facilities required in accordance with its
standard rate schedules.
After an installation is made, changes in location of meters for the convenience of
the customer will be at the customer’s expense, after the necessary service
entrance wiring to the new location has been completed by the customer.
Only service entrance conductors may run through meter sockets or meter
connection boxes.
Meter sockets/enclosures shall not be used as junction boxes.
All equipment furnished by the Company (excluding self-contained meter sockets)
shall remain its exclusive property and the Company shall have the right to remove
the same after termination of service for any reason whatsoever.
For identification purposes, it is necessary that wherever two or more meters are
grouped at one location, all sockets/metering equipment (inside and out) and
breakers shall be plainly and permanently marked to designate the particular
apartments, suites or offices served (e.g., Apt 1A). Likewise, the apartment or
suite entrance(s) shall be identified accordingly (e.g., APT 1A). Tags shall be
used marking entrance equipment or service or service conductors, whereas
sockets or meter connection boxes may be marked by neat stencils with paint
as well as by the use of permanent tags (label maker tags are not acceptable).
These identification markings shall be located as follows:
Inside main disconnect electrical panel in the apartment or suite,
Inside the meter socket near the jaw assembly, or
23 September 2015
On the cover of both main disconnect panel and meter socket.
For multi-meter installations, any unmetered positions shall have the cardboard
shipping covers replaced by plastic protectors.
Metered and unmetered conductors shall not be in the same trough, conduit, or
wireway.
For typical installations, refer to Exhibits 6, 8, 11, 12, 13, 14, 15, 16, 17, 18, 19,
20, and 21. In unusual cases, the customer should contact the Company.
7.7 Minimum Size Meter Socket - 480-Volt Services
The smallest permissible size meter socket on 480Y/277-volt three-phase four-wire services is
200 amps.
7.8 Installations Requiring 400 Amperes & Less of Continuous Metering Load
Typically on new installations or on existing installations where the service entrance conductors,
service entrance panel, or main disconnect switch are rearranged, the meters shall be installed
outdoors. If an indoor installation is required, the customer shall consult the Company before
starting the installation.
7.9 Installations Requiring Over 400 Amperes of Continuous Metering Load
The regional Metering Services Section shall determine in each case (either new or to be rebuilt)
the type of meter installation to be made.
Instrument transformers are required for these installations. In most situations, the Company shall
supply and the customer shall install a current transformer cabinet or mounting facility in
accordance with Company requirements. Refer to Exhibits 19 and 20. These instrument
transformer cabinets shall not be used as junction boxes or raceways (troughs). Other alternative
current transformer locations (e.g., in pad-mounted transformer), as determined by the regional
Metering Services Section, may be applicable as per Exhibit 21. All instrument transformer
locations shall be readily accessible to authorized Company representatives for checking and
testing. However, before such an installation is made, the Company shall be consulted regarding
the meter location and facilities required.
When a phone connection to the meter is required by the Company or requested by the customer,
the customer shall provide a telephone line and conduit to the meter socket. Monthly charges for
the phone connection are the customer’s responsibility. Customer shall contact the regional
Metering Services Section for details.
When the space above the instrument transformer cabinet is intended as the location for the meter
or meters, it is necessary that adequate space be reserved for this purpose.
Where the instrument transformer and/or service conductors are of such size that it is not practical
to use instrument transformer cabinets, the current transformers may be mounted, at the
customer's expense, in a bus structure. The current transformer compartment shall have a hinged
lockable door. However, before such an installation is made, the Company shall be consulted
regarding the meter location and facilities required.
For services exceeding 2400 amperes, the customer shall provide a switchgear enclosure for
metering. Switchgear compartments meeting IEEE C57.12.28 shall be a minimum of 36-inches
high by 30-inches wide by 20-inches deep with a bus separation of at least 10.5 inches on center,
7.5-inch minimum separation from the enclosure sides, and located on the supply-side of any
protective equipment. The bus dimension shall be a maximum of five (5) inches to allow for
window type current transformers. The customer shall contact the regional Metering Services
Section to determine specific details and if the proposed installation allows for an alternative
metering arrangement.
September 2015
24
7.10 Approved Current Transformer Cabinets
When a current transformer cabinet is required, the Company shall provide an approved unit from
the table shown below. These cabinets shall not be used as junction boxes for circuit extensions
and shall have line and load sides identified.
All current transformer cabinets listed below are rated for indoor/outdoor use unless otherwise
noted.
The short-circuit current ratings that will be labeled on the current transformer cabinets are
included next to the catalog numbers listed below. This information is being provided so that the
customer can select a unit with a short-circuit current rating equal to or greater than the available
short-circuit current at the cabinet as may be required by the local or state inspection authority.
Current-Transformer Cabinets (400 Amperes to 2400 Amperes):
Shall be UL listed and labeled as a “Metering Transformer Cabinet,
Use 14 gauge electroplated galvanized or equivalent gray painted steel
(or aluminum with equivalent physical strength and corrosion resistance),
Outdoor type shall be weatherproofed,
Double door with stainless steel hinges (or equivalent hinges for
aluminum cabinet),
Padlockable handle (for Company lock) on door with internal mechanism
for three points of latching: top of door, bottom of door, and handle,
Each door shall be equipped with a non-detachable door stop for holding
it in a fixed open position,
Typical dimensions for cabinets rated 400 A to 800 A: 36-inch wide, 36-
inch high, and 10-inch deep
Typical dimensions for cabinets rated 1000 A to 2400 A: 42-inch wide,
60-inch high, and 20-inch deep,
Removable copper bus bar on each phase for installation of window-type
current transformers (Company will provide current transformer
dimensions upon request),
Each bus bar shall be drilled and tapped on both ends with a 10-32 screw
to facilitate connection of meter potential wires, and
Bus support brackets on each phase shall be spaced to accommodate
installation of standard bar-type current transformers.
25 September 2015
Approved Manufacturer/Catalog Numbers
Manufacturer
CT Cabinet Catalog Number
Short-Circuit Current Rating
Size: 600 - 800 Amperes
East Coast Panelboard
CTJ-800-A (indoor)
50,000 amps *
CTJ-800R-A (outdoor)
Erickson Electrical
CT-84-FECD
100,000 amps
Hoffman Enclosures A800HCT1R 50,000 amps
Lake Shore Electric JCTC-Series 50,000 amps
Brooks Meter Devices
507U7591-1
10,000 amps
Milbank U5990-O 50,000 amps
Nav-Tech
CT-800 (indoor)
CT-800R (outdoor)
50,000 amps
*
The Durham Company
1011245
50,000 amps
*
Size: 1000 Amperes
East Coast Panelboard
CTJ-1000-A (indoor)
50,000 amps*
CTJ-1000R-A (outdoor)
Erickson Electrical
CT-124-FECD
100,000 amps
Lake Shore Electric MCTC-Series 50,000 amps
Size: 1200 Amperes
East Coast Panelboard
CTJ-1200-A (indoor)
50,000 amps*
CTJ-1200R-A (outdoor)
Erickson Electrical
CT-124-FECD
100,000 amps
Lake Shore Electric
MCTC-Series
50,000 amps
Size: 1600 Amperes
East Coast Panelboard
CTJ-1600-A (indoor)
50,000 amps*
CTJ-1600R-A (outdoor)
Erickson Electrical CT-164-FECD 100,000 amps
Lake Shore Electric
SCTC-Series
100,000 amps
Size: 2000 Amperes
East Coast Panelboard
CTJ-2000-A (indoor)
50,000 amps*
CTJ-2000R-A (outdoor)
Erickson Electrical CT-204-FECD 100,000 amps
Lake Shore Electric
SCTC-Series
100,000 amps
Size: 2400 Amperes
East Coast Panelboard
CTJ-2500-A (indoor)
50,000 amps*
CTJ-2500R-A (outdoor)
Erickson Electrical
CT254-FECD
100,000 amps
Lake Shore Electric SCTC-Series 100,000 amps
* To achieve rating, customer must wrap line cables together and load cables together with nylon rope per
manufacturer’s instruction.
September 2015
26
7.11 Service at Voltages Greater Than 600 Volts
Service at primary distribution, subtransmission, or transmission voltage level may be available
dependent upon the size of the load served, location of the facility, and other economic factors.
The customer should contact the local Engineering Services Section for additional information.
The customer shall contact the Company well in advance of the time such service will be required
so that the customer's and the Company's engineering, design, and construction work may be
properly coordinated and equipment made available.
7.12 Disconnect Requirements
Multiple Meter Installations
Disconnect requirements on installations with multiple meters vary dependent upon the nature of
the installation and level of load served. For disconnect (main and/or individual meter)
requirements, the customer shall contact the regional Metering Services Section.
480-Volt Self-Contained Meter Installations
For all single-phase and three-phase 480-volt services with self-contained metering, a non-fused
disconnecting means is required on the source side of the meter socket. The disconnecting means
shall be installed, owned, and maintained by the customer. The disconnecting means shall have
provisions for a Company meter seal and/or padlock. Refer to Exhibit 15 for details.
For 480-volt multiple metering units (i.e., gang sockets), a disconnecting means is required on the
source side of each socket as specified above for single meter installations. This requirement
also applies to 480-volt multiple metering units having a main disconnect. Refer to Exhibit 16 for
details.
The customer shall contact the Company’s Metering Services Section during the electrical design
stage to discuss the 480-volt meter disconnect requirements and to obtain approval for the
proposed installation.
8.0 CUSTOMER EQUIPMENT
8.1 Motors (Inrush Limitations & Motor Protection)
Single-Phase Motors
1. All single-phase motors with ratings of one hp and larger should be connected for supply at
240 volts whenever it is practical, in order to minimize voltage fluctuation in the wiring system.
Where service is supplied from a 208Y/120-volt system, these motors should be purchased
for operation at 208 volts.
2. Motor installations for air conditioning equipment, farm applications, and heat pumps in ratings
of one to seven and one-half (7-1/2) hp should be of the capacitor start-capacitor run design.
The Company shall be notified of each installation of five hp or more. In addition, the customer
shall notify the Company before installing central air conditioning or heat pumps.
3. Overload protection must be provided for all motor circuits in accordance with National
Electrical Code requirements.
4. The use of automatic time-delay circuit breakers for circuit protection is strongly recommended
and where fuses are used, they should always be of the time-delay type. In many instances,
this time-delay will prevent unnecessary shutdowns due to the tripping of an instantaneous
type circuit breaker or blowing of ordinary short-time fuses by large currents resulting from
motor starting, temporary overloads, or temporary low-voltage conditions.
27 September 2015
Three-Phase Motors
1. Before any three-phase motors are installed, the Company shall be consulted to determine
the character and adequacy of the available service.
2. The customer shall provide nameplate information for all motors 10 hp or greater to the
Company. The Company will provide the maximum permissible inrush for the location and for
the conditions of that particular installation.
3. The use of reverse phase relays, phase failure relays, and low voltage relays, preferably of
the adjustable time-delay type, with circuit breakers or equivalent devices, is highly
recommended. These devices are desirable to disconnect motors automatically that cannot
be safely reversed or would be damaged by a phase or voltage failure. Such devices shall be
furnished, installed, and maintained by the customer at the customer’s expense (refer to
Section 8.8).
Starting Currents General
1. Motor starts can produce voltage fluctuations resulting in objectionable flicker on lighting
supplied by the same or nearby circuits.
2. Starting of large three-phase motors and operation of furnaces and welders requires special
consideration of the power supply and wiring. The Company may assist the customer in
planning these installations; and in every case, the Company must be notified so that
adequacy of the service facilities may be determined and changes may be made if necessary.
Starting Currents - Frequently Started Motors
Frequently started (i.e., more than four starts per hour) single-phase motors for general use, such
as for refrigerators, oil burners, water pumps, and similar devices, should have a locked rotor
current not exceeding 20 amperes for operation at 120 volts and 25 amperes for operation at 240
volts. These motors are permissible on the system.
Starting Currents - Intermittent Started Motors
1. Single-phase motors for installations such as heat pumps, central air conditioners, grain
dryers, etc., with locked rotor currents not exceeding 175 amperes served at nominal 120/240
volts or network 120/208Y volts, may be connected to the single-phase service furnished
through one meter.
2. Motors that have starting currents exceeding the limits stated in "Starting Currents - Frequently
Started Motors" and in item (1.) of Intermittent Started Motors above should not be installed
without the consent of the Company.
3. The maximum permissible motor starting currents, as indicated in item (5.) below, shall apply
to the application of manually or infrequently started motors. These values are based on not
more than four starts per hour with long periods of continuous operation under maximum load
conditions.
4. Where equipment ratings or inrush characteristics other than those covered in this section are
being considered, the Company shall be consulted. The starting currents permitted will
depend upon the frequency of start of the motor, the size, and character of the customer's
load, and the capacity of the Company's system in the area. The maximum allowable starting
current will be that value which in the Company's opinion can be supplied without causing
undue interference with service to other customers.
5. Maximum Permissible Motor Starting Currents
September 2015
28
a. Equipment with motors rated in horsepower:
Equipment Rated at: Total Locked Rotor Current not to Exceed:
120 volts, single-phase 50 amps
208 or 240 volts, single-phase
2 hp or less 60 amps
2 hp to 6.5 hp 60 amps plus 20 amps/hp over 2 hp
Over 6.5 hp Consult the Company
208 or 240 volts, three-phase
2 hp or less 50 amps
2 hp to 19.9 hp 50 amps plus 14 amps/ hp over 2 hp
Over 19.9 hp Consult the Company
b. Room and unitary air conditioning or heat pump equipment rated in Btu per hour (Btu/h).
Note: 12,000 Btu/h equals one ton.
Equipment Rated at: Total Locked Rotor Current not to Exceed:
120 volts, single-phase 50 amps
208 or 240 volts, single-phase
20,000 Btu/h or less 60 amps
20,000 Btu/h to 43,333 Btu/h 60 amps plus 3 amps/1000 Btu/h in excess of
20,000 Btu/h
Over 43,333 Btu/h Consult the Company
208 or 240 volts, three-phase
20,000 Btu/h or less 50 amps
20,000 Btu/h to 50,000 Btu/h 50 amps plus 2.5 amps/1000 Btu/h in excess of
20,000 Btu/h
Over 50,000 Btu/h Consult the Company
6. Definitions & Notes for Motor Starting Requirements
a. Total locked rotor current is defined as the steady state current taken from the supply line
with the motor rotor or rotors locked, with all other power-consuming components
including a current-reducing starter if used connected in the starting position, and with
rated voltage and frequency applied.
b. Where the equipment contains more than one motor and some motors are arranged for
sequence starting, locked rotor current applies to that combination of power-consuming
components simultaneously started that produces a higher draw of starting current than
any other combination. In such sequence arrangements, the subsequent motor(s) shall
not be started for a minimum of 1/2 second after the preceding motor(s) have completed
their starting mode.
c. Where the design of the equipment is such that unequal currents appear in the supply
wires (i.e., auxiliary motors on single-phase equipment or single-phase auxiliary motors
on three-phase equipment), locked rotor current applies to the supply wire carrying the
largest current.
d. For three-phase motors and equipment rated at voltages other than 240 volts, the locked
rotor currents specified shall be multiplied by the inverse ratio of the voltages [For
example, for a 480-volt motor, the locked rotor current would be the value in the table in
item (5) above multiplied times the ratio 240/480 (0.5)].
29 September 2015
8.2 Power Factor
It is desirable to maintain the power factor of any load as near to unity as possible.
In general, the customer power factor shall be between 85 percent (lagging) and 99 percent
(leading) at the customer’s peak load. If power factor corrective equipment is necessary, it,
together with required switching equipment, shall be provided and maintained by the customer at
the customer’s expense.
In general, capacitors must be applied more carefully than most types of electrical equipment in
order that satisfactory operation and maintenance will result. The customer should consult with
the Company before any installations of this type of equipment are made.
8.3 Welders & Industrial Furnaces
The Company may assist its customers in planning installations of electric welders and industrial
type furnaces. To have ample time to determine the electrical supply requirements, the customer
shall consult the Company when such installations are being planned and before the customer
commits to the purchase of the equipment.
8.4 Commercial Cooking, Space Heating, Water Heating, & Ice / Snow Melting
In some instances, installations of commercial cooking, space heating, water heating (including
tank-less), ice and snow melting, and similar equipment require additional service capacities for
satisfactory operation. Before any such installations are made, consultation with the Company is
advisable. The customer shall contact the Company before installing water heating (including
tank-less) in excess of a total of 5,500 watts.
8.5 Low-Voltage Surge Arresters (600 Volts or Less)
When low-voltage surge arresters are installed by the customer, they shall not be connected to
the service drop conductors, to the service entrance conductors, or installed in the meter socket.
Where installed to protect utilization equipment, low-voltage surge arresters may be either inside
or outside the enclosure containing the equipment to be protected or installed at the service
equipment. These arresters should never be considered as taking the place of the bond between
the neutral or grounded conductor and the metallic systems at ground potential such as: metallic
siding, water, waste lines, central heating, television towers and antennas, and sometimes
lightning rods, but only as devices which may help to reduce appliance failures.
8.6 UPS, Cogeneration, Back-up Generation, & Interconnected Generation
It is necessary to consult with the Company before considering or commencing design of such a
system, due to the potential safety hazard involved. In addition, if generation can run in parallel
with the Company supply system; obtain additional information on interconnection requirements
from the Company's local Engineering Services Section. It is specifically prohibited to operate
generation in parallel with Company facilities unless the Company has approved the
interconnection design.
When installing emergency generators, customers shall employ a switch that will prevent electrical
backfeed onto Company facilities when the generator is in operation.
Retail Interconnection applies to current retail customers who add generation to their side of the
utility meter and interconnect to the electric grid to reduce the energy delivered by their electric
utility. Retail interconnections are governed by the retail service tariffs, which are filed with and
approved by the PSC of WV. Additional information on interconnected generation can be found
at www.firstenergycorp.com
. Choose Mon Power or Potomac Edison from the drop-down menu
at the top of the page, and then click on “Generator Interconnection Process” under “General
Information.”
September 2015
30
8.7 Harmonic Producing Equipment
Customers shall meet the requirements of IEEE Standard 519 Section 10, Recommended
Practices for Individual Customers. Typical examples of harmonic producing equipment are
rectifiers, Silicon-Controlled Rectifier (SCR) drives, power supplies, inverters, arc-furnaces,
welders, etc.
8.8 Protective Devices
When requested, the Company shall provide necessary information regarding the required
interrupting capacity of protective devices to be installed at the customer’s point of service. Where
service is supplied from high short-circuit current systems, special power fuses, or breakers of
high interrupting capacity shall be used. While the Company will endeavor, where possible, to
anticipate system changes, which may affect these values, it does not assume responsibility or
liability with respect to such protective devices, nor guarantee their continuing adequacy against
increased interrupting capacity requirements resulting from system changes.
The service equipment installed, irrespective of type, should be of such capacity as to permit the
full utilization of the capacity of the service entrance conductors installed at the time of the original
installation. Circuit breaker type service equipment is preferable in all cases, and its use is strongly
recommended. However, fused type equipment is also acceptable.
Protection against loss of voltage, voltage unbalance, undervoltage transient, sustained
overvoltage, phase reversal, loss of synchronism, overcurrent, short circuit, and single phasing is
highly recommended for three-phase equipment and is the responsibility of the customer.
Reverse phase relays must be provided on three-phase motors for elevators, cranes, hoists, or
any other equipment requiring constant direction of rotation, where reversal of power would result
in damage to the equipment.
As indicated in Section 3.6, the Company shall not be responsible in any way for damage to the
customer’s equipment that is due to failure of the customer to provide adequate protection.
8.9 Special Equipment
It is also necessary that the installation of any special equipment not covered in this section be
referred to the Company for advice before any commitments for purchase or installation are made.
Such special equipment shall include X-ray, induction and dielectric heating equipment, sign
flashers, compressors or radio transmission rectifiers, and other similar devices.
1. Customer shall provide trenching, conduit (when required), and backfill to Company requirements.
2. Customer/contractor shall contact Company for location of Company and customer electrical facilities and
the approved trench route for connecting them.
3. The customer/contractor shall not deviate from the Company’s approved trench route unless expressly
approved by an authorized Company representative.
4. Before excavation begins, the excavator shall notify the appropriate state one-call agency (refer to Sections
3.13 and 3.14). The trench contractor shall be responsible for any damage caused by the excavator.
5. Applicant shall also coordinate the installation of all other buried utilities that are installing their facilities
nearby, will jointly occupy the trench, or cross the electrical supply trench.
6. Minimum clearances between electric supply lines (direct buried or in conduit) and the following utility lines:
Steam or cryogenic lines - six (6) feet (use of an approved thermal barrier may reduce this clearance),
Fuel lines (gas, oil, propane, or other) - four (4) feet,
Water, sewer, & telecommunication (i.e., telephone & CATV) lines - one (1) foot,
Clearances from telephone & CATV lines may be reduced to 0 ft or no deliberate separation (a.k.a.,
random lay) if all involved parties agree and NESC Rules are met,
Other utility companies (e.g., local water, sewer, and fuel) may require greater clearances than stated
above,
If required (e.g., trenching through solid rock) clearances may be reduced to one (1) foot minimum if all
involved parties agree,
Other facilities are prohibited from running above/below and parallel to the electrical cable without
specific Company’s approval.
7. The Company's minimum trench dimensions are based on providing adequate cover per NEC and NESC
codes (depth) and acceptable working areas (width). Minimum cover shall be maintained at all times. See
drawings for trench dimensions. Customer should contact the Company, if the trench must be more than four
(4) feet deep.
Owner (Code)
Customer-Installed Facilities (NEC)
(Inches)
Company (NESC)
(Inches)
Voltage
(Ø - Ø)
Direct
Buried
Cable
Rigid
Metallic
Conduit
(RMC)
Rigid
Nonmetallic
Conduit (RNC)
Street /
Road
Parking Lot
(Note 21)
Direct Buried Cable
0 – 600 V 24 6 18 24 24
> 600 V– 22 kV 30 6 18 24 30
> 22 kV – 40 kV 36 6 24 24 30
8. Customer shall clear the cable route of trees, tree stumps, boulders, or other obstructions. The excavato
r
shall grade the trench route to final grade level.
9. Customer/contractor shall not use power-excavating equipment within 18 inches of any existing buried cables
or other electrical or communications equipment.
10. Because of changing weather conditions and possibility of cave-ins, the excavator should not open the trench
any more than 24 hours before Company scheduled work. If a cave-in occurs, it is the customer/contracto
r
responsibility and expense to retrench before the Company can do its work.
11. Excavated material (“spoils”) should be placed on the field side of the trench (unless directed by the Company
otherwise), two (2) feet from the edge of excavations (per OSHA Standard 1926.651(j) (2)).
12. Standing water in the trench should be removed by pumping or draining (per OSHA Standard 1926.651(h)).
13. The bottom of the trench shall be relatively smooth, undisturbed earth, well-tamped earth, or sand, which is
free of rock, cinders, or sharp objects. For direct buried cables, a six (6) inch layer of select bedding (sand
or screening) may be required in certain soil conditions. Customer shall consult with the Company.
14. Conduit may be required in certain locations. Customer shall consult with the Company.
15. If conduit is used, secondary and service lateral conduits shall be sized per NEC. Use Schedule 40 PVC,
electrical grade conduit and a 30-inch minimum radius elbow at the terminal pole. Primary conduits are sized
for the installation of primary conductors. Customer shall contact the Company for the
p
roper primar
y
conduit diameter. Primary conduit shall be Schedule 40 PVC, electrical grade conduit. Use a 36-inch
minimum radius elbow at the terminal pole.
16. All joints shall be glued together. Conduit shall be cleaned and plugged at each end to keep water and dir
t
out. Customer shall install ¼-inch, unbroken nylon or polypropylene pull rope inside the conduit.
17. Before backfilling, the customer/contractor shall verify that the Company and local electrical inspector have
completed all required inspections of the trench (if required). In addition, the customer shall verify other
utilities that were approved to use joint trench have completed their work.
18. The customer/contractor shall backfill around all cables and conduits with six (6) inches of approved backfill.
Approved backfill shall be graded sand, stone dust, limestone dust, rock-free (1/4 inch or less diameter stones)
earth, or topsoil. Materials that "set up" such as fly ash, culm, and foundry waste are not acceptable. The
remainder of the trench shall be backfilled with native soil and not contain large rocks (greater than 4 inch)
or rocks with sharp edges. An additional six (6) inches of mounded backfill is recommended to allow fo
r
settling.
19. Backfill should be compacted in six-inch layers by hand or using with pneumatic or vibrating tamping
equipment to lessen the effects of settling. Note: “Machine compaction should not be used within six (6)
inches of the cable” (per NESC Rule 353A).
20. The customer/contractor shall bury warning tape above all customer-owned cables or conduits (
p
er NEC
300.Sd (3)). The warning tape shall be placed in the trench at least 12 inches above the cable or conduit.
N
otes:
1. Customer shall contact the Company prior to beginning work to discuss the details of transformer
foundation position and orientation, working clearances, barrier protection, construction
specifications, and inspection procedures. The Customer is responsible for installing, owning, and
maintaining the transformer foundation. The contractor shall provide a clear and firm approach to
the transformer foundation and keep the area above the transformer clear of obstructions that may
block the use of Company vehicles (e.g., crane access to the transformer).
2. Install all conduits before placing pad. Conduits should not be placed under sections of pad
supporting transformer so that original ground will not be disturbed.
3. Conduit shall be rigid Type II PVC, Schedule 40 PVC, or Schedule 80 PVC.
4. Backfill shall be clean granular soil, free of large stones and perishable material. All backfill shall
be spread and compacted in maximum layers of 8 inches.
5. Thoroughly compact base crushed stone or gravel.
6. Concrete pad may be poured-in-place or may be precast (4000 min. psi concrete).
7. To prevent water migration from concrete when pouring, place waterproof membrane on crushed
stone or gravel before pouring concrete.
8. Reinforcing wire mesh shall conform to ASTM designation A185.
9. Cement to be 1 or 1-A and meeting ASTM designations C-150 and C-175 respectively.
10. Poured pad concrete to develop minimum 4000 psi at 28 days age, contain minimum of 5.5 bags
of cement per cubic yard and maximum of 6 gallons of water per 94-pound bag of cement, and
conform to ASTM designation C-94. Fourteen (14) days minimum drying time before
transformer is set. For Exhibit 26, the volume of concrete is approximately 0.7 cubic yards. Fo
r
Exhibit 27, the volume of concrete is approximately 1.7 cubic yards.
11. Seal all openings around conduits with grout; cap all spare conduits to prevent entry of rodents
and animals into transformer compartment.
12. If conduit extends into building, it shall be sealed (per NEC) at building end to prevent gas fro
m
entering building through the conduit.
13. Where damage to transformer by vehicles is possible, transformer shall be protected b
y
appropriate barriers. See Exhibit 30. Customer shall contact Company for details.
14. Communication ground – The NESC requires
b
onding of all communications equipment
(telephone, CATV, etc.) that are within six (6) feet of the pad-mounted transformer. The wire fo
r
bonding communications equipment shall be minimum #6 AWG solid copper wire that is attached
directly to ground rod, runs underneath the concrete pad, extends 12 inches beyond the edge of the
pad, and finally runs alongside the pad foundation (see Exhibits 26 and 27 for details). The
required minimum length of wire for Exhibit 26 is 7-1/2 feet and for Exhibit 27 is 8-1/2 feet.
15. In areas where settling may occur, install three (3) concrete piers, 8-inch minimum diameter, 36
inches deep, in a triangular configuration under foundation. Customer shall contact the Compan
y
for details.
BUILDER INSTALL REQUEST
Please Type or Print
FORM 1046 (REV. 03-14) Check the Appropriate Boxes Below
OPERATING COMPANY
OHIO EDISON
PHONE 1-800-633-4766
FAX 1-877-289-3674
THE ILLUMINATING CO.
PHONE 1-800-589-3101
FAX 1-877-289-3674
TOLEDO EDISON
PHONE 1-800-447-3333
FAX 1-877-289-3674
PENN POWER
PHONE 1-800-720-3600
FAX 1-877-289-3674
POTOMAC EDISON
PHONE 1-800-686-0011
FAX 1-877-289-3674
MET-ED
PHONE 1-800-545-7741
FAX 1-877-289-3674
PENELEC
PHONE 1-800-545-7741
FAX 1-877-289-3674
JCP&L
PHONE 1-800-662-3115
FAX 1-877-289-3674
MON POWER
PHONE 1-800-686-0022
FAX 1-877-289-3674
WEST PENN POWER
PHONE 1-800-686-0021
FAX 1-877-289-3674
DETAILS OF SERVICE REQUIREMENTS
TEMPORARY ONLY (Fee Will Be Assessed) PERMANENT TEMP TO PERM (Fee May Be Assessed)
BUILDER INFORMATION
REQUESTED BY
BUILDING COMPANY NAME
COMPANY PHONE NO.
CONTACT PERSON
CONTACT PHONE NO.
FAX NO.
* If service application is in the “builder’s “name, the “buyer” must contact us when it is time to transfer service.
BILLING NAME AND MAILING INFORMATION
NAME OF PARTY RESPONSIBLE FOR THE ELECTRIC BILL
SOCIAL SECURITY NO./TAX ID
CONTACT PHONE NO.
E-MAIL ADDRESS
STREET ADDRESS (MAILING)
CITY
STATE
ZIP CODE
LOCATION WHERE SERVICE IS NEEDED
NAME OF DEVELOPMENT OR ALLOTMENT
LOT NO.
BUILDING NO.
FLOOR NO.
ROOM/APARTMENT/UNIT NO.
STREET ADDRESS
CITY
STATE
ZIP CODE
COUNTY/TOWNSHIP/BOROUGH/TAX DISTRICT
NEAREST CROSS STREET/POLE NO.
CONNECTION TYPE
UNDERGROUND
OVERHEAD
SQ. FT. OF STRUCTURE
SET BACK FROM ROAD (In Feet)
PREMISE TYPE
Is this application for a multi-tenant structure? YES NO If yes, how many units?
Please attach a separate page with the list of street addresses and lot numbers.
RESIDENTIAL
HOUSE MOBILE HOME APARTMENT DUPLEX TOWNHOUSE OTHER
NON-RESIDENTIAL
COMMERCIAL INDUSTRIAL CABLE COMPANY EQUIPMENT TYPE OF STRUCTURE/SITE USE
SERVICE ENTRANCE
AMPERAGE
100 200 OTHER
VOLTAGE
120/240 120/208 277/480 OTHER
PHASE
SINGLE PHASE THREE PHASE
DETAILS REGARDING STRUCTURE
HEAT SOURCE HEAT TYPE
HEATING SYSTEM
ELECTRIC
OIL
GAS
PROPANE
KEROSENE
UNKNOWN
GEOTHERMAL HEAT PUMP
BASEBOARD
HOT AIR/ELECTRIC FURNACE
HOT WATER/STEAM
ADD-ON HEAT PUMP
UNKNOWN
OTHER (DESCRIBE) OTHER (DESCRIBE)
HOT WATER SOURCE HOT WATER TYPE
WATER HEATER
ELECTRIC
OIL
GAS
PROPANE
STORAGE TANK
TANK LESS
OTHER
SIZE IN GALLONS
AIR CONDITIONER
YES NO TONS
COOLING TYPE
CENTRAL AIR HEAT PUMP WINDOW/WALL
WELL PUMP
YES NO UNKNOWN
OTHER HIGH USAGE APPLIANCES/EQUIPMENT:
NAME OF ELECTRICIAN: PHONE NO.:
STAGE OF CONSTRUCTION STAKED FOUNDATION FRAMED UNDER ROOF OTHER
DIRECTIONS/COMMENTS