SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 1 05.08.20
PRO LED+ Phase Adaptive Power Module
The DIN Power Module (DPM) family is a group of
modular products for the control of lighting loads and
motor loads.
This document describes the following product:
LQSE-4A5-120-D: 4-Zone DIN Power Module
for phase control dimming
of lighting loads
Features
PRO LED+ Phase Adaptive Power Modules can be used
in a HomeWorks system using a QSX processor.
Includes QS link for seamless integration of lights and
controls.
An auto-detect mode is available to detect and
configure forward-phase or reverse-phase dimming for
incandescent / halogen, electronic / magnetic low-voltage
and neon / cold cathode light sources.
• A locked forward-phase or reverse-phase mode
is available.
Controls dimmable LED loads. Refer to
www.lutron.com/ledtool for compatibility with dimmable
LED light sources.
NEMA SSL 7A-2015 compliant for compatibility with
solid state lighting.
RTISS technology compensates for incoming line-
voltage variations such as changes in Root Mean Square
(RMS) voltage, frequency shifts (up to ± 2% change in
frequency /second), harmonics and line noise.
RTISS-TE technology allows for true instantaneous
voltage compensation for incoming line-voltage
variations. Only operates in reverse-phase when
"voltage-comp." is enabled.
RTISS-ICM technology is able to withstand high-inrush
LEDs, bulb blowouts, and direct shorts
Provides air gap off (when all zones are off).
Integral protection for common temporary over-current
and over-voltage conditions.
LQSE-4A5-120-D
LEDs on the module provide diagnostic information.
• Buttons on the module provide override control.
• Manual Override contact closure input (CCI).
• UL
® 924 certified for use with a LUT-ELI emergency
lighting interface.
• Power failure memory automatically returns the
outputs to the levels they were set to prior to a
power outage.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 2 05.08.20
4
HN
Zn 1
Zn 2Zn 3Zn 4
Ta > 65 ˚C
Prog
120 V~ 5 A ea
1
2
3
Opt
CCI
COM
1
2
3
Def
MUX
COM
MUX
120 V~ 50 / 60 Hz
HomeWorks QS
LQSE-4T5-120-D
lutron.com
5 /16 in
8 mm
Input | Entrada
Entrée
4.4 in-lb
0.5 N
m
0-10 V -
50 mA
H
M
L
L1
+24
COM
L2
COM
CCI
V+
COM
MUX
MUX
0,28 in
7 mm
===LED | DEL
T
x
R
x
4,4 in-lb
0,5 N
m
V+
COM
MUX
MUX
HQP7-2
HomeWorks
24-36 V- 250 mA SELV NEC
®
Class 2
lutron.com +1.844.LUTRON1
+44.(0)20.7702.0657
L1: 24 V- 1.0 A L2: 24 V- 1.0 A
Notes:
1
See "Output Zone Ratings" in “Specifications” section, for specific load types ratings.
System Example
QS Link
HomeWorks
Power Module
Adaptive Power
Module
GRAFIK
Eye QS
QS Contact
Closure
Interface
HomeWorks
Panel
HomeWorks QSX
Processor
Sivoia QS
Shade / Drapery
Palladiom
Keypad
Contact Closure Input
Up to 100
total QS
devices
120 V~ Control Power
800 W Adaptive load
1
500 W Adaptive load
1
500 W Adaptive load
1
500 W Adaptive load
1
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 3 05.08.20
Specifications
Adaptive Power Module
Power
120 V~ 50/60 Hz
16 A maximum total input current.
Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to
6000 V and current surges of up to 3000 A.
• Contact Lutron for ungrounded delta feed applications.
Regulatory Approvals
Lutron Quality Systems registered to ISO 9001.2015
• cULus Listed
• NOM Certified
ICES-5(B) / NMB-5(B)
FCC Class B
• UL
® 924
• NEMA SSL 7A-2015
Environment
• See Mounting on page 6 for thermal specifications.
Relative humidity: less than 90% non-condensing.
For indoor use only.
Output Zone Ratings
Each zone has no minimum load requirement.
When programmed to "auto detect" mode, the unit
starts in reverse-phase and if an incompatible load is
detected, it will convert to forward-phase.
• Internal relay provides an air gap off when all zones
are off.
One load type per zone.
• Output must not be used to control receptacles. If
controlling plug-in lamps, installation must ensure a
method of preventing non-rated loads being plugged
into the unit. An example is a dedicated receptacle
with an alternate plug load such as a Duplex Dimming
Receptacle (NTR-15-DDTR-WH) and Dimming Lamp
Plug (RP-FDU-10-).
Output must be directly connected to the load.
• Output breakers or switches must not be used.
• Run a separate neutral for each load circuit.
A common neutral connection is not recommended.
Unit may be powered by Ground Fault Circuit
Interrupter (GFCI) or Arc Fault Circuit Interrupter (AFCI)
if required. If using a GFCI or an AFCI incorporating
GFCI protection, maximum wire length between the
power module and the load must be less than
100 ft (30 m). Load circuit wiring (from breaker to unit
to load) must be run in its own non-metallic conduit, or
nuisance tripping may occur.
• For applications requiring 0–10 V- control, use Ten
Volt Interface (GRX-TVI) or the LQSE-4T5-120-D.
• For applications requiring higher wattage ratings, use a
power booster (PHPM-PA-120-WH).
For dimmable loads only. For applications requiring
switching control, use a PHPM-SW-DV-WH interface
or the LQSE-4S8-120-D.
• Works up to the output current rating with all
dimmable LED drivers whose inrush current does
not exceed NEMA410 standards for electronic
ballast / driver.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 4 05.08.20
Specifications (continued)
Output Zone Ratings (continued)
No Derating is required when using a Lutron panel. See Lutron Specification Submittals 3691055 or 3691106 at
www.lutron.com
No Derating is required if all the conditions below are met:
– Calibration point maximum is 158 ºF (70 ºC)
Room ambient temperature is between 32 ºF and 86 ºF (0 ºC and 30 ºC)
Panel ambient temperature is between 32 ºF and 122 ºF (0 ºC and 50 ºC)
100 W Derating is required on all zones for a single module in a single non-ventilated DIN enclosure if:
The room ambient temperature is between 86 ºF and 104 ºF (30 ºC and 40 ºC)
200 W Derating is required on all zones for multiple row non-ventilated DIN enclosure if:
The room ambient temperature is between 86 ºF and 104 ºF (30 ºC and 40 ºC)
Each zone is rated for the following wattage and load types
A, B
:
Load Type
Zone 1 Rating Zone 2, 3 and 4 Rating (per zone)
No Derating
100 W
Derating
200 W
Derating No Derating
100 W
Derating
200 W
Derating
LED (reverse-phase)
B
6.6 A 5.8 A 5 A 4.2 A 3.3 A 2.5 A
Lutron Hi-lume A-series LTE
F
4.0 A (20 drivers
maximum)
3.2 A (20 drivers
maximum)
2.4 A (20 drivers
maximum)
3.0 A (13 drivers
maximum)
2.2 A (13 drivers
maximum)
1.4 A (13 drivers
maximum)
LED SSL7A-2015 (forward-phase)
E
400 W 400 W 400 W 200 W 200 W 200 W
Incandescent / Halogen, ELV 800 W 700 W 600 W 500 W 400 W 300 W
Neon / Cold Cathode, MLV
D
800 VA (525 W
C
) 700 VA (525 W
C
) 600 VA (450 W
C
) 500 VA (375 W
C
) 400 VA (300 W
C
) 300 VA (225 W
C
)
A
Additional load type options are available in the HomeWorks software suite, some may require an interface. Contact Lutron for details.
B
Works with all dimmable LED drivers whose inrush current does not exceed NEMA410 standards for electronic ballast/drivers. Refer to
www.lutron.com/ledtool for specific LED compatibility information and recommended LED light sources.
C
Actual lamp wattage.
D
Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1.
E
Complies with SSL7A-2015 when configured in the HomeWorks software suite to LED forward phase with low-end trim set to 10% and high-end trim set
to 90%.
F
Load type must be set to "Hi-lume 1% 2-Wire LTE LED", with low-end trim = 32% and high-end trim = 78%. Setting the proper trim and load type is
necessary to ensure optimal performance and 1% dimming capability.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 5 05.08.20
Specifications (continued)
Terminals (Torque, wire gauge & type ratings)
Mains wiring: 5 in-lbs (0.6 N•m)
14 AWG to 10 AWG (2.5 mm² to 4.0 mm²)
(single wire, solid or stranded)
Zone wiring: 5 in-lbs (0.6 N•m)
14 AWG to 10 AWG (2.5 mm² to 4.0 mm²)
(single wire, solid or stranded)
CCI wiring: 5 in-lbs (0.6 N•m)
20 AWG to 10 AWG (0.5 mm² to 4.0 mm²)
(single wire, solid or stranded)
20 AWG to 16 AWG (0.5 mm² to 1.5 mm²)
(two wires, solid or stranded)
QS Link: 5 in-lbs (0.6 N•m)
Power (terminal 1):
22AWG to 12AWG (0.25mm
2
to 2.5mm
2
)
(single wire, solid or stranded)
22 AWG to 18 AWG (0.25mm
2
to 1mm
2
)
(two wires, solid or stranded)
Data (terminals 3 and 4):
1 pair, twisted and shielded,
22 AWG to 12 AWG (0.25mm
2
to 2.5mm
2
)
(single wire, solid or stranded)
22 AWG to 18 AWG (0.25mm
2
to 1mm
2
)
(two wires, solid or stranded)
Out of Box Functionality
This section describes the default functionality when
the unit is first installed.
Manual Override Contact Closure Input (CCI)
When the CCI is open, the unit will enter Manual
Override Mode, which will turn on all loads to their
manual override level and disable control of local
zones and QS devices.
When the CCI is closed or jumpered, zones will
return to the settings or levels they were at prior to
entering manual override mode.
Note: Unit will process any sensor events received
while in manual override mode after it exits manual
override mode.
Normal Mode Operation
By default each zone is set to an Auto Detect load
type with ON and OFF control only. Each zone will
turn load ON or OFF until it is configured via unit
programming.
Zone and raise/lower buttons on the unit can be
used to:
– Turn loads ON and OFF.
– Dim loads up and down.
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 6 05.08.20
Mounting
Unit is 12 DIN modules wide, 8.5 in (216 mm).
Mount in a Lutron DIN panel (see Lutron Specification
Submittal 3691055 or 3691106 at www.lutron.com)
or in an IP20 (minimum) or NEMA Type 1 (minimum)
enclosure with an integrated DIN rail (please refer to
Lutron P/N 048466 at www.lutron.com).
Mount unit in orientation shown.
Mount to DIN rail by pressing unit onto rail with
clips locked. To remove from rail, unlock clips using
a screwdriver.
Mount in an accessible and serviceable location.
Unit generates heat, maximum 75 BTUs / Hour.
Mount unit such that all the conditions below are met:
Room ambient temperature is between 32 ºF and 86 ºF
(0 ºC and 30 ºC)
Temperature inside mounting panel, within 0.8 in
(20 mm) of unit, is between 32 ºF and 122 ºF
(0 ºC and 50 ºC)
Calibration point maximum: 158 ºF (70 ºC)
Unlocked
4 mounting clips on unit
Locked
Mechanical Dimensions
Front View
3.54 in
(90 mm)
8.50 in
(216 mm)
Left Side View
Calibration
point
3.54 in
(90 mm)
2.17 in
(55 mm)
2.75 in
(70 mm)
2.99 in
(76 mm)
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 7 05.08.20
Overview of Wiring Terminals
QS
Link
Mains
Input
Load
Neutrals
Contact
Closure
Input (CCI)
Phase Adaptive Outputs
Zone
1
Zone
4
Zone
2
Zone
3
Mains
Wiring
L
L
N N N N N
DL1 DL2 DL3 DL4
CCI
COM
MUX
COM
MUX
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 8 05.08.20
Verify Wiring
Apply power to loads to identify any load or wiring faults
prior to connecting loads to unit.
Reference the Lutron panel spec sheets 3691055
and 3691106 at www.lutron.com for alternate wiring
verification method.
To verify wiring:
1. Turn off power.
2. Connect loads directly to Line / Hot to bypass
the unit and protect it from wiring faults.
3. Apply power, ensure the desired loads are
powered and properly wired.
4. Turn off power and connect loads to DL
terminals on unit for normal operation.
Neutral
Line / Hot
120 V~
Earth
L
L
N N N N N
DL1 DL2 DL3 DL4
CCI
COM
MUX
COM
MUX
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 9 05.08.20
Wiring from Distribution to Adaptive Power Module
• Turn off all circuit breakers or isolators feeding the
Adaptive Power Module at distribution panel.
• Run line / hot, neutral, and earth (
) wires from a
120 V~ 50/60 Hz feed to the power module.
Run a separate neutral for each load circuit.
Mains Wiring and NECR Class 2 Separation
• Follow appropriate local and national codes to ensure
proper separation.
Dim Hot
Neutral
Zone 1 Example
Mains Voltage Wiring
Load
Earth
Neutral
Line / Hot
Distribution
Panel
(120 V~)
L L
N N N N N
DL1 DL2 DL3 DL4
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 10 05.08.20
NECR Class 2 Contact Closure Input
• Contact Closure Input (CCI) wiring is
NEC
® Class 2.
• Follow all applicable national and local codes for
proper circuit separation and protection.
• Turn off all breakers or isolators feeding the
unit at distribution panel before servicing unit.
The CCI is a local control only and cannot control
other units over the QS link. A maximum of 32 units
may be connected in parallel to a Manual Override
device if the event is intended to affect multiple
devices.
• When in manual override mode, all zone outputs will
be at their programmed emergency light level
(configurable for each zone, default is 100%).
All sensors and controls are locked out.
• Contact closure input is normally closed (NC). The
unit is shipped with a jumper pre-installed.
Note: The unit will default to Manual Override Mode
if the CCI is left open. If no Manual Override Contact
Closure Input is required, leave the wire jumper in the
CCI terminals.
H
M
L
QSNE-4A-D
DIN Rail Power Module
230 V~ 50 / 60 Hz 10 A
www.lutron.com
+44.(0)20.7702.0657
Input
S1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
Def
Option
H
M
L
QSNE-4A-D
DIN Rail Power Module
230 V~ 50 / 60 Hz 10 A
www.lutron.com
+44.(0)20.7702.0657
Input
S1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
Def
Option
CCI
Common
Wiring: Contact Closure Input
Note: Shown with
pre-installed jumper.
CCI
COM
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3691126b 11 05.08.20
Wiring: QS Link
QS Link NECR Class 2 Wiring
• Follow all applicable national and local codes for proper
circuit separation and protection.
• Link communicates using NECR Class2 wiring.
• Wiring may be daisy chained or T-tapped.
• Do NOT connect terminal 2.
(1) COM
(2) Do Not Connect Teminal 2
1
(3) MUX
(4) MUX
Palladiom
Keypads
Palladiom
Keypads
QSE-CI-DMX
QSE-CI-DMX
Daisy-Chain Wiring Example
T-Tap Wiring Example
1
Unit does not consume or supply PDUs on
the QS link. Do not connect the 24 V- wire
to unit.
Note: 24 V- wire must bypass the unit
if other devices on the link consume
PDUs.
)Lutron, Lutron, GRAFIK Eye, Hi-lume, HomeWorks,
Palladiom, RTISS Equipped, RTISS-TE, and Sivoia are
trademarks or registered trademarks of Lutron Electronics Co.,
Inc. in the US and/or other countries.
All product names, logos, and brands are property of their
respective owners.
QS Link Wiring Options
Control
Link
Length
Wire Gauge (for terminals)
Available from
Lutron
in one cable:
Less
than
500ft
(153m)
Power (terminals 1 and 2):
1 pair 18AWG (1.0mm
2
)
GRX-CBL-346S
Data (terminals 3 and 4):
1 pair 22AWG (0.5mm
2
), twisted
and shielded*
500ft
(153m)
to
2000ft
(610m)
Power (terminals 1 and 2):
1 pair 12AWG (4.0mm
2
)
GRX-CBL-46L
Data (terminals 3 and 4):
1 pair 22AWG (0.5mm
2
), twisted
and shielded*
MUX
COM
MUX
11