Note: Numbering is based on SI edition of ASHRAE 90.1-2010. December 23, 2013
ONTARIO BUILDING CODE AND SUPPLEMENTARY STANDARD SB-10
PROJECT INFORMATION
Project:
Location:
Building Permit Application No.:
Date:
Architectural Designer
Information*
Mechanical Designer
Information*
Electrical Designer
Information*
Name
Name
Name
Address
Address
Address
City Province
City Province
City Province
Signature Date(YY/MM/DD)
Signature Date(YY/MM/DD)
Signature Date(YY/MM/DD)
*IF MORE DESIGNERS ARE INVOLVED, PROVIDE ADDITIONAL COPIES OF THIS FORM.
THIS CHECKLIST IS A CONVENIENCE DOCUMENT ONLY AND IS BASED ON THE ENERGY EFFICIENCY REQUIREMENTS DESCRIBED IN THE ONTARIO
BUILDING CODE SUPPLEMENTARY STANDARD SB-10 DIVISION 2. THIS CHECKLIST IS NOT A SUBSTITUTE FOR COMPLYING WITH THE REQUIREMENTS OF
THE ONTARIO BUILDING CODE. WHILE CARE HAS BEEN TAKEN TO ENSURE ACCURACY OF THIS CHECKLIST, DESIGNERS AND BUILDING OFFICIALS MUST
REFER TO THE ACTUAL WORDING AND REQUIREMENTS OF THE ONTARIO BUILDING CODE (O.REG. 332/12 AND AMENDMENTS UP TO DECEMBER 23,
2013).
THIS CHECKLIST IS MADE AVAILABLE FOR CODE USERS BY THE MINISTRY OF MUNICIPAL AFFAIRS AND HOUSING. USERS SHOULD ALWAYS CONSULT
WITH THE AUTHORITY HAVING JURISDICTION, IF THE CHECKLIST IS GOING TO BE SUBMITTED TO THAT AUTHORITY. THE MINISTRY OF MUNICIPAL
AFFAIRS AND HOUSING DOES NOT ASSUME RESPONSIBILITY FOR ERRORS OR OVERSIGHTS RESULTING FROM THE INFORMATION CONTAINED HEREIN.
PLEASE FILL IN THE ACTUAL VALUES INSTALLED AND CHECK BOXES AS THEY APPLY.
OBC SB-10 COMPLIANCE SUMMARY
Energy Efficiency Design:
There are four energy compliance options to meet the requirements of OBC SB-10 Division 2. Please select the
conformance option selected for this project. The energy efficiency of all buildings must be designed to:
Compliance Path
(A-1) Exceed by not less than 25% the energy efficiency levels attained by conforming to the CCBFC, “Model
National Energy Code for Buildings (MNECB).”
Note that this compliance path requires that the proposed building is shown to consume at least 25% less energy
than the MNECB reference building when modelled according to the procedures outlined in Part 8 of the MNECB.
YES
(A-2) Exceed by not less than 5% the energy efficiency levels attained by conforming to the ANSI/ASHRAE/IESNA
90.1 - 2010 “Energy Standard for Buildings Except Low-Rise Residential Buildings.”
Note that this compliance path requires that the proposed building is shown to consume at least 5% less energy
than the ASHRAE 90.1-2010 reference building when modelled according to the procedures outlined in Chapter
11 of ASHRAE 90.1-2010.
Note that this path cannot be used for a building with electric space heating. Refer to SB-10.
YES
(B) Achieve the energy efficiency levels attained by conforming to the ASHRAE 90.1-2010, “Energy Standard for
Buildings Except Low-Rise Residential Buildings” and Division 2 of SB-10.
This compliance path includes both prescriptive and performance path options. Please proceed to Form B.
YES
(C) Achieve the energy efficiency levels attained by conforming to the NECB-2011 National Energy Code of Canada
for Buildings and Division 2 of SB‐10.
This compliance path includes both prescriptive and performance path options. Please proceed to NECB Forms
YES
OBC SB‐10 COMPLIANCE (1) EXCEED MNECB BY NOT LESS THAN 25% FORM A
(2) EXCEED ASHRAE 90.1‐2010 BY NOT LESS THAN 5%
Please select which of the two options pursued for compliance:
PROPOSED BUILDING IS SHOWN TO CONSUME AT LEAST 25% LESS ENERGY (GJ or kWh) ANNUALLY THAN THE
MNECB REFERENCE BUILDING. ENERGY CONSUMPTION VALUES ARE DETERMINED ACCORDING TO THE MODELLING
PROCEDURES IDENTIFIED IN PART 8 OF THE MNECB.
YES
PROPOSED BUILDING IS SHOWN TO CONSUME AT LEAST 5% LESS ENERGY (GJ or kWh) ANNUALLY THAN THE
ASHRAE 90.1‐2010 REFERENCE BUILDING. ENERGY CONSUMPTION VALUES ARE DETERMINED ACCORDING TO THE
MODELLING PROCEDURES OUTLINED IN CHAPTER 11 OF ASHRAE 90.1‐2010.
YES
Project:
Modeller Name:
An
n
ual
Ene
r
gy
Summary
(1)
Occupancies Floor Area
Assembly
Health/Institutional
Hotel/Motel
Light Manufacturing
Multifamily
Office
Re
s
t
aurant
Retail
School
Warehouse
Other
Total
Proposed Building Description
Annual Consumption Summary Reference Building Proposed Units
Energy Building Energy
Space
He
ating
Space Cooling
HVAC Auxiliar
y
Misc.
Electr
ical
Service
Hot
Water
Interior
Lighting
Other
Other
Total Annual Energy >
Percentage less energy used
by proposed building:
Total Annual CO
2
e Emissions ………………… > ………………………..
Percentage less CO
2
e emissions by proposed building ………………………..
Peak Electric Demand ………………… > ……………………….. □ YES or
Building components specified in Sentence 1.1.2.3.(2) of Chapter 1 of Division 2 of SB‐10
comply with the prescriptive requirements of ASHRAE 90.1‐2010 □ YES
Reference Building Energy and Proposed Building Energy Consumptions are calculated
by:
Ple
as
e
spec
ify modelling
software:
D
e
scriptions
Energy
Efficiency
Features
i
n Proposed
Building
Design
(2)
Reference Building Design
Proposed Building Design
The reference building and proposed building design are modelled in accordance with the requirements of the SB‐10 and the applicable
standard specified above □ Yes
The information submitted above is accurate to the best of my knowledge.
Signature: Name/Title:
Notes: (1) Verify with building official whether full modelling report is required to be submitted.
(2) Explain major energy saving features utilized to achieve modelled savings.
Note: Numbering is based on SI edition of ASHRAE 90.1‐2010. December 23, 2012
OBC SB‐10 AND ASHRAE 90.1 ‐ 2010 – COMPLIANCE SUMMARY Form B
Project: Location of Project:
Building Permit Application No.: Climate Zone:
ASHRAE 90.1 – 2010 COMPLIANCE AS MODIFIED BY OBC SB‐10 DIVISION 2
The
building design complies
w
i
t
h the
mandatory
provi
s
ions of t
h
e following se
c
t
i
ons
regar
d
l
ess
o
f the
compliance
path:
ASHRAE 90.1‐2010 Standard Section Compliance
Column
Form
5.4 BUILDING
E
NVELO
P
E
AND
S
B
‐10
DIVISION
2
YES
FORM 5.4
6.4 HEATING, VENTILATING AND AIR CONDITIONING AND SB‐10 DIVISION 2 YES FORM 6.3 or
FORM 6.4
7.4 SERVICE W
A
TER
HEATING
SYSTEMS AND
EQUIPMENT
AND
S
B
‐10
DIVISION
2
YES
FORM 7.4
8.4
POW
E
R
AND
S
B
‐10
DIVISION
2
YES
FORM 8.4
9.4 LIGHTING
AND
S
B
‐10
DIVISION
2
YES
FORM 9.4
10.4 OTHER EQUIPMENT AND SB‐10 DIVISION 2 YES FORM 10.4
METHOD OF COMPLIANCE
Building Design must comply with either the Prescriptive Requirements or the Energy Cost Budget Method. Indicate which method was
selected.
Compliance Method Compliance
Column
Form
PRES
C
R
IPTIVE
C
OMPLIANCE
YES
COMPLE
T
E SEC
T
ION
B
‐1
ENERGY COST BUDGET MET
H
OD
YES
COMPLE
T
E SEC
T
ION
B
‐2
B‐1: PRESCRIPTIVE COMPLIANCE – ASHRAE 90.1‐2010 AND OBC SB‐10
The
building
de
si
gn complies
wi
t
h the
Pr
e
scripti
v
e
Compliance
of
the
following sections:
Standard Section
R
e
fer
e
nce
Compliance
Column
Form
Sec 5 BUILDING ENVELOPE Prescriptive Requirements (5.5 of 90.1)
Building Envelope Trade‐Off (5.6 of 90.1)
YES
YES
FORM 5.5 or
FORM 5.6
Sec 6 HVAC SYSTEMS Simplified Approach for HVAC Systems
Mandato
r
y
+ Pr
e
scriptive
Path
Option
YES
YES
FORM 6.3 or
FORM 6.4
Sec
7
SERVICE WATER
HEATING
Pr
e
scriptive
Path
Option
YES
FORM 7.4
Sec 9 LIGHTING Prescriptive Requirements YES FORM 9.5
B‐2: ENERGY COST BUDGET METHOD – ASHRAE 90.1‐2010 AND OBC SB‐10
Compliance
Column
Form
The building design complies with the provisions of Section 11 of ASHRAE 90.1‐2010,
based on the provisions of Division 2 of SB‐10.
YES FORM 11
Note: Numbering is based on SI edition of ASHRAE 90.1‐2010. December 23, 2013
Note:
Numb
e
ring
i
s
based
on
SI
edition
of
AS
H
RAE
9
0
.1
‐2
0
10.
December 23, 2013
ASHRAE 90.1‐2010 AND OBC SB‐10 DIVISION 2– BUILDING ENVELOPE PROVISIONS Form 5.4
SECTION
5.4
M
A
NDATORY
PRO
V
ISIONS
Building insulation has been designed to comply with section 5.4.1 of ASHRAE 90.1‐2010 as
modified by Division 2 of OBC SB‐10.
YES
Building fenestration and doors have been designed to comply with section 5.4.2 of ASHRAE
90.1‐2010 as modified by Division 2 of OBC SB‐10.
YES
Building air leakage has been designed to comply with section 5.4.3 of ASHRAE 90.1‐2010 as
modified by Division 2 of OBC SB‐10.
YES
ASHRAE 90.1‐2010 & SB‐10 – SECTION 5.5 – PRESCRIPTIVE ENVELOPE OPTION Form 5.5‐1
Section 5.5 Overall Building Design Requirements
The building design must comply with the following general requirements. If any of these requirements are not met, the prescriptive
path cannot be pursued. Consider the building envelope trade‐off compliance or the Energy Cost Budget Method Described
in
Chapter
11
of ASHRAE
90.1
‐2010:
Identify SB‐
10
Tabl
e
used for
ma
ximum
U
‐Factors
or
minimum RSI‐Values:
_____________________
Gross Wall Area:
Vertical Fenestration Area:
Vertic
a
l
fenestration area
i
s
less
than 40%
of the
gross
w
a
l
l
a
r
ea
YES
Gross Roof Area:
Skylight Area:
Total skylight area does not exceed 5% of the gross roof area
YES
The vertical fenestration areas of the building meet the requirements of Section 5.5.4.5. of the
ASHRAE 90.1‐2010 as modified by Division 2 of OBC SB‐10
YES
If electric space heating is used, Table SB5.5‐7 has been used regardless of climatic location YES N/A
For Climate Zone 5, minimum skylight fenestration area conforms to the requirements of
ASHRAE 90.1‐2010 5.5.4.2.3.
YES N/A
Complete the table on Form 5.5‐2 to show compliance for all envelope components. Attach as many copies of this form as required
to ensure that all envelope components are represented.
For all opaque surfaces, compliance must be demonstrated by meeting either:
1. The minimum R‐values of insulation added in framing cavities and continuous insulation as specified in Tables SB5.5‐5 to
SB5.5‐7.
2. The maximum U‐factor, C‐factor, or F‐factor for the entire assembly as specified in Tables SB5.5‐5 to SB5.5‐7. U‐factor is to be
determined from tables in Appendix A of ASHRAE 90.1‐2010 or through calculation methods described in ASHRAE 90.1‐2010
Appendix Section A9.
For all fenestration products, compliance with U‐factors and SHGC must be determined for the overall fenestration product.
1. Fenestration shall have a U‐factor and SHGC not greater than those specified in SB‐10 Tables SB5.5‐5 to SB5.5‐7.
2. U‐factor to be determined through CSA or NFRC rating or by using ASHRAE 90.1‐2010 Appendix A default values.
Note:
Numb
e
ring
i
s
based
on
SI
edition
of
AS
H
RAE
9
0
.1
‐2
0
10.
December
23,
2
0
1
3
ASHRAE 90.1‐2010 & SB‐10 – SECTION 5.5 – PRESCRIPTIVE ENVELOPE OPTION Form 5.5‐2
Please complete the following table to include information on all walls, roofs, doors, and floors used in the design.
OPAQUE BUILDING ENVELOPE COMPONENTS
Opaque Element
Description
(1)
Space Conditioning
Category
(2)
Class of
Construction
(3)
Criteria Max. U‐Value
(4)
or Min RSI‐Value
Design U‐Value
(
4
)
or RSI‐Value
Area Weighted
Average Used
(5)
?
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR
R
SH
Y
N
Please complete the following table to include information on all fenestration products used in the design.
FENESTRATION ENVELOPE COMPONENTS
Fenestration ‐
Description
(1)
Space Conditioning
Category
(2)
Class of
Construction
(3)
U‐Value
(4)
SHGC
(
6
)
Area Weighted
Average Used
(5)
?
Criteria Design Criteria Design
NR
R
SH
Y
N
NR R SH
Y N
NR
R
SH
Y
N
NR
R
SH
Y
N
NR R SH
Y N
NR
R
SH
Y
N
NR R SH
Y N
NR
R
SH
Y
N
NR R SH
Y N
(1) Indicate if Element is a Wall, Roof, Floor, Door, Window or Skylight and a Tag or Description (eg Wall – W1).
(2) Select from Non‐residential (NR), Residential (R), or Semiheated (SH).
(3) Select from the subclasses of roofs, walls, floors, doors and fenestration provided in Tables SB5.5‐5 to SB5.5‐7 (eg. Steel
Framed for walls). Note that curtain wall systems are considered a steel framed wall.
(4) F‐Factors can be used for floors and C‐Factors for below Grade Walls as applicable.
(5) Elements of the same type, space category, and class of construction can be averaged using area weighting to show
compliance only if U‐Values are used.
(6) Design SHGC may be higher than the criteria if the one of the exceptions from ASHRAE 90.1‐2010 5.5.4.4.1 is applicable.
Please use the space below to identify the fenestration elements (if any) which an exception for SHGC is being claimed:
SHGC EXCEPTIONS
Fenestration Element SHGC Exception from ASHRAE 90.1‐2010 5.5.4.4.1
Note: Numbering is based on SI edition of ASHRAE 90.1‐2010. December 23, 2013
ASHRAE 90.1‐2010 & SB‐10 – SECTION 5.6 –BUILDING. ENVELOPE TRADE‐OFF OPTION Form 5.6
Note that this option may only be pursued if the procedure as described in ASHRAE 90.1‐2010 section 5.6 has been
modified with the requirements of Division 2 of SB‐10.
Complete only Section A or Section B
Section A
(Complete only where software report contains the percentage of difference between budget and design buildings)
A software program incorporating the envelope requirements of ASHRAE 90.1‐2010 as modified by SB‐10
has been used to demonstrate compliance with SB‐10 in accordance with rules set by Section 5.6 of ASHRAE
90.1
2010
.
YES
State the percentage by which the envelope performance of the proposed building is better than the budget
building.
______ %, or
□ Equal
A report from this software is attached.
Name
of
software:
_______
YES
Section B
(Complete only where software report contains envelope performance factors for the budget and design buildings)
The compliance calculations are based on the envelope requirements of ASHRAE 90.1‐2010 as modified by
SB‐10.
YES
Envelope performance factor (EPF) for proposed building is less than or equal to the envelope performance
factor of the budget building.
Calculated EPF for proposed building:
Calculated EPF for budget building:
YES
The envelope performance factor considers only the building envelope components. YES
Schedules of operation, lighting power, equipment power, occupant density, and mechanical systems are the
same in both the proposed and budget building.
YES
Calculations from ASHRAE 90.1‐2010 Appendix C have been attached, and include the modifications from SB‐10. YES
Note:NumberingisbasedonSIeditionofASHRAE90.12010. April23,2012
ASHRAE90.1&SB10‐SECTION6.3HVACSIMPLIFIEDAPPROACHForm6.3
IfsimplifiedHVACmethodisusedcompletethisform,otherwiseproceedtoForm6.4.
NumberofStories: Grossfloorarea: 

Reference StandardCompliance
6.3.1 Thebuildingis2storiesorlessinheightandhasagrossfloorarealessthan2,323m².□YES NO
6.3.2 AlloftherequirementsinSection6.3asoutlinedbelowmustbemetbyeachHVACsysteminthe
facility.
6.3.2.a SystemservesasingleHVACzone.□YES NO
6.3.2.b TheequipmentmeetsthevariableflowrequirementsofSection6.4.3.10.□YES□N/A□NO
6.3.2.c Ifacoolingisinstalled,itisprovidedbyaunitarypackagedorsplitsystemairconditionerthatis
eitheraircooledorevaporativelycooledandmeetstheefficiencyrequirementsshowninTables
6.8.1A,6.8.1B,and6.8.1D.
□YES□N/A□NO
6.3.2.d Thesystemhasanaireconomizerwithoutsideairflowcapacityandcontrolsasrequiredper
Section6.5.1.,unlessexempt.
□YES□N/A□NO
6.3.2.e Heatingisprovidedbyaunitarypackagedorsplitsystemheatpump,afuelfiredfurnace,an
electricresistanceheaterorabaseboardsystemconnectedtoaboiler.Allheatingequipment
meetstheefficiencyrequirementsshowninTable6.8.1B,6.8.1D,6.8.1E,and6.8.1F.
□YES□N/A□NO
6.3.2.f SystemmeetstheexhaustairenergyrecoveryrequirementsofSection6.5.6.1,unlessexempt.□YES□N/A□NO
6.3.2.g Thesystemiscontrolledbyamanualchangeoverordualsetpointthermostat.□YES NO
6.3.2.h Heatpumpsequippedwithauxiliaryinternalelectricresistanceheaters(ifany)havecontrolsto
preventsupplementalheateroperationwhentheheatingloadcanbemetbytheheatpump
alone.
□YES□N/A□NO
6.3.2.i Thesystemcontrolsdonotpermitreheatoranyotherformofsimultaneousheatingandcooling
forhumiditycontrol.
□YES□N/A□NO
6.3.2.j Systemsareprovidedwithatimeswitchthat(1)canstartandstopthesystemunderdifferent
schedulesforsevendifferentdaytypesperweek;(2)iscapableofretainingprogrammingand
timesettingduringalossofpowerforaperiodofatleast10h;(3)includesanaccessiblemanual
overridethatallowstemporaryoperationofthesystemforupto2h;(4)iscapableof
temperaturesetbackdownto13°Cduringoffhours;and(5)iscapableoftemperaturesetupto
32°Cduringoffhoursunlessexempt.
□YES□N/A□NO
6.3.2.k PipingisinsulatedinaccordancewithvaluesgiveninTable6.8.3Aand6.8.3B.Insulationexposed
toweatherissuitableforoutdoorservice(i.e.protectedbyaluminum,sheetmetal,etc.orpainted
withacoatingthatiswaterretardantandprovidesshieldingfromsolarradiation).
□YES□N/A□NO
6.3.2.l DuctworkandplenumsareinsulatedinaccordancewithTables6.8.2Aand6.8.2Bandsealedin
accordancewithSection6.4.4.2.1.
□YES□N/A□NO
6.3.2.m Specificationscallforductedairsystemstobebalanced.□YES□N/A□NO
6.3.2.n OutdoorairintakeandexhaustsystemsmeetthecontrolsrequirementsofSection6.4.3.4.□YES□N/A□NO
6.3.2.o Whereseparateheatingandcoolingequipmentservethesametemperaturezone,thermostats
areinterlockedtopreventsimultaneousheatingandcooling.
□YES□N/A□NO
6.3.2.p Systemswithadesignsupplyaircapacitygreaterthan5,000L/shaveoptimumstartcontrols.□YES□N/A□NO
6.3.2.q Inspaceslargerthan50m²andwithdesignoccupancyofmorethan40peopleper100m²,the
systemcomplieswiththedemandcontrolventilationrequirementsinSection6.4.3.9,unless
exempt.
□YES□N/A□NO
SECTION
6
HVAC
6.4
MAND
A
TORY
PROVISIONS
AND
6.5
PR
E
SCRIPTIVE
REQ
U
IREMENTS
Form 6.4
Reference
Standard Compliance
Mandatory
Pro
v
isions
Complete
only
if simp
l
ified
HVAC me
th
od
is
no
t
u
s
ed.
6.4.1 Equipment shown in Tables 6.8.1A through 6.8.1K meets minimum performance at the specified
rating conditions in accordance with the test procedures in the tables or those referred to in
Division
2 of SB‐10.
□ YES □ NO
6.4.2.1 Load calculations for heating and cooling systems are done as per ASHRAE Standard 183‐2007 for
selection
of all equipment and
s
y
stems.
□ YES □ NO
6.4.2.2 Pressure drop through each device and pipe segment in the critical circuit at design conditions has
been calculated in accordance with generally accepted engineering standards and handbooks.
□ YES □ NO
6.4.3 Mandatory controls requirements are met by all the equipment in the building as outlined in
Section 6.4.3.
□ YES □ NO
6.4.4.1
Ductwo
r
k,
pipi
ng
,
and equip
me
nt
insulation meets
the
require
m
e
nts
of Section 6.4.4.1.
YES
NO
6.4.4.2 Construction documents specify sealing and pressure testing of ductworks and plenums as per
Section 6.4.4.2.
□ YES □ NO
Prescripti
v
e
R
e
q
u
ireme
n
ts
Com
p
l
e
te
th
i
s
sec
t
ion
if
n
o
t
using
Energy Cost
Budg
e
t
Method.
6.5.1
Each
cooling
sy
s
tem
that has
a
f
an emp
l
oys
e
i
ther
airside
or
waterside
economizer
unless
exem
p
t.
□ YES
N/A
NO
6.5.1.1 Airside economizers are capable of modulating outdoor air dampers to provide up to 100% design
airflow
for cooling
and
th
e
s
y
st
e
m
provides r
e
lief
capacity for su
c
h airflow.
□ YES □ N/A □ NO
6.5.1.2.1 Waterside economizers are capable of cooling supply air up to 100% of the expected system
cooling
load at
th
e
conditions li
s
t
e
d
under
S
e
cti
o
n
6.5.1.2.1.
□ YES □ N/A □ NO
6.5.1.2.2 Waterside economizer systems with pressure drop greater than 45kPa are isolated from main
cooling loop to reduce pumping input in the normal cooling mode.
□ YES □ N/A □ NO
6.5.1.3 Economizer systems are capable of providing cooling even when additional mechanical cooling is
required to meet the cooling load.
□ YES □ N/A □ NO
6.5.2 Simultaneous heating and cooling is limited with compliant zone, hydronic system,
dehumidification,
and humidification contr
o
ls
as
per
Section 6.5.2.
□ YES □ N/A □ NO
6.5.3
Variable
air vol
u
me
(VAV) fan controls
comply
w
i
th the
require
m
e
nts
of 6.5.3.2
a
nd 6.5.3.3.
YES
N/A
NO
6.5.3.1 Fan systems exceeding 4kW nameplate power meet prescriptive fan power limitations as per
Table
6.5.3.1.1A
and Section 6.5.3.1.2.
□ YES □ N/A □ NO
6.5.4.1
Pumping
syste
m
s
greater
than 7
.
5
kW
emp
l
oy
c
o
mpliant variable
flow contr
o
ls,
u
n
l
e
ss e
x
empt.
YES
N/A
NO
6.5.4.2 Chilled water plants with more than one chiller and boiler plants with more than one boiler
reduce
loop water
flow automat
i
cally
whenever
a
chiller
o
r
boiler
i
s
shut down.
□ YES □ N/A □ NO
6.5.4.3 Hydronic systems exceeding design capacity of 88 kW include controls to reset supply water
temperature based on building loads or outdoor air temperature.
□ YES □ N/A □ NO
6.5.4.4 Hydronic heat pumps and unitary air‐conditioners include automatic water shutoff when the
compressor is off and those having total pump system power greater than 3.7 kW have variable
speed control.
□ YES □ N/A □ NO
6.5.4.5
Chilled
water
and condenser wa
t
e
r
pipe
i
s
sized according
to Table
6.5.4.5.
YES
N/A
NO
6.5.5 All heat rejection equipment with fan motors > 5.6 kW employs variable speed controls that
comply
with
Section 6.5.5.2.
□ YES □ N/A □ NO
6.5.6.1 Exhaust air energy recovery is provided for fan systems meeting the conditions listed on Table
6.5.6.1. Energy recovery is at least 50% effective and bypass is available to permit air economizer
operation as per Section 6.5.1.1.
□ YES □ N/A □ NO
6.5.6.2
Conden
s
er
heat
recovery
system
for heating
or
p
reheating
hot
w
at
e
r
i
s
provided, unless
exempt.
YES
N/A
NO
6.5.7.1
Kitchen exhaust
systems
are
d
e
signed
a
s
per
S
e
cti
on
6.5.7.1.
YES
N/A
NO
6.5.7.1.5
Specifications
c
a
l
l
for performance
testing
of kit
c
hen
ex
h
aust s
y
s
t
ems.
YES
N/A
NO
6.5.7.2 Laboratory fume hoods with a total exhaust system flow > 2,360 L/S comply with the variable air
volume control requirements of 6.5.7.2.
□ YES □ N/A □ NO
6.5.8.1
H
e
ating
of une
n
closed
spa
c
es
i
s
done by radiant
heating,
exc
e
pt
loading
docks
with air curtains.
YES
N/A
NO
6.5.9 Cooling equipment with hot‐gas bypass controls is designed with multiple steps of unloading or
continuous capacity modulation, unless exempt as indicated in Table 6.5.9.
□ YES □ N/A □ NO
Note: Numbering is based on SI edition of ASHRAE 90.1‐2010. December 23, 2013
ASHRAE 90.1 & SB‐10SECTION 7 SERVICE WATER HEATING Form 7.4
SECTION
7
SERVICE
WATER HEATING
7.4
M
A
NDATORY
PRO
V
ISIONS
AND
7.5
PRESCRIPTIVE
REQUIREMENTS
Reference Item Standard Compliance
7.4.1 Load calculations for heating and cooling systems are done in accordance with manufacturer’s
published sizing guidelines or generally accepted engineering standards and handbooks for
selection of all equipment and systems.
□ YES □ NO
7.4.2 Equipment used solely for heating potable water, pool heaters, and hot water storage tanks
meets or exceeds the efficiency requirements of Table 7.8. or those referred to in Division 2 of SB‐
10.
□ YES □ N/A □ NO
7.4.3 The following service hot water piping is insulated to levels shown in Table 6.8.3:
a. Recirculating system piping, including piping of a circulating tank type water heater.
b. The first 2.4m of outlet piping for a constant temperature non‐recirculating storage
system.
c. Inlet pipe between storage tank and heat trap in a non‐recirculating storage system.
d. Pipes that are externally heated (e.g. heat tracing).
□ YES □ N/A □ NO
7.4.4.1 All water‐heating systems have temperature controls that are adjustable down to 49
o
C or lower.
Exception: Equipment that must be protected from corrosion, as per manufacturer’s
installation instructions.
□ YES □ N/A □ NO
7.4.4.2 Systems designed with pipe heating systems such as heat trace have temperature or time
controls
to disa
b
l
e during
exten
d
ed
periods
without hot water
demand.
□ YES □ N/A □ NO
7.4.4.3
Public
lavatories
have
outlet
temperature
contro
l
s
that limit the
discharge
tempe
r
ature
to 43
o
C.
YES
N/A
NO
7.4.4.4 Tanks with remote heaters have circulation pump controls to limit operation of circulation pumps
to a maximum of five
minutes
a
f
ter
the
end of
th
e
heating
cycl
e
.
□ YES □ N/A □ NO
7.4.5.1 Pool heaters have readily accessible ON/OFF switch without adjusting the thermostat setting.
Gas
‐fired
h
eat
e
r
s
do not ha
v
e s
t
anding pilot lights.
□ YES □ N/A □ NO
7.4.5.2 Heated pools have vapour retardant covers. Pools heated to above 32°C have a pool cover with a
minimum insulation value
of RSI
‐2.1 unless
hea
t
ed
by sit
e
‐recovered
e
n
ergy
or
solar
energy.
□ YES □ N/A □ NO
7.4.5.3
Pool heaters
and circ
u
l
ation pumps ha
v
e time
switches, unless
exempt.
YES
N/A
NO
7.4.6
H
e
at
traps
are
provid
e
d
to all vertic
a
l
risers
serving
storage
water
heaters
and
storage
tanks.
YES
N/A
NO
Prescripti
v
e
R
e
q
u
ireme
n
t
Com
p
l
e
t
e
th
i
s
secti
o
n
if
no
t
us
i
n
g
Energy Cost
Bud
ge
t
Method.
7.5 Boiler systems that provide space heating as well as service water heating meet the conditions of
Sections 7.5.1 and 7.5.2.
□ YES □ N/A □ NO
Note: Numbering is based on SI edition of ASHRAE 90.1‐2010. December 23, 2013
Note: Numbering is based on SI edition of ASHRAE 90.1-2010. April 23, 2012
ASHRAE 90.1 & SB-10- SECTION 8,9 &10 POWER, LIGHTING AND OTHER EQUIPMENT
SECTION 8 POWER 8.4 MANDATORY PROVISIONS Form 8.4
Reference
Item
Standard Compliance
8.1.2
Low Voltage Dry-Type Distribution Transformers meet nominal efficiencies shown in Table 8.1,
unless exempt.
□ YES □ N/A □ NO
8.4.1
Feeder conductors and branch conductors are sized as per Section 8.4.1.
□ YES □ NO
8.4.2
At least 50% of all 125 volt 15- and 20-Ampere receptacles installed in computer classrooms are
provided with automatic receptacle controls that function on a) time-of-day schedule or b)
occupant sensor or c) occupancy signal from another control or alarm system.
□ YES □ NO
SECTION 9 LIGHTING 9.4 MANDATORY PROVISIONS Form 9.4
Reference
Item
Standard Compliance
9.4.1
Any automatic control devices used are “manual ON” or multi-level where the “automatic ON”
function provides no more than 50% power unless exempt.
□ YES □ NO
9.4.1.1
Automatic lighting shutoff controls are provided for all interior spaces based on either a
scheduled basis or controlled by an occupant sensor unless exempt.
□ YES □ N/A □ NO
Schedule-based control devices are provided with independent schedules for areas of no more
than 2,323m² but no more than one floor.
□ YES □ NO
Occupancy-based control devices turn lights off within 30 minutes of all occupants leaving the
space, or a signal from another control or alarm system that indicates the area is unoccupied.
□ YES □ NO
9.4.1.2
Each space enclosed by ceiling-height partitions has at least one readily accessible control device
that independently operates general lighting within the space in such a way that occupants can
see the controlled lighting with multi-step controls and occupant sensors as per Section 9.4.1.2
□ YES □ NO
9.4.1.3
Lighting for parking garages is controlled by automatic shutoff controls meeting the requirements
outlined in Section 9.4.1.1.
□ YES □ N/A □ NO
Parking garage lighting is capable of automatically reducing lighting power by at least 30% based
on occupancy.
□ YES □ N/A □ NO
Daylight transition zones in parking garages are controlled separately. These are automatically
turned on during daylight hours and off at sunset.
□ YES □ N/A □ NO
Parking garage luminaires within 6m of perimeter walls that have a net opening-to-wall ratio of at
least 40% automatically reduce power in response to daylight, except daylight transition zones.
□ YES □ N/A □ NO
9.4.1.4
Automatic daylighting controls are provided for separate control of general lighting in primary
sidelighted areas greater than 23m² in an enclosed space. Multilevel photocontrol device
complies with 9.4.1.4c unless exempt.
□ YES □ N/A □ NO
9.4.1.5
Automatic daylighting controls are provided for separate control of general lighting in daylight
areas as required under Section 9.4.1.5. Multilevel photocontrol device complies with 9.4.1.5c
unless exempt.
□ YES □ N/A □ NO
9.4.1.6
Additional control is provided to the applications listed in Section 9.4.1.6. and Div. 2 of SB-10
□ YES □ N/A □ NO
9.4.1.7
Exterior lights are shut off by an automatic photosensor when available daylight is sufficient,
unless exempt.
□ YES □ N/A □ NO
All building façade and landscape lighting is automatically shut off overnight as per 9.4.1.7b.
□ YES □ NO
Exterior lighting not for façade, landscape lighting, or uncovered parking areas, including
advertising signage, is automatically controlled to reduce lighting power by at least 30% overnight
or during inactive periods.
□ YES □ NO
9.4.2
Exit signs do not exceed 5 W per face.
□ YES □ NO
9.4.4
Third party functional testing of all lighting control devices and systems is specified in the
construction documents.
□ YES □ NO
SECTION 9 LIGHTING – INSTALLED LIGHTING POWER COMPLIANCE CHECKLIST* Form 9.5
R
e
fer
e
nce
Standard
Compliance
9.4.3 Exterior Lighting Zone (Table 9.4.3A)
Total Installed Exterior Lighting Power W ≤ value of
exterior LPA W *
List any exemptions that apply:
□ YES □ N/A □ NO
Prescriptive Requirements – Complete if not using Energy Cost Budget Method
9.5, 9.6
METHOD
O
F INTERIOR
LI
G
HTING
ALLOWANCE
CA
LC
ULATION
Bui
l
ding
Spa
c
e
9.5 INTERIOR LIGHTING POWER ALLOWANCE BY BUILDING TYPE
Calculation of Interior Lighting Power Allowance (ILPA) by Building Type based on Table 9.5.1.*
B
uilding
Type
Gross Lighted Area
Lighting Power Density W/m²
Total Installed Interior Lighting Power W ≤ value of
interior LPA W *
□ YES □ N/A □ NO
9.6 INTERIOR LIGHTING POWER ALLOWANCE BY SPACE FUNCTION
Calculation of Interior Lighting Power Allowance (ILPA) for each space based on Table 9.6.1. *
Total Installed Interior Lighting Power W ≤ value of
Interior LPA W *
List any exemptions that apply:
□ YES □ N/A □ NO
Total installed interior and exterior lighting power allowances are met. □ YES □ NO
* Calculation worksheets (FORM 9.5.2 and FORM 9.5.3) are required. Where a software program is used to calculate compliance with Sections 9.4, 9.5 and
9.6, the software report may be submitted in lieu of FORM 9.5 and worksheets.
SECTION 10 OTHER EQUIPMENT ‐ MANDATORY PROVISIONS Detailed Form 10.4
R
e
fer
e
nce
Item
Standard
Compliance
10.4.1 Electric motors comply with Table 10.4.1.A(a) and Table 10.4.1.A(b) of Division 2 of SB‐10. YES
10.4.2 Service water pressure booster pumps have pressure sensor to vary pump speed and/or start and
stop pump
s
.
YES N/A
No devices are installed to reduce the pressure of all of the water supplied by any booster system
or pump, except for safety devices.
YES N/A
Booster
pum
p
s
s
hut off when
ther
e
i
s
no service
water
flow.
YES
N/A
10.4.3
All elevator cab lighting systems have efficacy of not less than 35 lumens per Watt. YES N/A
Elevator cab ventilation fans for elevators without air conditioning consume less than 0.7 W∙s/L
at maximum speed.
YES N/A
Cab interior light and ventilation is disabled when elevators are stopped and unoccupied with
doors closed for over 15 minutes.
YES N/A
All mandatory provisions are met. □ YES □ NO
Note: Numbering is based on SI edition of ASHRAE 90.1‐2010. December 23, 2013
Note:NumberingisbasedonSIeditionofASHRAE90.12010. April23,2012
ASHRAE90.1&SB10‐SECTION9LIGHTINGCOMPLIANCEWORKSHEET FORM9.5.2
Project: DesignerName:
InteriorPowerAllowance(BuildingAreaMethod)Table9.5.1
Building
Type
LightingPowerDensity
Allowance(W/m²)
GrossLightedFloorArea
(m²)
LightingPowerAllowance
(W)(LPDxGLFA)





Total PowerAllowance
InteriorLightingPowerAllowance(SpacebySpaceMethod)Table9.6.1
Building
Type
Common/Specific
SpaceType
LightingPowerDensity
Allowance(W/m²)
SpaceArea
(m²)
LightingPowerAllowance
(W)









Total PowerAllowance
InteriorConnectedLightingPower
Space
ID
LuminaireDescription
(includingnumberoflampsperfixture,watts
perlamp,typeofballast,typeoffixture)
Numberof
Luminaires
Watts/
Luminaire
Total
Watts











Total InteriorLightingPower
*Ifadditionalspaceisrequiredtoprovidefurtherinformation,pleaseattachaseparatesheet(s)ofpaper.
**Ifadditionalinteriorlightingpower,tradeoffsorexceptionsareusedattachcalculations.
Note:NumberingisbasedonSIeditionofASHRAE90.12010. April23,2012
ASHRAE90.1&SB10‐SECTION9LIGHTINGCOMPLIANCEWORKSHEET FORM9.5.3
Project: DesignerName:
ExteriorBuildingLightingPowerAllowance
Location/Application Allowance AreaorLength(m²orm) Tradable
Power
Allowance










ExteriorLightingZone
BaseSiteAllowance

TradablePowerAllowance
ExteriorInstalledLightingPower
ID Luminairedescription(includingnumberoflampsperfixture,wattsperlamp,
typeofballast,typeoffixture)
Numberof
Luminaires
Watts/
Luminaire
Total
Watts












Total ExteriorLightingPower
*Ifadditionalspaceisrequiredtoprovidefurtherinformation,pleaseattachaseparatesheet(s)ofpaper.
**Iftradeoffsorexceptionsareusedattachcalculations.
ASHRAE 90.1‐2010 & SB‐10 ENERGY COST BUDGET (ECB) COMPLIANCE REPORT FORM 11
Proj
e
ct:
Designer
Na
m
e
:
Occupancies Floor Area
Assembly
Health/Institutional
Hotel/Motel
Light Manufacturing
Multifamily
Office
Re
s
t
aurant
Retail
School
Warehouse
Other
Total
Proposed Building Description
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
Annual Consumption Reference Building Proposed Units
Summary
(1)
Energy Building Energy
Space
He
ating
Space Cooling
HVAC Auxiliar
y
Misc.
Electr
ical
Service
Hot
Water
Interior
Lighting
Other
Other
Total Annual Energy
Total Annual Energy Cost $ > $
Total Annual CO
2
e Emissions ……………………… > ……………………….. …………….
Peak Electric Demand ……………………… > ……………………….. YES or
Building components specified in Sentence 1.1.2.3.(2) of Chapter 1 of Division 2 of SB-10
comply with the prescriptive requirements of ASHRAE 90.1-2010
□ YES
Reference Building Energy and Proposed Building Energy Consumptions are calculated
by:
Ple
as
e
spec
ify modelling
software:
D
e
scriptions
Energy
Efficiency
Features
i
n Proposed Building
Design
(2)
Reference Building Design
Proposed Building Design
Building is in compliance with mandatory requirements of sections
5.4,
6.4,
7.4,
8.4,
9.4,
and 10.4
YES
Compliance Re
sult
The design detailed in the above referenced plans complies with the mandatory requirements of the ASHRAE 90.1-2010 Standard and
the additional requirements of Supplementary Standard SB-10. The calculated proposed building energy cost (design energy cost), CO
2
emissions and peak electric demand do not exceed the calculated reference building energy cost (energy cost budget) CO
2
emissions
and peak electric demand. Therefore, this design DOES COMPLY with the ASHRAE 90.1-2010 ECB compliance methodology and the
additional requirements of Supplementary Standard SB-10.
The information submitted above is accurate to the best of my knowledge.
Signature: Name/Title:
Notes: (1) Verify with building official whether full modelling report is required to be submitted.
(2) Explain major energy saving features utilized to achieve modelled savings.
Note: Numbering is based on SI edition of ASHRAE 90.1-2010. December 23, 2013