SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 3 05.08.20
Specifications
Adaptive Power Module
Power
• 120 V~ 50/60 Hz
• 16 A maximum total input current.
• Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to
6000 V and current surges of up to 3000 A.
• Contact Lutron for ungrounded delta feed applications.
Regulatory Approvals
• Lutron Quality Systems registered to ISO 9001.2015
• cULus Listed
• NOM Certified
• ICES-5(B) / NMB-5(B)
• FCC Class B
• UL
® 924
• NEMA SSL 7A-2015
Environment
• See Mounting on page 6 for thermal specifications.
• Relative humidity: less than 90% non-condensing.
• For indoor use only.
Output Zone Ratings
• Each zone has no minimum load requirement.
• When programmed to "auto detect" mode, the unit
starts in reverse-phase and if an incompatible load is
detected, it will convert to forward-phase.
• Internal relay provides an air gap off when all zones
are off.
• One load type per zone.
• Output must not be used to control receptacles. If
controlling plug-in lamps, installation must ensure a
method of preventing non-rated loads being plugged
into the unit. An example is a dedicated receptacle
with an alternate plug load such as a Duplex Dimming
Receptacle (NTR-15-DDTR-WH) and Dimming Lamp
Plug (RP-FDU-10-).
• Output must be directly connected to the load.
• Output breakers or switches must not be used.
• Run a separate neutral for each load circuit.
A common neutral connection is not recommended.
• Unit may be powered by Ground Fault Circuit
Interrupter (GFCI) or Arc Fault Circuit Interrupter (AFCI)
if required. If using a GFCI or an AFCI incorporating
GFCI protection, maximum wire length between the
power module and the load must be less than
100 ft (30 m). Load circuit wiring (from breaker to unit
to load) must be run in its own non-metallic conduit, or
nuisance tripping may occur.
• For applications requiring 0–10 V- control, use Ten
Volt Interface (GRX-TVI) or the LQSE-4T5-120-D.
• For applications requiring higher wattage ratings, use a
power booster (PHPM-PA-120-WH).
• For dimmable loads only. For applications requiring
switching control, use a PHPM-SW-DV-WH interface
or the LQSE-4S8-120-D.
• Works up to the output current rating with all
dimmable LED drivers whose inrush current does
not exceed NEMA410 standards for electronic
ballast / driver.