14.2.0 Testing Component Circuits
The example used here is a
control operated by a remote
switch, such as a float switch.
Assume that the device being
controlled (a three-phrase motor)
is in good working order but is not
receiving power. Figure 10-64
shows such a circuit.
The first thing you should check is
the line voltage. To do this check,
remove the cover of the control
box and test each line with a
voltmeter. You should take the
volt readings between L1 and L2,
L2 and L3, and then between L3
and L1. If you find full voltage,
visually check the power circuit for
loose connections. These
terminals include L1, L2, L3, T1,
T2, and T3. Look for signs of
heating at these connections.
When a connection becomes
loose, the terminal becomes very
hot, and the screw, wire, and
terminal become discolored or charred. Check all terminals and tighten them if
necessary. ONLY do this checking and tightening with the power OFF.
Next, check the control circuitry within the controller. Do this check by looking at the
control circuit shown in Figure 10-64. The external controls, the magnetic holding coil,
and the normally closed overload contacts are always located between line 1 and line 2.
Unless the control has been altered, line 3 is not part of the control circuit. Check also
that the externally located controlling switches, such as the push button, float, pressure,
or limit switches, are connected between line 1 and the holding coil. The normally
closed overload contacts are always located between the holding coil and line 2. A
wiring diagram usually can be found in the cover of the controller. Now you have
established that the motor and line voltage are in working order. This checking has
narrowed the problem to the control circuit and the chance that some components are
open.
You can locate opens in the control circuit with a voltmeter. Connect one lead of the
voltmeter to line 1, and touch the other lead to first one terminal or the holding coil and
then the other terminal. The voltage reading should be the same as between line 1 and
line 2. If the control circuit voltage is supplied with a transformer, the voltage read
should be that of the transformer output. If there is no voltage on either side of the
holding coil, the overload contacts are open. Pushing the RESET button should close
the overload contacts. If they do not close after they have had time to cool, they may be
defective. In this case, replace them.
If there is a voltage on one terminal of the holding coil but not the other, the coil is open.
You must then replace the coil. If there is a voltage on both terminals of the holding coil,
assume the coil and the overload contacts are in working order. To double check these
Figure 10-64 — Three phase starter
controlled by a float switch.