ENVIRONMENTAL HEALTH AND SAFETY
Fire and Life Safety
Plummer Building, Room 100 • PO Box 10807
Beaumont, Texas 77710 • Phone (409) 880.7115
EHS - Fire and Life Safety Page 1 of 5
Annual Building Fire Inspection Report
ANNUAL BUILDING FIRE INSPECTION REPORT
Date of Inspection: Re-Inspection Date:
Bu
ilding:
Ad
dress:
Contact Person: Phone:
Inspection conducted by EHS
Inspection conducted by Beaumont Fire and Rescue (BFR)
EHS Inspector:
BFR Inspector:
A F
ire and Life Safety inspection was conducted in accordance with Environmental Health and Safety (EHS) Policy.
Review of documents used as guidelines for compliance were Lamar University Safety Manual, Applicable
Administrative Directives and standards promulgated by:
OSHA 29CFR1910
NFPA 1 Fire and Life Safety Code 101
State Fire Marshal Review
National Electric Code
National Safety Counsel
Texas Hazard Communication Act
Findings of Inspection:
YES
NO
N/A
CODE EXTERIOR
NFPA 80A Is there waste accumulation around the building?
NFPA 13 Is fire department connection blocked? (8.17.2.4)
NFPA 13 Are caps missing from fire department connection? (8.17.2.4)
NFPA 1 Are fire lanes obstructed? (3.3.10.5)
feet
NFPA 13 What is distance to nearest fire hydrant?
YES
NO
N/A
CODE MEANS OF EGRESS
NFPA 101 Are stairways and all other fire doors closed (i.e., doors not blocked open)?
(8.2.4.3.5)
NFPA 101 Are self-closures on doors working properly? (7.2.1)
NFPA 101 Are means of egress open and without obstruction? (7.1.3.2.3)
NFPA 101 Are panic and fire exit hardware present and working properly? (7.3.2)
NFPA 101 Are means of egress equipped with emergency lights with backup power? (7.9)
NFPA 101 Do exit signs remain illuminated at all times with backup power? (7.10)
NFPA 101 Are exit doors operable without a key? (thumb bolt lock and/or panic
hardware) (7.2.1.5.4)
Clear Form
ENVIRONMENTAL HEALTH AND SAFETY
Fire and Life Safety
Plummer Building, Room 100 • PO Box 10807
Beaumont, Texas 77710 • Phone (409) 880.7115
EHS - Fire and Life Safety Page 2 of 5
Annual Building Fire Inspection Report
YES
NO
N/A
CODE STORAGE AND GENERAL HOUSKEEEPING
NFPA 231 Are hazardous conditions present?
NFPA 30
Are oily rags kept in locations other than a self-closing metal cabinet?
(4.1.3.5.12)
NFPA 30 Is storage of combustibles disorderly instead of neat and orderly? (106.D.3)
NFPA 30
Are combustibles stored too close to a heating source? (3 ft. minimum
clearance) (10.2.1)
NFPA 13 Is storage height within 18 inches of ceiling of sprinklered building? (E.5.6.1)
NFPA 13
Is storage height within 24 inches of ceiling of non-sprinklered building?
(8.5.6.2)
NFPA 13
Is there storage in boiler, mechanical, and electrical rooms? (not allowed)
(8.5.5.1)
NFPA 13
Is there less than 3 feet between sprinklers and tops of pile of combustible
fibers?
NFPA 101
Are areas under stairs missing the No Storage Allowed marking?
YES
NO
N/A
CODE FLAMMABLE STORAGE
NFPA 30 Are gas cylinders secured from falling and capped when not in use? (4.5.8)
NFPA 30 Are flammable liquids stored in approved closed metal cabinet? (6.3.2)
NFPA 30 Are gasoline and other flammable liquids stored in safety cans? (7.5.2)
YES
NO
N/A
CODE ELECTRICAL
NFPA 70 Are electrical wiring and/or components in need of repair? (110.3)
NFPA 70
Are there less than 30 inches in width, 36 inches in depth, and 78 inches in
height in and around electrical equipment? (110.26)
NFPA 70 Are circuits unmarked for proper usage? (110.22)
NFPA 70 Are multi-plug adapters used? (not allowed unless surge protected) (400.7.C)
NFPA 70
Are extension cords being used improperly? (such as used for permanent
wiring) (400.8)
NFPA 70 Are approved junction boxes missing cover plates? (314.28.C)
NFPA 70 Is exposed wiring visible? (not allowed) (100.3)
ENVIRONMENTAL HEALTH AND SAFETY
Fire and Life Safety
Plummer Building, Room 100 • PO Box 10807
Beaumont, Texas 77710 • Phone (409) 880.7115
EHS - Fire and Life Safety Page 3 of 5
Annual Building Fire Inspection Report
YES
NO
N/A
CODE FIRE SEPARATIONS
NFPA 101 Are repairs needed to fire walls/separations? (8.2.3.2.3.1)
NFPA 101 Are improper hold-open devices being used? (magnetic devices only) (7.2.1.14)
NFPA 101 Does closing device need adjustment or repair? (7.2.1)
NFPA 101
Are ceiling tiles missing from suspended ceilings? (must be in place)
(8.2.3.2.3.1)
YES
NO
N/A
CODE FIRE EXTINGUISHERS
NFPA 10
Are fire extinguishers present? (50 to 75 feet travel distance in normal
conditions for ABC fire extinguishers) (5.1.4)
NFPA 10
Is the annual inspection of fire extinguishers up-to-date? (6.2.1)
Date of last inspection:
NFPA 10
Are fire extinguishers installed in accessible and visible areas? (3.5 to 5 feet in
height with a minimum of 4 inches from floor) (157(C)(1))
YES
NO
N/A
CODE SPRINKLER SYSTEMS
NFPA 13 Are sprinkler heads located at the top and bottom of stairways? (8.15.3.2)
NFPA 13
Is the annual inspection and testing of sprinkler system up-to-date? (2.2.4.2)
Date of last inspection:
NFPA 13
Is the annual inspection and testing of standpipes up-to-date? (2.2.4.2)
Date of last inspection:
NFPA 14 Is fire hydrant located within 100 feet of fire department connection?
NFPA 13 Are signs for sprinkler system FDC and/or standpipe visible? (8.17.2.4.5)
NFPA 13 Is there a backflow preventer or check valve on the system? (7.8.4.2)
NFPA 13
Is a sprinkler head located in the bottom of elevator pit within 2 feet from
floor? (Hydraulic oil and/or combustible only) (8.15.5)
NFPA 13
Is attic sprinklered? (8.3.2.5)
NFPA 13
Are sprinkler heads installed under fixed obstructions over 4 feet wide?
(8.10.6.2)
NFPA 13
Are sprinkler heads located in all mechanical, communication, electrical and
storage rooms? (8.15.10.1)
ENVIRONMENTAL HEALTH AND SAFETY
Fire and Life Safety
Plummer Building, Room 100 • PO Box 10807
Beaumont, Texas 77710 • Phone (409) 880.7115
EHS - Fire and Life Safety Page 4 of 5
Annual Building Fire Inspection Report
NFPA 13
FOR DRY PIPE SYSTEMS - Is the trip test connection located on the end of the
most distant sprinkler pipe in the upper story? (8.16.2.4.6)
YES
NO
N/A
CODE FIRE ALARM SYSTEMS
NFPA 72 Is alarm annunciator panel located near entry? (4.4.6.3)
NFPA 72 Are smoke detectors provided in the elevator lobby area? (9.5.4.6)
NFPA 72
Is annual inspection and testing of system up-to-date? (10.2.1.2.2)
Date of last inspection:
NFPA 72 Is system in proper working order? (10.2.2.2)
NFPA 72
Are alarm system components clear and/or accessible?
NFPA 72 Are smoke detectors located in corridors and all sleeping areas? (4.4.6)
NFPA 72 Is elevator recall tied to the alarm system and working properly? (5.5.2.1)
NFPA 72 Do magnetic door locks release when the alarm system activated? (7.2)
NFPA 72
Does H
VAC system shut down when the alarm system is activated? (7.2)
NFPA 72
Are all strobes operating properly in all assembly rooms, restrooms, ADA rooms
an
d corridors? (5.7.4.2.2)
NFPA 72
Are smoke alarms located in the elevator shaft? (sm
oke detector at the shaft
and heat detector at bottom) (5.4.6)
NFPA 72
Do all mechanical, data, electrical, laundry and storage
rooms have operable
smoke and/or heat detectors? (5.4.6)
YES
NO
N/A
CODE HOOD AND DUCT SYSTEMS
NFPA 96 Are required hood and duct systems present? (4.1.1)
NFPA 96 Is commercial cooking system working properly? (gas shutoff present) (10.4.1)
NFPA 96 Are hood and duct systems properly maintained and clean? (11.4.1)
NFPA 96
Is six month inspection and testing of kitchen suppression system up-to-date?
(11.3) Date of last inspection:
YES
NO
N/A
CODE BOILER AND MECHANICAL ROOM HAZARDS
NFPA 31 Is emergency shut off to heating units labeled? (4.4.3)
NFPA 31 Are chimney and heating units maintained in a safe condition? (6.2.3)
ENVIRONMENTAL HEALTH AND SAFETY
Fire and Life Safety
Plummer Building, Room 100 • PO Box 10807
Beaumont, Texas 77710 • Phone (409) 880.7115
EHS - Fire and Life Safety Page 5 of 5
Annual Building Fire Inspection Report
NFPA 31 Is boiler room door self-closing and minimum one hour fireresistant rated?
(5.2.14.1)
NFPA 31
Is annual inspection of gas and oil-fired boilers up-to-date? (6.6.7.1)
Date of last inspection:
YES
NO
N/A
CODE EMERGENCY BUIDING SERVICES
NA Is smoking prohibited in the building?
NA Are no smoking signs posted?
NFPA 1 Are fire lanes kept clear and identified? (3.3.10.5)
NFPA 70 Are all utility rooms properly marked in case of emergency? (9.110.27(C))
NFPA 70 Are electrical and mechanical rooms labeled as such? (9.110.27(C))
NFPA 1 Does the Fire Department have access to all parts of the building? (7.110.8.5)
NFPA 101
Is evacuation plan(s) posted? (7.10.8.5)
TH&S Are AEDs maintained and inspections up to date? (799.007)
OSHA 1910 Are sharps containers maintained? (1030)
YES
NO
N/A
CODE HAZARDOUS CHEMICALS
OSHA 1200 Are all containers of hazardous chemicals properly labeled? (1200.B.3.i)
OSHA 1910 Are required SDS sheets for hazardous materials kept on file? (1900(G))
OSHA 1200 Does the department have a Hazard Communication Program that includes a
written inventory of hazardous chemicals, contact information of the
designated responsible party, location and access for the SDS for each chemical,
location of hazard communications training records, and emergency response
procedures? (1200.B.1)
OSHA 1200 Are hazard communications training records up to date? (1200.B.4.iii)
NOTES: