Type of Charging Station(s) Proposed Power Levels (proposed circuit rating)
Check one
Level1
110/120 volt alternating current
(VAC ) at 15 or 20 Amps
Commercial/Office Building
Level 2 – 3.3 kilowatt (kW) (Low) 208/240 VAC at 20 or 30 Amps MultiUnit dwelling
Level 2 – 6.6 kW (medium) 208/240 VAC at 40 Amps Commercial Office Building
Level 2 – 9.6 kW (high) 208/240 VAC at 50 Amps Public Access
Level 2 – 19.2 kW (highest) 208/240 VAC at 100 Amps
DC Fast Charging 440 or 480 VAC
Public Access/Large Com.
Office Building or parks
Hospitality & Recreation
Other (Provide Detail):__________
Provide Ratings:__________________
PERMIT APPLICATION
A. Is the application complete with the following information: Project address, parcel #,
builder/owner name, contractor name, valid contractor license #, phone numbers etc.
Y N
B. Does the application include EVCS manufacturer’s specs and installation guidelines
Y
N
ELECTRIC LOAD CALCULATION WORKSHEET
A. Is an electrical load calculation worksheet included? (CEC 220)
Y
N
B. Based on the load calculation worksheet, is a new electrical service panel upgrade required
Y
N
1) If yes, do plans include the electrical service panel upgrade
Y N
C. Is the charging circuit appropriately sized for a continuous load (125%)
Y
N
D. If charging equipment proposed is a Level 2 – 9.6 kW station with a circuit rating of 50 Amps or
higher, is a completed circuit card with electrical calculations included with the single line diagram
Y
N
SITE PLAN & SINGLE LINE DRAWING
A. Is a site plan and electrical plan with a singleline diagram included with the permit application
Y
N
1) If mechanical ventilation requirements are triggered for indoor venting requirements
(CEC 625.52), is a mechanical plan included with the permit application
Y
N
B. Is the site plan fully dimensioned and drawn to scale
Y
N
1) Showing location, size, and use of all structures
Y
N
2) Showing location of electrical panel to charging system
Y
N
3) Showing type of charging system and mounting
Y
N
COMPLIANCE WITH 2019 CALIFORNIA ELECTRCIAL CODE (TITLE 24, PART 3)
A. Does the plan include EVCS manufacturer's specs and installation guidelines
Y
N
B. Does the electrical plan identify the amperage and location of existing electrical service panel
Y
N
1) If yes, does the existing panel schedule show room for additional breakers
Y
N
C. Is the charging unit rated more than 60 amps or more than 150V to ground
Y
N
1) If yes, are disconnecting means provided in a readily accessible location in line of site and
within 50’ of EVCS. (CEC 625.43)
Y
N
D. Does the charging equipment have a Nationally Recognized Testing Laboratory (NRTL) approved
listing mark. (UL 2202/UL 2200)
Y
N
E. If trenching is required, is the trenching detail called out
Y N
1) Is the trenching in compliance with electrical feeder requirements from structure to
structure? (CEC 225)
Y
N
2) Is the trenching in compliance of minimum cover requirements for wiring methods or circuits
(18” for direct burial per CEC 300)
Y
N
CITY OF YORBA LINDA
4845 Casa Loma Avenue Yorba Linda, California 92886
BUILDING DIVISION (714) 961-7120
Eligiblity Checklist for Expedited Electric Vehicle Charging Station Non-Residential Permitting
This checklist is provided to determine if your application is eligible for expedited EVCS processing.
If any item is checked NO, revise design, otherwise application must go through standard review process.
COMPLIANCE WITH 2019 MANDATORY CALGREEN CODE FOR NEW CONSTRUCTION
A. Do CAL Green EV Readiness installation requirements apply to this project
Y
N
1) Should be identified during plan review. (5.106.5.3.3)
Y
N
2) Do the plans demonstrate conformance with mandatory measures for 3% of total parking
spaces in lots with 51+ must be EV capable
Y
N